.1.3,RFC1155-SMI::org,,,,,,
.1.3.6,RFC1155-SMI::dod,,,,,,
.1.3.6.1,RFC1155-SMI::internet,,,,,,
.1.3.6.1.1,RFC1155-SMI::directory,,,,,,
.1.3.6.1.2,RFC1155-SMI::mgmt,,,,,,
.1.3.6.1.2.1,SNMPv2-SMI::mib-2,,,,,,
.1.3.6.1.2.1.1,RFC1213-MIB::system,,,,,,
.1.3.6.1.2.1.1.1,RFC1213-MIB::sysDescr,OCTET,read-only,,mandatory,,A textual description of the entity. This value should include the full name and version identification of the system's hardware type, software operating-system, and networking software. It is mandatory that this only contain printable ASCII characters.
.1.3.6.1.2.1.1.2,RFC1213-MIB::sysObjectID,OBJECT,read-only,,mandatory,,The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining `what kind of box' is being managed. For example, if vendor `Flintstones, Inc.' was assigned the subtree 1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'.
.1.3.6.1.2.1.1.3,RFC1213-MIB::sysUpTime,TimeTicks,read-only,,mandatory,,The time (in hundredths of a second) since the network management portion of the system was last re-initialized.
.1.3.6.1.2.1.1.4,RFC1213-MIB::sysContact,OCTET,read-write,,mandatory,,The textual identification of the contact person for this managed node, together with information on how to contact this person.
.1.3.6.1.2.1.1.5,RFC1213-MIB::sysName,OCTET,read-write,,mandatory,,An administratively-assigned name for this managed node. By convention, this is the node's fully-qualified domain name.
.1.3.6.1.2.1.1.6,RFC1213-MIB::sysLocation,OCTET,read-write,,mandatory,,The physical location of this node (e.g., `telephone closet, 3rd floor').
.1.3.6.1.2.1.1.7,RFC1213-MIB::sysServices,INTEGER,read-only,,mandatory,,A value which indicates the set of services that this entity primarily offers. The value is a sum. This sum initially takes the value zero, Then, for each layer, L, in the range 1 through 7, that this node performs transactions for, 2 raised to (L - 1) is added to the sum. For example, a node which performs primarily routing functions would have a value of 4 (2^(3-1)). In contrast, a node which is a host offering application services would have a value of 72 (2^(4-1) + 2^(7-1)). Note that in the context of the Internet suite of protocols, values should be calculated accordingly: layer functionality 1 physical (e.g., repeaters) 2 datalink/subnetwork (e.g., bridges) 3 internet (e.g., IP gateways) 4 end-to-end (e.g., IP hosts) 7 applications (e.g., mail relays) For systems including OSI protocols, layers 5 and 6 may also be counted.
.1.3.6.1.2.1.2,RFC1213-MIB::interfaces,,,,,,
.1.3.6.1.2.1.2.1,RFC1213-MIB::ifNumber,INTEGER,read-only,,mandatory,,The number of network interfaces (regardless of their current state) present on this system.
.1.3.6.1.2.1.2.2,RFC1213-MIB::ifTable,,not-accessible,,mandatory,,A list of interface entries. The number of entries is given by the value of ifNumber.
.1.3.6.1.2.1.2.2.1,RFC1213-MIB::ifEntry,,not-accessible,ifIndex,mandatory,,An interface entry containing objects at the subnetwork layer and below for a particular interface.
.1.3.6.1.2.1.2.2.1.1,RFC1213-MIB::ifIndex,INTEGER,read-only,,mandatory,,A unique value for each interface. Its value ranges between 1 and the value of ifNumber. The value for each interface must remain constant at least from one re-initialization of the entity's network management system to the next re- initialization.
.1.3.6.1.2.1.2.2.1.2,RFC1213-MIB::ifDescr,OCTET,read-only,,mandatory,,A textual string containing information about the interface. This string should include the name of the manufacturer, the product name and the version of the hardware interface.
.1.3.6.1.2.1.2.2.1.3,RFC1213-MIB::ifType,INTEGER,read-only,,mandatory,other(1):regular1822(2):hdh1822(3):ddnX25(4):rfc877x25(5):ethernetCsmacd(6):iso88023Csmacd(7):iso88024TokenBus(8):iso88025TokenRing(9):iso88026Man(10):starLan(11):proteon10Mbit(12):proteon80Mbit(13):hyperchannel(14):fddi(15):lapb(16):sdlc(17):ds1(18):e1(19):basicISDN(20):primaryISDN(21):propPointToPointSerial(22):ppp(23):softwareLoopback(24):eon(25):ethernet3Mbit(26):nsip(27):slip(28):ultra(29):ds3(30):sip(31):frameRelay(32):rs232(33):para(34):arcnet(35):arcnetPlus(36):atm(37):miox25(38):sonet(39):x25ple(40):iso88022llc(41):localTalk(42):smdsDxi(43):frameRelayService(44):v35(45):hssi(46):hippi(47):modem(48):aal5(49):sonetPath(50):sonetVT(51):smdsIcip(52):propVirtual(53):propMultiplexor(54):ieee80212(55):fibreChannel(56):hippiInterface(57):frameRelayInterconnect(58):aflane8023(59):aflane8025(60):cctEmul(61):fastEther(62):isdn(63):v11(64):v36(65):g703at64k(66):g703at2mb(67):qllc(68):fastEtherFX(69):channel(70):ieee80211(71):ibm370parChan(72):escon(73):dlsw(74):isdns(75):isdnu(76):lapd(77):ipSwitch(78):rsrb(79):atmLogical(80):ds0(81):ds0Bundle(82):bsc(83):async(84):cnr(85):iso88025Dtr(86):eplrs(87):arap(88):propCnls(89):hostPad(90):termPad(91):frameRelayMPI(92):x213(93):adsl(94):radsl(95):sdsl(96):vdsl(97):iso88025CRFPInt(98):myrinet(99):voiceEM(100):voiceFXO(101):voiceFXS(102):voiceEncap(103):voiceOverIp(104):atmDxi(105):atmFuni(106):atmIma(107):pppMultilinkBundle(108):ipOverCdlc(109):ipOverClaw(110):stackToStack(111):virtualIpAddress(112):mpc(113):ipOverAtm(114):iso88025Fiber(115):tdlc(116):gigabitEthernet(117):hdlc(118):lapf(119):v37(120):x25mlp(121):x25huntGroup(122):transpHdlc(123):interleave(124):fast(125):ip(126):docsCableMaclayer(127):docsCableDownstream(128):docsCableUpstream(129):a12MppSwitch(130):tunnel(131):coffee(132):ces(133):atmSubInterface(134):l2vlan(135):l3ipvlan(136):l3ipxvlan(137):digitalPowerline(138):mediaMailOverIp(139):dtm(140):dcn(141):ipForward(142):msdsl(143):ieee1394(144):if-gsn(145):dvbRccMacLayer(146):dvbRccDownstream(147):dvbRccUpstream(148):atmVirtual(149):mplsTunnel(150):srp(151):voiceOverAtm(152):voiceOverFrameRelay(153):idsl(154):compositeLink(155):ss7SigLink(156):propWirelessP2P(157):frForward(158):rfc1483(159):usb(160):ieee8023adLag(161):bgppolicyaccounting(162):frf16MfrBundle(163):h323Gatekeeper(164):h323Proxy(165):mpls(166):mfSigLink(167):hdsl2(168):shdsl(169):ds1FDL(170):pos(171):dvbAsiIn(172):dvbAsiOut(173):plc(174):nfas(175):tr008(176):gr303RDT(177):gr303IDT(178):isup(179):propDocsWirelessMaclayer(180):propDocsWirelessDownstream(181):propDocsWirelessUpstream(182):hiperlan2(183):propBWAp2Mp(184):sonetOverheadChannel(185):digitalWrapperOverheadChannel(186):aal2(187):radioMAC(188):atmRadio(189):imt(190):mvl(191):reachDSL(192):frDlciEndPt(193):atmVciEndPt(194):opticalChannel(195):opticalTransport(196):propAtm(197):voiceOverCable(198):infiniband(199):teLink(200):q2931(201):virtualTg(202):sipTg(203):sipSig(204):docsCableUpstreamChannel(205):econet(206):pon155(207):pon622(208):bridge(209):linegroup(210):voiceEMFGD(211):voiceFGDEANA(212):voiceDID(213):mpegTransport(214):sixToFour(215):gtp(216):pdnEtherLoop1(217):pdnEtherLoop2(218):opticalChannelGroup(219):homepna(220):gfp(221):ciscoISLvlan(222):actelisMetaLOOP(223):fcipLink(224):rpr(225):qam(226):lmp(227):cblVectaStar(228):docsCableMCmtsDownstream(229):adsl2(230):macSecControlledIF(231):macSecUncontrolledIF(232):aviciOpticalEther(233):atmbond(234):voiceFGDOS(235):mocaVersion1(236):ieee80216WMAN(237):adsl2plus(238):dvbRcsMacLayer(239):dvbTdm(240):dvbRcsTdma(241):x86Laps(242):wwanPP(243):wwanPP2(244):voiceEBS(245):ifPwType(246):ilan(247):pip(248):aluELP(249):gpon(250):vdsl2(251):capwapDot11Profile(252):capwapDot11Bss(253):capwapWtpVirtualRadio(254):bits(255):docsCableUpstreamRfPort(256):cableDownstreamRfPort(257):vmwareVirtualNic(258):ieee802154(259):otnOdu(260):otnOtu(261):ifVfiType(262):g9981(263):g9982(264):g9983(265):aluEpon(266):aluEponOnu(267):aluEponPhysicalUni(268):aluEponLogicalLink(269):aluGponOnu(270):aluGponPhysicalUni(271):vmwareNicTeam(272):docsOfdmDownstream(277):docsOfdmaUpstream(278):gfast(279):sdci(280):xboxWireless(281):fastdsl(282):docsCableScte55d1FwdOob(283):docsCableScte55d1RetOob(284):docsCableScte55d2DsOob(285):docsCableScte55d2UsOob(286):docsCableNdf(287):docsCableNdr(288):ptm(289):ghn(290):otnOtsi(291):otnOtuc(292):otnOduc(293):otnOtsig(294):microwaveCarrierTermination(295):microwaveRadioLinkTerminal(296),The type of interface, distinguished according to the physical/link protocol(s) immediately `below' the network layer in the protocol stack.
.1.3.6.1.2.1.2.2.1.4,RFC1213-MIB::ifMtu,INTEGER,read-only,,mandatory,,The size of the largest datagram which can be sent/received on the interface, specified in octets. For interfaces that are used for transmitting network datagrams, this is the size of the largest network datagram that can be sent on the interface.
.1.3.6.1.2.1.2.2.1.5,RFC1213-MIB::ifSpeed,Gauge32,read-only,,mandatory,,An estimate of the interface's current bandwidth in bits per second. For interfaces which do not vary in bandwidth or for those where no accurate estimation can be made, this object should contain the nominal bandwidth.
.1.3.6.1.2.1.2.2.1.6,RFC1213-MIB::ifPhysAddress,OCTET,read-only,,mandatory,,The interface's address at the protocol layer immediately `below' the network layer in the protocol stack. For interfaces which do not have such an address (e.g., a serial line), this object should contain an octet string of zero length.
.1.3.6.1.2.1.2.2.1.7,RFC1213-MIB::ifAdminStatus,INTEGER,read-write,,mandatory,up(1):down(2):testing(3),The desired state of the interface. The testing(3) state indicates that no operational packets can be passed.
.1.3.6.1.2.1.2.2.1.8,RFC1213-MIB::ifOperStatus,INTEGER,read-only,,mandatory,up(1):down(2):testing(3),The current operational state of the interface. The testing(3) state indicates that no operational packets can be passed.
.1.3.6.1.2.1.2.2.1.9,RFC1213-MIB::ifLastChange,TimeTicks,read-only,,mandatory,,The value of sysUpTime at the time the interface entered its current operational state. If the current state was entered prior to the last re- initialization of the local network management subsystem, then this object contains a zero value.
.1.3.6.1.2.1.2.2.1.10,RFC1213-MIB::ifInOctets,Counter32,read-only,,mandatory,,The total number of octets received on the interface, including framing characters.
.1.3.6.1.2.1.2.2.1.11,RFC1213-MIB::ifInUcastPkts,Counter32,read-only,,mandatory,,The number of subnetwork-unicast packets delivered to a higher-layer protocol.
.1.3.6.1.2.1.2.2.1.12,RFC1213-MIB::ifInNUcastPkts,Counter32,read-only,,mandatory,,The number of non-unicast (i.e., subnetwork- broadcast or subnetwork-multicast) packets delivered to a higher-layer protocol.
.1.3.6.1.2.1.2.2.1.13,RFC1213-MIB::ifInDiscards,Counter32,read-only,,mandatory,,The number of inbound packets which were chosen to be discarded even though no errors had been detected to prevent their being deliverable to a higher-layer protocol. One possible reason for discarding such a packet could be to free up buffer space.
.1.3.6.1.2.1.2.2.1.14,RFC1213-MIB::ifInErrors,Counter32,read-only,,mandatory,,The number of inbound packets that contained errors preventing them from being deliverable to a higher-layer protocol.
.1.3.6.1.2.1.2.2.1.15,RFC1213-MIB::ifInUnknownProtos,Counter32,read-only,,mandatory,,The number of packets received via the interface which were discarded because of an unknown or unsupported protocol.
.1.3.6.1.2.1.2.2.1.16,RFC1213-MIB::ifOutOctets,Counter32,read-only,,mandatory,,The total number of octets transmitted out of the interface, including framing characters.
.1.3.6.1.2.1.2.2.1.17,RFC1213-MIB::ifOutUcastPkts,Counter32,read-only,,mandatory,,The total number of packets that higher-level protocols requested be transmitted to a subnetwork-unicast address, including those that were discarded or not sent.
.1.3.6.1.2.1.2.2.1.18,RFC1213-MIB::ifOutNUcastPkts,Counter32,read-only,,mandatory,,The total number of packets that higher-level protocols requested be transmitted to a non- unicast (i.e., a subnetwork-broadcast or subnetwork-multicast) address, including those that were discarded or not sent.
.1.3.6.1.2.1.2.2.1.19,RFC1213-MIB::ifOutDiscards,Counter32,read-only,,mandatory,,The number of outbound packets which were chosen to be discarded even though no errors had been detected to prevent their being transmitted. One possible reason for discarding such a packet could be to free up buffer space.
.1.3.6.1.2.1.2.2.1.20,RFC1213-MIB::ifOutErrors,Counter32,read-only,,mandatory,,The number of outbound packets that could not be transmitted because of errors.
.1.3.6.1.2.1.2.2.1.21,RFC1213-MIB::ifOutQLen,Gauge32,read-only,,mandatory,,The length of the output packet queue (in packets).
.1.3.6.1.2.1.2.2.1.22,RFC1213-MIB::ifSpecific,OBJECT,read-only,,mandatory,,A reference to MIB definitions specific to the particular media being used to realize the interface. For example, if the interface is realized by an ethernet, then the value of this object refers to a document defining objects specific to ethernet. If this information is not present, its value should be set to the OBJECT IDENTIFIER { 0 0 }, which is a syntatically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value.
.1.3.6.1.2.1.3,RFC1213-MIB::at,,,,,,
.1.3.6.1.2.1.3.1,RFC1213-MIB::atTable,,not-accessible,,deprecated,,The Address Translation tables contain the NetworkAddress to `physical' address equivalences. Some interfaces do not use translation tables for determining address equivalences (e.g., DDN-X.25 has an algorithmic method); if all interfaces are of this type, then the Address Translation table is empty, i.e., has zero entries.
.1.3.6.1.2.1.3.1.1,RFC1213-MIB::atEntry,,not-accessible,atIfIndex:atNetAddress,deprecated,,Each entry contains one NetworkAddress to `physical' address equivalence.
.1.3.6.1.2.1.3.1.1.1,RFC1213-MIB::atIfIndex,INTEGER,read-write,,deprecated,,The interface on which this entry's equivalence is effective. The interface identified by a particular value of this index is the same interface as identified by the same value of ifIndex.
.1.3.6.1.2.1.3.1.1.2,RFC1213-MIB::atPhysAddress,OCTET,read-write,,deprecated,,The media-dependent `physical' address. Setting this object to a null string (one of zero length) has the effect of invaliding the corresponding entry in the atTable object. That is, it effectively dissasociates the interface identified with said entry from the mapping identified with said entry. It is an implementation-specific matter as to whether the agent removes an invalidated entry from the table. Accordingly, management stations must be prepared to receive tabular information from agents that corresponds to entries not currently in use. Proper interpretation of such entries requires examination of the relevant atPhysAddress object.
.1.3.6.1.2.1.3.1.1.3,RFC1213-MIB::atNetAddress,NetworkAddress,read-write,,deprecated,,The NetworkAddress (e.g., the IP address) corresponding to the media-dependent `physical' address.
.1.3.6.1.2.1.4,RFC1213-MIB::ip,,,,,,
.1.3.6.1.2.1.4.1,RFC1213-MIB::ipForwarding,INTEGER,read-write,,mandatory,forwarding(1):not-forwarding(2),The indication of whether this entity is acting as an IP gateway in respect to the forwarding of datagrams received by, but not addressed to, this entity. IP gateways forward datagrams. IP hosts do not (except those source-routed via the host). Note that for some managed nodes, this object may take on only a subset of the values possible. Accordingly, it is appropriate for an agent to return a `badValue' response if a management station attempts to change this object to an inappropriate value.
.1.3.6.1.2.1.4.2,RFC1213-MIB::ipDefaultTTL,INTEGER,read-write,,mandatory,,The default value inserted into the Time-To-Live field of the IP header of datagrams originated at this entity, whenever a TTL value is not supplied by the transport layer protocol.
.1.3.6.1.2.1.4.3,RFC1213-MIB::ipInReceives,Counter32,read-only,,mandatory,,The total number of input datagrams received from interfaces, including those received in error.
.1.3.6.1.2.1.4.4,RFC1213-MIB::ipInHdrErrors,Counter32,read-only,,mandatory,,The number of input datagrams discarded due to errors in their IP headers, including bad checksums, version number mismatch, other format errors, time-to-live exceeded, errors discovered in processing their IP options, etc.
.1.3.6.1.2.1.4.5,RFC1213-MIB::ipInAddrErrors,Counter32,read-only,,mandatory,,The number of input datagrams discarded because the IP address in their IP header's destination field was not a valid address to be received at this entity. This count includes invalid addresses (e.g., 0.0.0.0) and addresses of unsupported Classes (e.g., Class E). For entities which are not IP Gateways and therefore do not forward datagrams, this counter includes datagrams discarded because the destination address was not a local address.
.1.3.6.1.2.1.4.6,RFC1213-MIB::ipForwDatagrams,Counter32,read-only,,mandatory,,The number of input datagrams for which this entity was not their final IP destination, as a result of which an attempt was made to find a route to forward them to that final destination. In entities which do not act as IP Gateways, this counter will include only those packets which were Source-Routed via this entity, and the Source- Route option processing was successful.
.1.3.6.1.2.1.4.7,RFC1213-MIB::ipInUnknownProtos,Counter32,read-only,,mandatory,,The number of locally-addressed datagrams received successfully but discarded because of an unknown or unsupported protocol.
.1.3.6.1.2.1.4.8,RFC1213-MIB::ipInDiscards,Counter32,read-only,,mandatory,,The number of input IP datagrams for which no problems were encountered to prevent their continued processing, but which were discarded (e.g., for lack of buffer space). Note that this counter does not include any datagrams discarded while awaiting re-assembly.
.1.3.6.1.2.1.4.9,RFC1213-MIB::ipInDelivers,Counter32,read-only,,mandatory,,The total number of input datagrams successfully delivered to IP user-protocols (including ICMP).
.1.3.6.1.2.1.4.10,RFC1213-MIB::ipOutRequests,Counter32,read-only,,mandatory,,The total number of IP datagrams which local IP user-protocols (including ICMP) supplied to IP in requests for transmission. Note that this counter does not include any datagrams counted in ipForwDatagrams.
.1.3.6.1.2.1.4.11,RFC1213-MIB::ipOutDiscards,Counter32,read-only,,mandatory,,The number of output IP datagrams for which no problem was encountered to prevent their transmission to their destination, but which were discarded (e.g., for lack of buffer space). Note that this counter would include datagrams counted in ipForwDatagrams if any such packets met this (discretionary) discard criterion.
.1.3.6.1.2.1.4.12,RFC1213-MIB::ipOutNoRoutes,Counter32,read-only,,mandatory,,The number of IP datagrams discarded because no route could be found to transmit them to their destination. Note that this counter includes any packets counted in ipForwDatagrams which meet this `no-route' criterion. Note that this includes any datagarms which a host cannot route because all of its default gateways are down.
.1.3.6.1.2.1.4.13,RFC1213-MIB::ipReasmTimeout,INTEGER,read-only,,mandatory,,The maximum number of seconds which received fragments are held while they are awaiting reassembly at this entity.
.1.3.6.1.2.1.4.14,RFC1213-MIB::ipReasmReqds,Counter32,read-only,,mandatory,,The number of IP fragments received which needed to be reassembled at this entity.
.1.3.6.1.2.1.4.15,RFC1213-MIB::ipReasmOKs,Counter32,read-only,,mandatory,,The number of IP datagrams successfully re- assembled.
.1.3.6.1.2.1.4.16,RFC1213-MIB::ipReasmFails,Counter32,read-only,,mandatory,,The number of failures detected by the IP re- assembly algorithm (for whatever reason: timed out, errors, etc). Note that this is not necessarily a count of discarded IP fragments since some algorithms (notably the algorithm in RFC 815) can lose track of the number of fragments by combining them as they are received.
.1.3.6.1.2.1.4.17,RFC1213-MIB::ipFragOKs,Counter32,read-only,,mandatory,,The number of IP datagrams that have been successfully fragmented at this entity.
.1.3.6.1.2.1.4.18,RFC1213-MIB::ipFragFails,Counter32,read-only,,mandatory,,The number of IP datagrams that have been discarded because they needed to be fragmented at this entity but could not be, e.g., because their Don't Fragment flag was set.
.1.3.6.1.2.1.4.19,RFC1213-MIB::ipFragCreates,Counter32,read-only,,mandatory,,The number of IP datagram fragments that have been generated as a result of fragmentation at this entity.
.1.3.6.1.2.1.4.20,RFC1213-MIB::ipAddrTable,,not-accessible,,mandatory,,The table of addressing information relevant to this entity's IP addresses.
.1.3.6.1.2.1.4.20.1,RFC1213-MIB::ipAddrEntry,,not-accessible,ipAdEntAddr,mandatory,,The addressing information for one of this entity's IP addresses.
.1.3.6.1.2.1.4.20.1.1,RFC1213-MIB::ipAdEntAddr,IpAddress,read-only,,mandatory,,The IP address to which this entry's addressing information pertains.
.1.3.6.1.2.1.4.20.1.2,RFC1213-MIB::ipAdEntIfIndex,INTEGER,read-only,,mandatory,,The index value which uniquely identifies the interface to which this entry is applicable. The interface identified by a particular value of this index is the same interface as identified by the same value of ifIndex.
.1.3.6.1.2.1.4.20.1.3,RFC1213-MIB::ipAdEntNetMask,IpAddress,read-only,,mandatory,,The subnet mask associated with the IP address of this entry. The value of the mask is an IP address with all the network bits set to 1 and all the hosts bits set to 0.
.1.3.6.1.2.1.4.20.1.4,RFC1213-MIB::ipAdEntBcastAddr,INTEGER,read-only,,mandatory,,The value of the least-significant bit in the IP broadcast address used for sending datagrams on the (logical) interface associated with the IP address of this entry. For example, when the Internet standard all-ones broadcast address is used, the value will be 1. This value applies to both the subnet and network broadcasts addresses used by the entity on this (logical) interface.
.1.3.6.1.2.1.4.20.1.5,RFC1213-MIB::ipAdEntReasmMaxSize,INTEGER,read-only,,mandatory,,The size of the largest IP datagram which this entity can re-assemble from incoming IP fragmented datagrams received on this interface.
.1.3.6.1.2.1.4.21,RFC1213-MIB::ipRouteTable,,not-accessible,,mandatory,,This entity's IP Routing table.
.1.3.6.1.2.1.4.21.1,RFC1213-MIB::ipRouteEntry,,not-accessible,ipRouteDest,mandatory,,A route to a particular destination.
.1.3.6.1.2.1.4.21.1.1,RFC1213-MIB::ipRouteDest,IpAddress,read-write,,mandatory,,The destination IP address of this route. An entry with a value of 0.0.0.0 is considered a default route. Multiple routes to a single destination can appear in the table, but access to such multiple entries is dependent on the table- access mechanisms defined by the network management protocol in use.
.1.3.6.1.2.1.4.21.1.2,RFC1213-MIB::ipRouteIfIndex,INTEGER,read-write,,mandatory,,The index value which uniquely identifies the local interface through which the next hop of this route should be reached. The interface identified by a particular value of this index is the same interface as identified by the same value of ifIndex.
.1.3.6.1.2.1.4.21.1.3,RFC1213-MIB::ipRouteMetric1,INTEGER,read-write,,mandatory,,The primary routing metric for this route. The semantics of this metric are determined by the routing-protocol specified in the route's ipRouteProto value. If this metric is not used, its value should be set to -1.
.1.3.6.1.2.1.4.21.1.4,RFC1213-MIB::ipRouteMetric2,INTEGER,read-write,,mandatory,,An alternate routing metric for this route. The semantics of this metric are determined by the routing-protocol specified in the route's ipRouteProto value. If this metric is not used, its value should be set to -1.
.1.3.6.1.2.1.4.21.1.5,RFC1213-MIB::ipRouteMetric3,INTEGER,read-write,,mandatory,,An alternate routing metric for this route. The semantics of this metric are determined by the routing-protocol specified in the route's ipRouteProto value. If this metric is not used, its value should be set to -1.
.1.3.6.1.2.1.4.21.1.6,RFC1213-MIB::ipRouteMetric4,INTEGER,read-write,,mandatory,,An alternate routing metric for this route. The semantics of this metric are determined by the routing-protocol specified in the route's ipRouteProto value. If this metric is not used, its value should be set to -1.
.1.3.6.1.2.1.4.21.1.7,RFC1213-MIB::ipRouteNextHop,IpAddress,read-write,,mandatory,,The IP address of the next hop of this route. (In the case of a route bound to an interface which is realized via a broadcast media, the value of this field is the agent's IP address on that interface.)
.1.3.6.1.2.1.4.21.1.8,RFC1213-MIB::ipRouteType,INTEGER,read-write,,mandatory,other(1):invalid(2):direct(3):indirect(4),The type of route. Note that the values direct(3) and indirect(4) refer to the notion of direct and indirect routing in the IP architecture. Setting this object to the value invalid(2) has the effect of invalidating the corresponding entry in the ipRouteTable object. That is, it effectively dissasociates the destination identified with said entry from the route identified with said entry. It is an implementation-specific matter as to whether the agent removes an invalidated entry from the table. Accordingly, management stations must be prepared to receive tabular information from agents that corresponds to entries not currently in use. Proper interpretation of such entries requires examination of the relevant ipRouteType object.
.1.3.6.1.2.1.4.21.1.9,RFC1213-MIB::ipRouteProto,INTEGER,read-only,,mandatory,other(1):local(2):netmgmt(3):icmp(4):egp(5):ggp(6):hello(7):rip(8):is-is(9):es-is(10):ciscoIgrp(11):bbnSpfIgp(12):ospf(13):bgp(14),The routing mechanism via which this route was learned. Inclusion of values for gateway routing protocols is not intended to imply that hosts should support those protocols.
.1.3.6.1.2.1.4.21.1.10,RFC1213-MIB::ipRouteAge,INTEGER,read-write,,mandatory,,The number of seconds since this route was last updated or otherwise determined to be correct. Note that no semantics of `too old' can be implied except through knowledge of the routing protocol by which the route was learned.
.1.3.6.1.2.1.4.21.1.11,RFC1213-MIB::ipRouteMask,IpAddress,read-write,,mandatory,,Indicate the mask to be logical-ANDed with the destination address before being compared to the value in the ipRouteDest field. For those systems that do not support arbitrary subnet masks, an agent constructs the value of the ipRouteMask by determining whether the value of the correspondent ipRouteDest field belong to a class-A, B, or C network, and then using one of: mask network 255.0.0.0 class-A 255.255.0.0 class-B 255.255.255.0 class-C If the value of the ipRouteDest is 0.0.0.0 (a default route), then the mask value is also 0.0.0.0. It should be noted that all IP routing subsystems implicitly use this mechanism.
.1.3.6.1.2.1.4.21.1.12,RFC1213-MIB::ipRouteMetric5,INTEGER,read-write,,mandatory,,An alternate routing metric for this route. The semantics of this metric are determined by the routing-protocol specified in the route's ipRouteProto value. If this metric is not used, its value should be set to -1.
.1.3.6.1.2.1.4.21.1.13,RFC1213-MIB::ipRouteInfo,OBJECT,read-only,,mandatory,,A reference to MIB definitions specific to the particular routing protocol which is responsible for this route, as determined by the value specified in the route's ipRouteProto value. If this information is not present, its value should be set to the OBJECT IDENTIFIER { 0 0 }, which is a syntatically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value.
.1.3.6.1.2.1.4.22,RFC1213-MIB::ipNetToMediaTable,,not-accessible,,mandatory,,The IP Address Translation table used for mapping from IP addresses to physical addresses.
.1.3.6.1.2.1.4.22.1,RFC1213-MIB::ipNetToMediaEntry,,not-accessible,ipNetToMediaIfIndex:ipNetToMediaNetAddress,mandatory,,Each entry contains one IpAddress to `physical' address equivalence.
.1.3.6.1.2.1.4.22.1.1,RFC1213-MIB::ipNetToMediaIfIndex,INTEGER,read-write,,mandatory,,The interface on which this entry's equivalence is effective. The interface identified by a particular value of this index is the same interface as identified by the same value of ifIndex.
.1.3.6.1.2.1.4.22.1.2,RFC1213-MIB::ipNetToMediaPhysAddress,OCTET,read-write,,mandatory,,The media-dependent `physical' address.
.1.3.6.1.2.1.4.22.1.3,RFC1213-MIB::ipNetToMediaNetAddress,IpAddress,read-write,,mandatory,,The IpAddress corresponding to the media- dependent `physical' address.
.1.3.6.1.2.1.4.22.1.4,RFC1213-MIB::ipNetToMediaType,INTEGER,read-write,,mandatory,other(1):invalid(2):dynamic(3):static(4),The type of mapping. Setting this object to the value invalid(2) has the effect of invalidating the corresponding entry in the ipNetToMediaTable. That is, it effectively dissasociates the interface identified with said entry from the mapping identified with said entry. It is an implementation-specific matter as to whether the agent removes an invalidated entry from the table. Accordingly, management stations must be prepared to receive tabular information from agents that corresponds to entries not currently in use. Proper interpretation of such entries requires examination of the relevant ipNetToMediaType object.
.1.3.6.1.2.1.4.23,RFC1213-MIB::ipRoutingDiscards,Counter32,read-only,,mandatory,,The number of routing entries which were chosen to be discarded even though they are valid. One possible reason for discarding such an entry could be to free-up buffer space for other routing entries.
.1.3.6.1.2.1.5,RFC1213-MIB::icmp,,,,,,
.1.3.6.1.2.1.5.1,RFC1213-MIB::icmpInMsgs,Counter32,read-only,,mandatory,,The total number of ICMP messages which the entity received. Note that this counter includes all those counted by icmpInErrors.
.1.3.6.1.2.1.5.2,RFC1213-MIB::icmpInErrors,Counter32,read-only,,mandatory,,The number of ICMP messages which the entity received but determined as having ICMP-specific errors (bad ICMP checksums, bad length, etc.).
.1.3.6.1.2.1.5.3,RFC1213-MIB::icmpInDestUnreachs,Counter32,read-only,,mandatory,,The number of ICMP Destination Unreachable messages received.
.1.3.6.1.2.1.5.4,RFC1213-MIB::icmpInTimeExcds,Counter32,read-only,,mandatory,,The number of ICMP Time Exceeded messages received.
.1.3.6.1.2.1.5.5,RFC1213-MIB::icmpInParmProbs,Counter32,read-only,,mandatory,,The number of ICMP Parameter Problem messages received.
.1.3.6.1.2.1.5.6,RFC1213-MIB::icmpInSrcQuenchs,Counter32,read-only,,mandatory,,The number of ICMP Source Quench messages received.
.1.3.6.1.2.1.5.7,RFC1213-MIB::icmpInRedirects,Counter32,read-only,,mandatory,,The number of ICMP Redirect messages received.
.1.3.6.1.2.1.5.8,RFC1213-MIB::icmpInEchos,Counter32,read-only,,mandatory,,The number of ICMP Echo (request) messages received.
.1.3.6.1.2.1.5.9,RFC1213-MIB::icmpInEchoReps,Counter32,read-only,,mandatory,,The number of ICMP Echo Reply messages received.
.1.3.6.1.2.1.5.10,RFC1213-MIB::icmpInTimestamps,Counter32,read-only,,mandatory,,The number of ICMP Timestamp (request) messages received.
.1.3.6.1.2.1.5.11,RFC1213-MIB::icmpInTimestampReps,Counter32,read-only,,mandatory,,The number of ICMP Timestamp Reply messages received.
.1.3.6.1.2.1.5.12,RFC1213-MIB::icmpInAddrMasks,Counter32,read-only,,mandatory,,The number of ICMP Address Mask Request messages received.
.1.3.6.1.2.1.5.13,RFC1213-MIB::icmpInAddrMaskReps,Counter32,read-only,,mandatory,,The number of ICMP Address Mask Reply messages received.
.1.3.6.1.2.1.5.14,RFC1213-MIB::icmpOutMsgs,Counter32,read-only,,mandatory,,The total number of ICMP messages which this entity attempted to send. Note that this counter includes all those counted by icmpOutErrors.
.1.3.6.1.2.1.5.15,RFC1213-MIB::icmpOutErrors,Counter32,read-only,,mandatory,,The number of ICMP messages which this entity did not send due to problems discovered within ICMP such as a lack of buffers. This value should not include errors discovered outside the ICMP layer such as the inability of IP to route the resultant datagram. In some implementations there may be no types of error which contribute to this counter's value.
.1.3.6.1.2.1.5.16,RFC1213-MIB::icmpOutDestUnreachs,Counter32,read-only,,mandatory,,The number of ICMP Destination Unreachable messages sent.
.1.3.6.1.2.1.5.17,RFC1213-MIB::icmpOutTimeExcds,Counter32,read-only,,mandatory,,The number of ICMP Time Exceeded messages sent.
.1.3.6.1.2.1.5.18,RFC1213-MIB::icmpOutParmProbs,Counter32,read-only,,mandatory,,The number of ICMP Parameter Problem messages sent.
.1.3.6.1.2.1.5.19,RFC1213-MIB::icmpOutSrcQuenchs,Counter32,read-only,,mandatory,,The number of ICMP Source Quench messages sent.
.1.3.6.1.2.1.5.20,RFC1213-MIB::icmpOutRedirects,Counter32,read-only,,mandatory,,The number of ICMP Redirect messages sent. For a host, this object will always be zero, since hosts do not send redirects.
.1.3.6.1.2.1.5.21,RFC1213-MIB::icmpOutEchos,Counter32,read-only,,mandatory,,The number of ICMP Echo (request) messages sent.
.1.3.6.1.2.1.5.22,RFC1213-MIB::icmpOutEchoReps,Counter32,read-only,,mandatory,,The number of ICMP Echo Reply messages sent.
.1.3.6.1.2.1.5.23,RFC1213-MIB::icmpOutTimestamps,Counter32,read-only,,mandatory,,The number of ICMP Timestamp (request) messages sent.
.1.3.6.1.2.1.5.24,RFC1213-MIB::icmpOutTimestampReps,Counter32,read-only,,mandatory,,The number of ICMP Timestamp Reply messages sent.
.1.3.6.1.2.1.5.25,RFC1213-MIB::icmpOutAddrMasks,Counter32,read-only,,mandatory,,The number of ICMP Address Mask Request messages sent.
.1.3.6.1.2.1.5.26,RFC1213-MIB::icmpOutAddrMaskReps,Counter32,read-only,,mandatory,,The number of ICMP Address Mask Reply messages sent.
.1.3.6.1.2.1.6,RFC1213-MIB::tcp,,,,,,
.1.3.6.1.2.1.6.1,RFC1213-MIB::tcpRtoAlgorithm,INTEGER,read-only,,mandatory,other(1):constant(2):rsre(3):vanj(4),The algorithm used to determine the timeout value used for retransmitting unacknowledged octets.
.1.3.6.1.2.1.6.2,RFC1213-MIB::tcpRtoMin,INTEGER,read-only,,mandatory,,The minimum value permitted by a TCP implementation for the retransmission timeout, measured in milliseconds. More refined semantics for objects of this type depend upon the algorithm used to determine the retransmission timeout. In particular, when the timeout algorithm is rsre(3), an object of this type has the semantics of the LBOUND quantity described in RFC 793.
.1.3.6.1.2.1.6.3,RFC1213-MIB::tcpRtoMax,INTEGER,read-only,,mandatory,,The maximum value permitted by a TCP implementation for the retransmission timeout, measured in milliseconds. More refined semantics for objects of this type depend upon the algorithm used to determine the retransmission timeout. In particular, when the timeout algorithm is rsre(3), an object of this type has the semantics of the UBOUND quantity described in RFC 793.
.1.3.6.1.2.1.6.4,RFC1213-MIB::tcpMaxConn,INTEGER,read-only,,mandatory,,The limit on the total number of TCP connections the entity can support. In entities where the maximum number of connections is dynamic, this object should contain the value -1.
.1.3.6.1.2.1.6.5,RFC1213-MIB::tcpActiveOpens,Counter32,read-only,,mandatory,,The number of times TCP connections have made a direct transition to the SYN-SENT state from the CLOSED state.
.1.3.6.1.2.1.6.6,RFC1213-MIB::tcpPassiveOpens,Counter32,read-only,,mandatory,,The number of times TCP connections have made a direct transition to the SYN-RCVD state from the LISTEN state.
.1.3.6.1.2.1.6.7,RFC1213-MIB::tcpAttemptFails,Counter32,read-only,,mandatory,,The number of times TCP connections have made a direct transition to the CLOSED state from either the SYN-SENT state or the SYN-RCVD state, plus the number of times TCP connections have made a direct transition to the LISTEN state from the SYN-RCVD state.
.1.3.6.1.2.1.6.8,RFC1213-MIB::tcpEstabResets,Counter32,read-only,,mandatory,,The number of times TCP connections have made a direct transition to the CLOSED state from either the ESTABLISHED state or the CLOSE-WAIT state.
.1.3.6.1.2.1.6.9,RFC1213-MIB::tcpCurrEstab,Gauge32,read-only,,mandatory,,The number of TCP connections for which the current state is either ESTABLISHED or CLOSE- WAIT.
.1.3.6.1.2.1.6.10,RFC1213-MIB::tcpInSegs,Counter32,read-only,,mandatory,,The total number of segments received, including those received in error. This count includes segments received on currently established connections.
.1.3.6.1.2.1.6.11,RFC1213-MIB::tcpOutSegs,Counter32,read-only,,mandatory,,The total number of segments sent, including those on current connections but excluding those containing only retransmitted octets.
.1.3.6.1.2.1.6.12,RFC1213-MIB::tcpRetransSegs,Counter32,read-only,,mandatory,,The total number of segments retransmitted - that is, the number of TCP segments transmitted containing one or more previously transmitted octets.
.1.3.6.1.2.1.6.13,RFC1213-MIB::tcpConnTable,,not-accessible,,mandatory,,A table containing TCP connection-specific information.
.1.3.6.1.2.1.6.13.1,RFC1213-MIB::tcpConnEntry,,not-accessible,tcpConnLocalAddress:tcpConnLocalPort:tcpConnRemAddress:tcpConnRemPort,mandatory,,Information about a particular current TCP connection. An object of this type is transient, in that it ceases to exist when (or soon after) the connection makes the transition to the CLOSED state.
.1.3.6.1.2.1.6.13.1.1,RFC1213-MIB::tcpConnState,INTEGER,read-write,,mandatory,closed(1):listen(2):synSent(3):synReceived(4):established(5):finWait1(6):finWait2(7):closeWait(8):lastAck(9):closing(10):timeWait(11):deleteTCB(12),The state of this TCP connection. The only value which may be set by a management station is deleteTCB(12). Accordingly, it is appropriate for an agent to return a `badValue' response if a management station attempts to set this object to any other value. If a management station sets this object to the value deleteTCB(12), then this has the effect of deleting the TCB (as defined in RFC 793) of the corresponding connection on the managed node, resulting in immediate termination of the connection. As an implementation-specific option, a RST segment may be sent from the managed node to the other TCP endpoint (note however that RST segments are not sent reliably).
.1.3.6.1.2.1.6.13.1.2,RFC1213-MIB::tcpConnLocalAddress,IpAddress,read-only,,mandatory,,The local IP address for this TCP connection. In the case of a connection in the listen state which is willing to accept connections for any IP interface associated with the node, the value 0.0.0.0 is used.
.1.3.6.1.2.1.6.13.1.3,RFC1213-MIB::tcpConnLocalPort,INTEGER,read-only,,mandatory,,The local port number for this TCP connection.
.1.3.6.1.2.1.6.13.1.4,RFC1213-MIB::tcpConnRemAddress,IpAddress,read-only,,mandatory,,The remote IP address for this TCP connection.
.1.3.6.1.2.1.6.13.1.5,RFC1213-MIB::tcpConnRemPort,INTEGER,read-only,,mandatory,,The remote port number for this TCP connection.
.1.3.6.1.2.1.6.14,RFC1213-MIB::tcpInErrs,Counter32,read-only,,mandatory,,The total number of segments received in error (e.g., bad TCP checksums).
.1.3.6.1.2.1.6.15,RFC1213-MIB::tcpOutRsts,Counter32,read-only,,mandatory,,The number of TCP segments sent containing the RST flag.
.1.3.6.1.2.1.7,RFC1213-MIB::udp,,,,,,
.1.3.6.1.2.1.7.1,RFC1213-MIB::udpInDatagrams,Counter32,read-only,,mandatory,,The total number of UDP datagrams delivered to UDP users.
.1.3.6.1.2.1.7.2,RFC1213-MIB::udpNoPorts,Counter32,read-only,,mandatory,,The total number of received UDP datagrams for which there was no application at the destination port.
.1.3.6.1.2.1.7.3,RFC1213-MIB::udpInErrors,Counter32,read-only,,mandatory,,The number of received UDP datagrams that could not be delivered for reasons other than the lack of an application at the destination port.
.1.3.6.1.2.1.7.4,RFC1213-MIB::udpOutDatagrams,Counter32,read-only,,mandatory,,The total number of UDP datagrams sent from this entity.
.1.3.6.1.2.1.7.5,RFC1213-MIB::udpTable,,not-accessible,,mandatory,,A table containing UDP listener information.
.1.3.6.1.2.1.7.5.1,RFC1213-MIB::udpEntry,,not-accessible,udpLocalAddress:udpLocalPort,mandatory,,Information about a particular current UDP listener.
.1.3.6.1.2.1.7.5.1.1,RFC1213-MIB::udpLocalAddress,IpAddress,read-only,,mandatory,,The local IP address for this UDP listener. In the case of a UDP listener which is willing to accept datagrams for any IP interface associated with the node, the value 0.0.0.0 is used.
.1.3.6.1.2.1.7.5.1.2,RFC1213-MIB::udpLocalPort,INTEGER,read-only,,mandatory,,The local port number for this UDP listener.
.1.3.6.1.2.1.8,RFC1213-MIB::egp,,,,,,
.1.3.6.1.2.1.8.1,RFC1213-MIB::egpInMsgs,Counter32,read-only,,mandatory,,The number of EGP messages received without error.
.1.3.6.1.2.1.8.2,RFC1213-MIB::egpInErrors,Counter32,read-only,,mandatory,,The number of EGP messages received that proved to be in error.
.1.3.6.1.2.1.8.3,RFC1213-MIB::egpOutMsgs,Counter32,read-only,,mandatory,,The total number of locally generated EGP messages.
.1.3.6.1.2.1.8.4,RFC1213-MIB::egpOutErrors,Counter32,read-only,,mandatory,,The number of locally generated EGP messages not sent due to resource limitations within an EGP entity.
.1.3.6.1.2.1.8.5,RFC1213-MIB::egpNeighTable,,not-accessible,,mandatory,,The EGP neighbor table.
.1.3.6.1.2.1.8.5.1,RFC1213-MIB::egpNeighEntry,,not-accessible,egpNeighAddr,mandatory,,Information about this entity's relationship with a particular EGP neighbor.
.1.3.6.1.2.1.8.5.1.1,RFC1213-MIB::egpNeighState,INTEGER,read-only,,mandatory,idle(1):acquisition(2):down(3):up(4):cease(5),The EGP state of the local system with respect to this entry's EGP neighbor. Each EGP state is represented by a value that is one greater than the numerical value associated with said state in RFC 904.
.1.3.6.1.2.1.8.5.1.2,RFC1213-MIB::egpNeighAddr,IpAddress,read-only,,mandatory,,The IP address of this entry's EGP neighbor.
.1.3.6.1.2.1.8.5.1.3,RFC1213-MIB::egpNeighAs,INTEGER,read-only,,mandatory,,The autonomous system of this EGP peer. Zero should be specified if the autonomous system number of the neighbor is not yet known.
.1.3.6.1.2.1.8.5.1.4,RFC1213-MIB::egpNeighInMsgs,Counter32,read-only,,mandatory,,The number of EGP messages received without error from this EGP peer.
.1.3.6.1.2.1.8.5.1.5,RFC1213-MIB::egpNeighInErrs,Counter32,read-only,,mandatory,,The number of EGP messages received from this EGP peer that proved to be in error (e.g., bad EGP checksum).
.1.3.6.1.2.1.8.5.1.6,RFC1213-MIB::egpNeighOutMsgs,Counter32,read-only,,mandatory,,The number of locally generated EGP messages to this EGP peer.
.1.3.6.1.2.1.8.5.1.7,RFC1213-MIB::egpNeighOutErrs,Counter32,read-only,,mandatory,,The number of locally generated EGP messages not sent to this EGP peer due to resource limitations within an EGP entity.
.1.3.6.1.2.1.8.5.1.8,RFC1213-MIB::egpNeighInErrMsgs,Counter32,read-only,,mandatory,,The number of EGP-defined error messages received from this EGP peer.
.1.3.6.1.2.1.8.5.1.9,RFC1213-MIB::egpNeighOutErrMsgs,Counter32,read-only,,mandatory,,The number of EGP-defined error messages sent to this EGP peer.
.1.3.6.1.2.1.8.5.1.10,RFC1213-MIB::egpNeighStateUps,Counter32,read-only,,mandatory,,The number of EGP state transitions to the UP state with this EGP peer.
.1.3.6.1.2.1.8.5.1.11,RFC1213-MIB::egpNeighStateDowns,Counter32,read-only,,mandatory,,The number of EGP state transitions from the UP state to any other state with this EGP peer.
.1.3.6.1.2.1.8.5.1.12,RFC1213-MIB::egpNeighIntervalHello,INTEGER,read-only,,mandatory,,The interval between EGP Hello command retransmissions (in hundredths of a second). This represents the t1 timer as defined in RFC 904.
.1.3.6.1.2.1.8.5.1.13,RFC1213-MIB::egpNeighIntervalPoll,INTEGER,read-only,,mandatory,,The interval between EGP poll command retransmissions (in hundredths of a second). This represents the t3 timer as defined in RFC 904.
.1.3.6.1.2.1.8.5.1.14,RFC1213-MIB::egpNeighMode,INTEGER,read-only,,mandatory,active(1):passive(2),The polling mode of this EGP entity, either passive or active.
.1.3.6.1.2.1.8.5.1.15,RFC1213-MIB::egpNeighEventTrigger,INTEGER,read-write,,mandatory,start(1):stop(2),A control variable used to trigger operator- initiated Start and Stop events. When read, this variable always returns the most recent value that egpNeighEventTrigger was set to. If it has not been set since the last initialization of the network management subsystem on the node, it returns a value of `stop'. When set, this variable causes a Start or Stop event on the specified neighbor, as specified on pages 8-10 of RFC 904. Briefly, a Start event causes an Idle peer to begin neighbor acquisition and a non-Idle peer to reinitiate neighbor acquisition. A stop event causes a non-Idle peer to return to the Idle state until a Start event occurs, either via egpNeighEventTrigger or otherwise.
.1.3.6.1.2.1.8.6,RFC1213-MIB::egpAs,INTEGER,read-only,,mandatory,,The autonomous system number of this EGP entity.
.1.3.6.1.2.1.10,SNMPv2-SMI::transmission,,,,,,
.1.3.6.1.2.1.11,RFC1213-MIB::snmp,,,,,,
.1.3.6.1.2.1.11.1,RFC1213-MIB::snmpInPkts,Counter32,read-only,,mandatory,,The total number of Messages delivered to the SNMP entity from the transport service.
.1.3.6.1.2.1.11.2,RFC1213-MIB::snmpOutPkts,Counter32,read-only,,mandatory,,The total number of SNMP Messages which were passed from the SNMP protocol entity to the transport service.
.1.3.6.1.2.1.11.3,RFC1213-MIB::snmpInBadVersions,Counter32,read-only,,mandatory,,The total number of SNMP Messages which were delivered to the SNMP protocol entity and were for an unsupported SNMP version.
.1.3.6.1.2.1.11.4,RFC1213-MIB::snmpInBadCommunityNames,Counter32,read-only,,mandatory,,The total number of SNMP Messages delivered to the SNMP protocol entity which used a SNMP community name not known to said entity.
.1.3.6.1.2.1.11.5,RFC1213-MIB::snmpInBadCommunityUses,Counter32,read-only,,mandatory,,The total number of SNMP Messages delivered to the SNMP protocol entity which represented an SNMP operation which was not allowed by the SNMP community named in the Message.
.1.3.6.1.2.1.11.6,RFC1213-MIB::snmpInASNParseErrs,Counter32,read-only,,mandatory,,The total number of ASN.1 or BER errors encountered by the SNMP protocol entity when decoding received SNMP Messages.
.1.3.6.1.2.1.11.8,RFC1213-MIB::snmpInTooBigs,Counter32,read-only,,mandatory,,The total number of SNMP PDUs which were delivered to the SNMP protocol entity and for which the value of the error-status field is `tooBig'.
.1.3.6.1.2.1.11.9,RFC1213-MIB::snmpInNoSuchNames,Counter32,read-only,,mandatory,,The total number of SNMP PDUs which were delivered to the SNMP protocol entity and for which the value of the error-status field is `noSuchName'.
.1.3.6.1.2.1.11.10,RFC1213-MIB::snmpInBadValues,Counter32,read-only,,mandatory,,The total number of SNMP PDUs which were delivered to the SNMP protocol entity and for which the value of the error-status field is `badValue'.
.1.3.6.1.2.1.11.11,RFC1213-MIB::snmpInReadOnlys,Counter32,read-only,,mandatory,,The total number valid SNMP PDUs which were delivered to the SNMP protocol entity and for which the value of the error-status field is `readOnly'. It should be noted that it is a protocol error to generate an SNMP PDU which contains the value `readOnly' in the error-status field, as such this object is provided as a means of detecting incorrect implementations of the SNMP.
.1.3.6.1.2.1.11.12,RFC1213-MIB::snmpInGenErrs,Counter32,read-only,,mandatory,,The total number of SNMP PDUs which were delivered to the SNMP protocol entity and for which the value of the error-status field is `genErr'.
.1.3.6.1.2.1.11.13,RFC1213-MIB::snmpInTotalReqVars,Counter32,read-only,,mandatory,,The total number of MIB objects which have been retrieved successfully by the SNMP protocol entity as the result of receiving valid SNMP Get-Request and Get-Next PDUs.
.1.3.6.1.2.1.11.14,RFC1213-MIB::snmpInTotalSetVars,Counter32,read-only,,mandatory,,The total number of MIB objects which have been altered successfully by the SNMP protocol entity as the result of receiving valid SNMP Set-Request PDUs.
.1.3.6.1.2.1.11.15,RFC1213-MIB::snmpInGetRequests,Counter32,read-only,,mandatory,,The total number of SNMP Get-Request PDUs which have been accepted and processed by the SNMP protocol entity.
.1.3.6.1.2.1.11.16,RFC1213-MIB::snmpInGetNexts,Counter32,read-only,,mandatory,,The total number of SNMP Get-Next PDUs which have been accepted and processed by the SNMP protocol entity.
.1.3.6.1.2.1.11.17,RFC1213-MIB::snmpInSetRequests,Counter32,read-only,,mandatory,,The total number of SNMP Set-Request PDUs which have been accepted and processed by the SNMP protocol entity.
.1.3.6.1.2.1.11.18,RFC1213-MIB::snmpInGetResponses,Counter32,read-only,,mandatory,,The total number of SNMP Get-Response PDUs which have been accepted and processed by the SNMP protocol entity.
.1.3.6.1.2.1.11.19,RFC1213-MIB::snmpInTraps,Counter32,read-only,,mandatory,,The total number of SNMP Trap PDUs which have been accepted and processed by the SNMP protocol entity.
.1.3.6.1.2.1.11.20,RFC1213-MIB::snmpOutTooBigs,Counter32,read-only,,mandatory,,The total number of SNMP PDUs which were generated by the SNMP protocol entity and for which the value of the error-status field is `tooBig.'
.1.3.6.1.2.1.11.21,RFC1213-MIB::snmpOutNoSuchNames,Counter32,read-only,,mandatory,,The total number of SNMP PDUs which were generated by the SNMP protocol entity and for which the value of the error-status is `noSuchName'.
.1.3.6.1.2.1.11.22,RFC1213-MIB::snmpOutBadValues,Counter32,read-only,,mandatory,,The total number of SNMP PDUs which were generated by the SNMP protocol entity and for which the value of the error-status field is `badValue'.
.1.3.6.1.2.1.11.24,RFC1213-MIB::snmpOutGenErrs,Counter32,read-only,,mandatory,,The total number of SNMP PDUs which were generated by the SNMP protocol entity and for which the value of the error-status field is `genErr'.
.1.3.6.1.2.1.11.25,RFC1213-MIB::snmpOutGetRequests,Counter32,read-only,,mandatory,,The total number of SNMP Get-Request PDUs which have been generated by the SNMP protocol entity.
.1.3.6.1.2.1.11.26,RFC1213-MIB::snmpOutGetNexts,Counter32,read-only,,mandatory,,The total number of SNMP Get-Next PDUs which have been generated by the SNMP protocol entity.
.1.3.6.1.2.1.11.27,RFC1213-MIB::snmpOutSetRequests,Counter32,read-only,,mandatory,,The total number of SNMP Set-Request PDUs which have been generated by the SNMP protocol entity.
.1.3.6.1.2.1.11.28,RFC1213-MIB::snmpOutGetResponses,Counter32,read-only,,mandatory,,The total number of SNMP Get-Response PDUs which have been generated by the SNMP protocol entity.
.1.3.6.1.2.1.11.29,RFC1213-MIB::snmpOutTraps,Counter32,read-only,,mandatory,,The total number of SNMP Trap PDUs which have been generated by the SNMP protocol entity.
.1.3.6.1.2.1.11.30,RFC1213-MIB::snmpEnableAuthenTraps,INTEGER,read-write,,mandatory,enabled(1):disabled(2),Indicates whether the SNMP agent process is permitted to generate authentication-failure traps. The value of this object overrides any configuration information; as such, it provides a means whereby all authentication-failure traps may be disabled. Note that it is strongly recommended that this object be stored in non-volatile memory so that it remains constant between re-initializations of the network management system.
.1.3.6.1.2.1.30,IANAifType-MIB::ianaifType,,,,,,This MIB module defines the IANAifType Textual Convention, and thus the enumerated values of the ifType object defined in MIB-II's ifTable.
.1.3.6.1.3,RFC1155-SMI::experimental,,,,,,
.1.3.6.1.4,RFC1155-SMI::private,,,,,,
.1.3.6.1.4.1,RFC1155-SMI::enterprises,,,,,,
.1.3.6.1.4.1.476,LIEBERT-GP-REGISTRATION-MIB::vertiv,,,,,,The enterprise registration for Vertiv.
.1.3.6.1.4.1.476.1,LIEBERT-GP-REGISTRATION-MIB::liebertCorp,,,,,,Liebert Corporation obtains its branch from Vertiv.
.1.3.6.1.4.1.476.1.42,LIEBERT-GP-REGISTRATION-MIB::liebertGlobalProducts,,,,,,This branch is used for Liebert Global Products related information.
.1.3.6.1.4.1.476.1.42.1,LIEBERT-GP-REGISTRATION-MIB::lgpModuleReg,,,,,,The Liebert Global Products MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.1,LIEBERT-GP-REGISTRATION-MIB::liebertModuleReg,,,,,,The Liebert Global Products MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.1.1,LIEBERT-GP-REGISTRATION-MIB::liebertGlobalProductsRegistrationModule,,,,,,The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2018 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
.1.3.6.1.4.1.476.1.42.1.2,LIEBERT-GP-REGISTRATION-MIB::liebertAgentModuleReg,,,,,,The Liebert Global Products AGENT MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.2.1,LIEBERT-GP-AGENT-MIB::liebertAgentModule,,,,,,The MIB module used to specify Liebert software or firmware agent SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
.1.3.6.1.4.1.476.1.42.1.3,LIEBERT-GP-REGISTRATION-MIB::liebertConditionsModuleReg,,,,,,The Liebert Global Products CONDITIONS MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.3.1,LIEBERT-GP-CONDITIONS-MIB::liebertGlobalProductsConditionsModule,,,,,,The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008,2013 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
.1.3.6.1.4.1.476.1.42.1.4,LIEBERT-GP-REGISTRATION-MIB::liebertNotificationsModuleReg,,,,,,The Liebert Global Products NOTIFICATIONS MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.4.1,LIEBERT-GP-NOTIFICATIONS-MIB::liebertGlobalProductsNotificationsModule,,,,,,The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
.1.3.6.1.4.1.476.1.42.1.5,LIEBERT-GP-REGISTRATION-MIB::liebertEnvironmentalModuleReg,,,,,,The Liebert Global Products ENVIRONMENTAL MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.5.1,LIEBERT-GP-ENVIRONMENTAL-MIB::liebertGlobalProductsEnvironmentalModule,,,,,,The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2015 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
.1.3.6.1.4.1.476.1.42.1.6,LIEBERT-GP-REGISTRATION-MIB::liebertPowerModuleReg,,,,,,The Liebert Global Products POWER MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.6.1,LIEBERT-GP-POWER-MIB::liebertGlobalProductsPowerModule,,,,,,The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
.1.3.6.1.4.1.476.1.42.1.7,LIEBERT-GP-REGISTRATION-MIB::liebertControllerModuleReg,,,,,,The Liebert Global Products CONTROLLER MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.7.1,LIEBERT-GP-CONTROLLER-MIB::liebertControllerModule,,,,,,The MIB module used to specify Liebert Controller OIDs Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
.1.3.6.1.4.1.476.1.42.1.8,LIEBERT-GP-REGISTRATION-MIB::liebertSystemModuleReg,,,,,,The Liebert Global Products SYSTEM MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.8.1,LIEBERT-GP-SYSTEM-MIB::liebertSystemModule,,,,,,The MIB module used to specify Liebert Controller OIDs Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
.1.3.6.1.4.1.476.1.42.1.9,LIEBERT-GP-REGISTRATION-MIB::liebertPduModuleReg,,,,,,The Liebert Global Products Power Distribution (PDU)  MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.9.1,LIEBERT-GP-PDU-MIB::liebertGlobalProductsPduModule,,,,,,The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2008-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
.1.3.6.1.4.1.476.1.42.1.10,LIEBERT-GP-REGISTRATION-MIB::liebertFlexibleModuleReg,,,,,,The Liebert Global Products Flexible  MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.10.1,LIEBERT-GP-FLEXIBLE-MIB::liebertGlobalProductsFlexibleModule,,,,,,The MIB module used to register Liebert Flexible related SNMP OIDs. Copyright 2013 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
.1.3.6.1.4.1.476.1.42.1.11,LIEBERT-GP-REGISTRATION-MIB::liebertFlexibleConditionsModuleReg,,,,,,The Liebert Global Products FLEXIBLE CONDITIONS MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.11.1,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::liebertGlobalProductsFlexibleConditionsModule,,,,,,The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2020 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
.1.3.6.1.4.1.476.1.42.1.12,LIEBERT-GP-REGISTRATION-MIB::liebertSrcModuleReg,,,,,,The Liebert Src Product MODULE-IDENTITY OIDs are registered via this branch.
.1.3.6.1.4.1.476.1.42.1.12.1,LIEBERT-GP-SRC-MIB::liebertGlobalProductsSrcModule,,,,,,The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2008-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
.1.3.6.1.4.1.476.1.42.2,LIEBERT-GP-REGISTRATION-MIB::lgpAgent,,,,,,All Liebert agent objects are registered in this branch.
.1.3.6.1.4.1.476.1.42.2.1,LIEBERT-GP-REGISTRATION-MIB::lgpAgentIdent,,,,,,Liebert Agent Identification - This branch contains OIDS that are used to identify an agent and its managed device.
.1.3.6.1.4.1.476.1.42.2.1.1,LIEBERT-GP-AGENT-MIB::lgpAgentIdentManufacturer,OCTET,read-only,,current,,The agent manufacturer.
.1.3.6.1.4.1.476.1.42.2.1.2,LIEBERT-GP-AGENT-MIB::lgpAgentIdentModel,OCTET,read-only,,current,,The agent model designation. This identifier is typically a model name or ID
.1.3.6.1.4.1.476.1.42.2.1.3,LIEBERT-GP-AGENT-MIB::lgpAgentIdentFirmwareVersion,OCTET,read-only,,current,,The firmware revision level of the agent.
.1.3.6.1.4.1.476.1.42.2.1.4,LIEBERT-GP-AGENT-MIB::lgpAgentIdentSerialNumber,OCTET,read-only,,current,,The serial number of the agent. This is a string of alphanumeric characters that uniquely identifies the agent hardware. This number is assigned when the agent hardware is manufactured and does not change throughout its lifecycle.
.1.3.6.1.4.1.476.1.42.2.1.5,LIEBERT-GP-AGENT-MIB::lgpAgentIdentPartNumber,OCTET,read-only,,current,,The agent model part number designation.
.1.3.6.1.4.1.476.1.42.2.1.6,LIEBERT-GP-AGENT-MIB::lgpAgentConnectedDeviceCount,Unsigned32,read-only,,current,,The number of devices currently connected and communicating successfully with the agent. Devices for which communications are currently being attempted are not considered in this count.
.1.3.6.1.4.1.476.1.42.2.3,LIEBERT-GP-REGISTRATION-MIB::lgpAgentNotifications,,,,,,This branch is used to register Liebert agent notify object identifiers.
.1.3.6.1.4.1.476.1.42.2.3.0,LIEBERT-GP-AGENT-MIB::lgpAgentEventNotifications,,,,,,Agent specific notifications.
.1.3.6.1.4.1.476.1.42.2.3.0.0,LIEBERT-GP-AGENT-MIB::lgpAgentEventNotificationsLegacy,,,,,,This branch contains copies of the notifications registered directly below lgpAgentEventNotifications. These are here to provide support  for some legacy devices which send out lgpAgentEventNotifications  as the SNMPv1 enterprise trap parameter instead of  lgpAgentNotifications, which causes problems with some SNMP clients  when converting from V1 to V2 notifications (RFC3584 Section 3).
.1.3.6.1.4.1.476.1.42.2.3.0.0.1,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceCommunicationLostLegacy,,,,,,The agent has lost communications with a managed device.
.1.3.6.1.4.1.476.1.42.2.3.0.0.5,LIEBERT-GP-AGENT-MIB::lgpAgentFirmwareUpdateSuccessfulLegacy,,,,,,The firmware update to the agent card has completed successfully.
.1.3.6.1.4.1.476.1.42.2.3.0.0.6,LIEBERT-GP-AGENT-MIB::lgpAgentFirmwareCorruptLegacy,,,,,,The firmware update to the agent card has failed and the firmware is now corrupt.
.1.3.6.1.4.1.476.1.42.2.3.0.0.7,LIEBERT-GP-AGENT-MIB::lgpAgentHeartbeatLegacy,,,,,,The agent card is alive.
.1.3.6.1.4.1.476.1.42.2.3.0.0.8,LIEBERT-GP-AGENT-MIB::lgpAgentDnsLookupFailureLegacy,,,,,,A Domain Name System (DNS) lookup of a network name failed to resolve. This may result in one or more of the following: 1. failure to notify a target address of an important condition 2. failure allow access for monitoring purposes This issue should be resolved as soon as possible with a network or system administrator.
.1.3.6.1.4.1.476.1.42.2.3.0.1,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceCommunicationLost,,,,,,The agent has lost communications with a managed device.
.1.3.6.1.4.1.476.1.42.2.3.0.5,LIEBERT-GP-AGENT-MIB::lgpAgentFirmwareUpdateSuccessful,,,,,,The firmware update to the agent card has completed successfully.
.1.3.6.1.4.1.476.1.42.2.3.0.6,LIEBERT-GP-AGENT-MIB::lgpAgentFirmwareCorrupt,,,,,,The firmware update to the agent card has failed and the firmware is now corrupt.
.1.3.6.1.4.1.476.1.42.2.3.0.7,LIEBERT-GP-AGENT-MIB::lgpAgentHeartbeat,,,,,,The agent card is alive.
.1.3.6.1.4.1.476.1.42.2.3.0.8,LIEBERT-GP-AGENT-MIB::lgpAgentDnsLookupFailure,,,,,,A Domain Name System (DNS) lookup of a network name failed to resolve. This may result in one or more of the following: 1. failure to notify a target address of an important condition 2. failure allow access for monitoring purposes This issue should be resolved as soon as possible with a network or system administrator.
.1.3.6.1.4.1.476.1.42.2.4,LIEBERT-GP-REGISTRATION-MIB::lgpAgentDevice,,,,,,This branch contains OIDs that are used to identify a managed device.
.1.3.6.1.4.1.476.1.42.2.4.2,LIEBERT-GP-AGENT-MIB::lgpAgentManagedDeviceTable,,not-accessible,,current,,This table contains one entry for each managed device.
.1.3.6.1.4.1.476.1.42.2.4.2.1,LIEBERT-GP-AGENT-MIB::lgpAgentManagedDeviceEntry,,not-accessible,lgpAgentDeviceIndex,current,,This entry describes a row in the table 'lgpAgentManagedDeviceTable'. The rows in this table cannot be created by the NMS. The rows are automatically created by the agent based upon the hardware configuration of the Liebert managed device(s) being monitored with this agent.
.1.3.6.1.4.1.476.1.42.2.4.2.1.1,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceIndex,Integer32,read-only,,current,,The device identifier. This is used as an index to address a particular row in the table 'lgpAgentManagedDeviceTable'.
.1.3.6.1.4.1.476.1.42.2.4.2.1.2,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceId,OBJECT,read-only,,current,,The managed device specific identifier defined by the product registration.
.1.3.6.1.4.1.476.1.42.2.4.2.1.3,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceManufacturer,OCTET,read-only,,current,,The managed device manufacturer.
.1.3.6.1.4.1.476.1.42.2.4.2.1.4,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceModel,OCTET,read-only,,current,,The managed device model designation.
.1.3.6.1.4.1.476.1.42.2.4.2.1.5,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceFirmwareVersion,OCTET,read-only,,current,,The firmware revision level of the managed device.
.1.3.6.1.4.1.476.1.42.2.4.2.1.6,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceUnitNumber,Integer32,read-write,,current,,The managed device unit number. Typically this is a number assigned to a managed device that uniquely identifies it from other similar devices within a 'system'.
.1.3.6.1.4.1.476.1.42.2.4.2.1.7,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceSerialNumber,OCTET,read-only,,current,,The serial number of the managed device.
.1.3.6.1.4.1.476.1.42.2.4.2.1.8,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceManufactureDate,OCTET,read-only,,current,,The manufacture date of the managed device.
.1.3.6.1.4.1.476.1.42.2.4.2.1.9,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceServiceContact,OCTET,read-write,,current,,The service contact of the managed device.
.1.3.6.1.4.1.476.1.42.2.4.2.1.10,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceServicePhoneNumber,OCTET,read-write,,current,,The phone number of the service contact of the managed device.
.1.3.6.1.4.1.476.1.42.2.4.2.1.11,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceServiceAddrLine1,OCTET,read-write,,current,,Line 1 of the service address of the managed device.
.1.3.6.1.4.1.476.1.42.2.4.2.1.12,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceServiceAddrLine2,OCTET,read-write,,current,,Line 2 of the service address of the managed device.
.1.3.6.1.4.1.476.1.42.2.4.2.1.13,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceServiceAddrLine3,OCTET,read-write,,current,,Line 3 of the service address of the managed device.
.1.3.6.1.4.1.476.1.42.2.4.2.1.14,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceServiceAddrLine4,OCTET,read-write,,current,,Line 4 of the service address of the managed device.
.1.3.6.1.4.1.476.1.42.2.4.2.1.15,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceUnitName,OCTET,read-write,,current,,Unit name for the managed device assigned by the customer.
.1.3.6.1.4.1.476.1.42.2.4.2.1.16,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceSiteIdentifier,OCTET,read-write,,current,,Identifier that uniquely identifies the site where this device is located.
.1.3.6.1.4.1.476.1.42.2.4.2.1.17,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceTagNumber,OCTET,read-write,,current,,Identifier that uniquely identifies this device within a particular site (see lgpAgentDeviceSiteIdentifier).
.1.3.6.1.4.1.476.1.42.2.4.2.1.18,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceOrderLine1,OCTET,read-write,,current,,Customer Sales Order information line 1.
.1.3.6.1.4.1.476.1.42.2.4.2.1.19,LIEBERT-GP-AGENT-MIB::lgpAgentDeviceOrderLine2,OCTET,read-write,,current,,Customer Sales Order information line 2.
.1.3.6.1.4.1.476.1.42.2.5,LIEBERT-GP-REGISTRATION-MIB::lgpAgentControl,,,,,,This branch contains objects relating to the control of the agent software.
.1.3.6.1.4.1.476.1.42.2.5.1,LIEBERT-GP-AGENT-MIB::lgpAgentReboot,Integer32,read-write,,current,,Perform an immediate 'reboot' of the agent process. When possible the reboot will approximate a power on reset of the agent communications hardware. This type of reboot will be performed if a hardware reset is supported by the hardware/software on the communications card. Otherwise a 'software' reboot will be executed. In both cases a temporary loss of communications and other agent functionality will result. Any valid INTEGER value may be written to this object to initiate the reboot operation. If read the value '0' will always be returned.
.1.3.6.1.4.1.476.1.42.2.5.2,LIEBERT-GP-AGENT-MIB::lgpAgentTelnetEnabled,INTEGER,read-write,,current,yes(1):no(2),This object represents the settings of Telnet. yes Telnet services are enabled. no Telnet services are disabled. The system must be rebooted before changes can take effect.
.1.3.6.1.4.1.476.1.42.2.5.3,LIEBERT-GP-AGENT-MIB::lgpAgentVelocityServerEnabled,INTEGER,read-write,,current,yes(1):no(2),This object configures the Velocity Server to grant external clients access to agent data via the Liebert Velocity protocol. yes Agent data is available to external clients via the Liebert Velocity protocol. no Agent data is not available to external clients via the Liebert Velocity protocol. The system must be rebooted before changes can take effect.
.1.3.6.1.4.1.476.1.42.2.5.4,LIEBERT-GP-AGENT-MIB::lgpAgentWebServerMode,INTEGER,read-write,,current,disabled(0):http(1):https(2),This object represents the settings of Web services. disabled Web services are disabled. http Web server mode is HTTP (not secure). https Web server mode is secure HTTP. The system must be rebooted before changes can take effect.
.1.3.6.1.4.1.476.1.42.3,LIEBERT-GP-REGISTRATION-MIB::lgpFoundation,,,,,,This branch is used to register Liebert objects that have common use across product families.
.1.3.6.1.4.1.476.1.42.3.2,LIEBERT-GP-REGISTRATION-MIB::lgpConditions,,,,,,This branch is used to register Liebert status condition object identifiers.
.1.3.6.1.4.1.476.1.42.3.2.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionsWellKnown,,,,,,
.1.3.6.1.4.1.476.1.42.3.2.1.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperature,,,,,,The temperature has exceeded the high temperature threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowTemperature,,,,,,The temperature is below the low temperature threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighHumidity,,,,,,The humidity has exceeded the high humidity threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowHumidity,,,,,,The humidity is below the low humidity threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLossOfAirflow,,,,,,The system has detected a loss of air flow.
.1.3.6.1.4.1.476.1.42.3.2.1.5.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLossOfAirflow1,,,,,,The system has detected a loss of air flow at sensor 1.
.1.3.6.1.4.1.476.1.42.3.2.1.5.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLossOfAirflow2,,,,,,The system has detected a loss of air flow at sensor 2.
.1.3.6.1.4.1.476.1.42.3.2.1.5.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLossOfAirflowBlower1,,,,,,The system has detected a loss of air flow from blower 1.
.1.3.6.1.4.1.476.1.42.3.2.1.5.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLossOfAirflowAllBlowers,,,,,,No air flow through the unit due to failure of all blowers.
.1.3.6.1.4.1.476.1.42.3.2.1.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionChangeFilter,,,,,,The system has detected a condition indicating the air filter should be changed.
.1.3.6.1.4.1.476.1.42.3.2.1.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressorHighHeadPressure,,,,,,This system has detected an excessive head pressure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.7.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor1HighHeadPressure,,,,,,The system has detected excessive head pressure in compressor 1.
.1.3.6.1.4.1.476.1.42.3.2.1.7.1.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor1AHighHeadPressure,,,,,,The system has detected excessive head pressure in compressor 1A.
.1.3.6.1.4.1.476.1.42.3.2.1.7.1.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor1BHighHeadPressure,,,,,,The system has detected excessive head pressure in compressor 1B.
.1.3.6.1.4.1.476.1.42.3.2.1.7.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor2HighHeadPressure,,,,,,The system has detected excessive head pressure in compressor 2.
.1.3.6.1.4.1.476.1.42.3.2.1.7.2.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor2AHighHeadPressure,,,,,,The system has detected excessive head pressure in compressor 2A.
.1.3.6.1.4.1.476.1.42.3.2.1.7.2.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor2BHighHeadPressure,,,,,,The system has detected excessive head pressure in compressor 2B.
.1.3.6.1.4.1.476.1.42.3.2.1.7.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor3HighHeadPressure,,,,,,The system has detected excessive head pressure in compressor 3.
.1.3.6.1.4.1.476.1.42.3.2.1.7.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor4HighHeadPressure,,,,,,The system has detected excessive head pressure in compressor 4.
.1.3.6.1.4.1.476.1.42.3.2.1.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressorOverload,,,,,,This system has detected a compressor overload condition.
.1.3.6.1.4.1.476.1.42.3.2.1.8.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor1Overload,,,,,,The system has detected an overload condition on compressor 1.
.1.3.6.1.4.1.476.1.42.3.2.1.8.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor2Overload,,,,,,The system has detected an overload condition on compressor 2.
.1.3.6.1.4.1.476.1.42.3.2.1.8.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor3Overload,,,,,,The system has detected an overload condition on compressor 3.
.1.3.6.1.4.1.476.1.42.3.2.1.8.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor4Overload,,,,,,The system has detected an overload condition on compressor 4.
.1.3.6.1.4.1.476.1.42.3.2.1.9,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressorShortCycle,,,,,,A compressor has exceeded the maximum number of starts in a minimum time period.
.1.3.6.1.4.1.476.1.42.3.2.1.9.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor1ShortCycle,,,,,,The system has detected a short cycle event on compressor 1. The compressor has exceeded the maximum number of starts for specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.9.1.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor1AShortCycle,,,,,,The system has detected a short cycle event on compressor 1A. The compressor has exceeded the maximum number of starts for specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.9.1.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor1BShortCycle,,,,,,The system has detected a short cycle event on compressor 1B. The compressor has exceeded the maximum number of starts for specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.9.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor2ShortCycle,,,,,,The system has detected a short cycle event on compressor 2. The compressor has exceeded the maximum number of starts for specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.9.2.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor2AShortCycle,,,,,,The system has detected a short cycle event on compressor 2A. The compressor has exceeded the maximum number of starts for specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.9.2.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor2BShortCycle,,,,,,The system has detected a short cycle event on compressor 2B. The compressor has exceeded the maximum number of starts for specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.9.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor3ShortCycle,,,,,,The system has detected a short cycle event on compressor 3. The compressor has exceeded the maximum number of starts for specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.9.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor4ShortCycle,,,,,,The system has detected a short cycle event on compressor 4. The compressor has exceeded the maximum number of starts for specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressorLowSuctionPressure,,,,,,The pressure at a compressor inlet has dropped below the minimum setting.
.1.3.6.1.4.1.476.1.42.3.2.1.10.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor1LowSuctionPressure,,,,,,The pressure at compressor 1 inlet has dropped below the minimum setting.
.1.3.6.1.4.1.476.1.42.3.2.1.10.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor2LowSuctionPressure,,,,,,The pressure at compressor 2 inlet has dropped below the minimum setting.
.1.3.6.1.4.1.476.1.42.3.2.1.10.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor3LowSuctionPressure,,,,,,The pressure at compressor 3 inlet has dropped below the minimum setting.
.1.3.6.1.4.1.476.1.42.3.2.1.10.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor4LowSuctionPressure,,,,,,The pressure at compressor 4 inlet has dropped below the minimum setting.
.1.3.6.1.4.1.476.1.42.3.2.1.11,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMainFanOverLoad,,,,,,The system has detected a main fan overload condition.
.1.3.6.1.4.1.476.1.42.3.2.1.12,LIEBERT-GP-CONDITIONS-MIB::lgpConditionManualOverride,,,,,,The system has detected a manual override condition.
.1.3.6.1.4.1.476.1.42.3.2.1.13,LIEBERT-GP-CONDITIONS-MIB::lgpConditionStandbyGlycoolPumpOn,,,,,,The standby Glycol or Glycool pump is activated.
.1.3.6.1.4.1.476.1.42.3.2.1.14,LIEBERT-GP-CONDITIONS-MIB::lgpConditionWaterUnderFloor,,,,,,Moisture has been detected under the floor.
.1.3.6.1.4.1.476.1.42.3.2.1.15,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHumidifierProblem,,,,,,The system has detected a humidifier problem.
.1.3.6.1.4.1.476.1.42.3.2.1.16,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowWaterInHumidifier,,,,,,The system has detected a low water condition in the humidifier reservoir.
.1.3.6.1.4.1.476.1.42.3.2.1.17,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSmokeDetected,,,,,,The system has detected smoke.
.1.3.6.1.4.1.476.1.42.3.2.1.18,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowWaterFlow,,,,,,The system has detected a low water flow rate condition.
.1.3.6.1.4.1.476.1.42.3.2.1.19,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLostPower,,,,,,The system has lost power before being switched off using the controls. This condition is activated when power is restored.
.1.3.6.1.4.1.476.1.42.3.2.1.20,LIEBERT-GP-CONDITIONS-MIB::lgpGeneralFault,,,,,,A fault condition has been detected that is not identified in the well known list.
.1.3.6.1.4.1.476.1.42.3.2.1.21,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLocalAlarm,,,,,,This system has detected a local, or customer, alarm condition.
.1.3.6.1.4.1.476.1.42.3.2.1.21.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLocalAlarm1,,,,,,The system has detected that customer alarm condition 1 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.21.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLocalAlarm2,,,,,,The system has detected that customer alarm condition 2 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.21.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLocalAlarm3,,,,,,The system has detected that customer alarm condition 3 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.21.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLocalAlarm4,,,,,,The system has detected that customer alarm condition 4 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.21.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLocalAlarm5,,,,,,The system has detected that customer alarm condition 5 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.21.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLocalAlarm6,,,,,,The system has detected that customer alarm condition 6 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.21.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLocalAlarm7,,,,,,The system has detected that customer alarm condition 7 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.21.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLocalAlarm8,,,,,,The system has detected that customer alarm condition 8 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.22,LIEBERT-GP-CONDITIONS-MIB::lgpConditionStandbyUnitOn,,,,,,The system has detected the standby unit is operating.
.1.3.6.1.4.1.476.1.42.3.2.1.23,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressorLowPressure,,,,,,This system has detected a low head compressor condition.
.1.3.6.1.4.1.476.1.42.3.2.1.23.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor1LowPressure,,,,,,The system has detected low pressure in compressor 1.
.1.3.6.1.4.1.476.1.42.3.2.1.23.1.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionTandemCompressorCircuit1LowPressure,,,,,,The system has detected low pressure in tandem compressor circuit 1.
.1.3.6.1.4.1.476.1.42.3.2.1.23.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor2LowPressure,,,,,,The system has detected low pressure in compressor 2.
.1.3.6.1.4.1.476.1.42.3.2.1.23.2.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionTandemCompressorCircuit2LowPressure,,,,,,The system has detected low pressure in tandem compressor circuit 2.
.1.3.6.1.4.1.476.1.42.3.2.1.23.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor3LowPressure,,,,,,The system has detected low pressure in compressor 3.
.1.3.6.1.4.1.476.1.42.3.2.1.23.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor4LowPressure,,,,,,The system has detected low pressure in compressor 4.
.1.3.6.1.4.1.476.1.42.3.2.1.24,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighWaterInPan,,,,,,The system has detected a high water condition in the condenser pan.
.1.3.6.1.4.1.476.1.42.3.2.1.25,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFaultySensor,,,,,,The system has detected a faulty temperature/humidity sensor.
.1.3.6.1.4.1.476.1.42.3.2.1.26,LIEBERT-GP-CONDITIONS-MIB::lgpConditionServiceCooling,,,,,,The Cooling system requires scheduled maintenance.
.1.3.6.1.4.1.476.1.42.3.2.1.27,LIEBERT-GP-CONDITIONS-MIB::lgpConditionServiceHumidifier,,,,,,The Humidifier requires scheduled maintenance.
.1.3.6.1.4.1.476.1.42.3.2.1.28,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSystemControlBatteryLow,,,,,,Charge level of the system control's battery is below the alarm set point.
.1.3.6.1.4.1.476.1.42.3.2.1.29,LIEBERT-GP-CONDITIONS-MIB::lgpConditionGroundSystemFault,,,,,,The system has detected a ground system fault.
.1.3.6.1.4.1.476.1.42.3.2.1.30,LIEBERT-GP-CONDITIONS-MIB::lgpConditionGroundFailure,,,,,,The system has detected a ground failure.
.1.3.6.1.4.1.476.1.42.3.2.1.31,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSecurityBreach,,,,,,The system has detected a security breach.
.1.3.6.1.4.1.476.1.42.3.2.1.32,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEmergencyShutdown,,,,,,The system has detected an emergency shutdown condition. The System is shutting down as a result of this emergency.
.1.3.6.1.4.1.476.1.42.3.2.1.33,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOnBypass,,,,,,This system has detected the load is being powered by a bypass source.
.1.3.6.1.4.1.476.1.42.3.2.1.33.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLoadOnBypass,,,,,,The load is being powered by a bypass source.
.1.3.6.1.4.1.476.1.42.3.2.1.33.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLoadOnMaintenceBypass,,,,,,The load is being powered by a maintenance bypass source.
.1.3.6.1.4.1.476.1.42.3.2.1.33.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionParallelSysLoadOnBypass,,,,,,The parallel system has transferred to bypass.
.1.3.6.1.4.1.476.1.42.3.2.1.33.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLoadOnBypassByImpact,,,,,,The system has detected a load impact and has transferred the load to the bypass source.
.1.3.6.1.4.1.476.1.42.3.2.1.33.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLoadTransferedToBypass,,,,,,The system has transferred to bypass. The load is being powered by the bypass source.
.1.3.6.1.4.1.476.1.42.3.2.1.33.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEmergencyTransferToBypass,,,,,,The system has performed an emergency transfer to bypass.
.1.3.6.1.4.1.476.1.42.3.2.1.34,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadVoltTHD,,,,,,The total harmonic distortion (THD) of the output voltage has exceeded a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.35,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLogicFailure,,,,,,The system has detected a control logic failure.
.1.3.6.1.4.1.476.1.42.3.2.1.36,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPowerSupplyFault,,,,,,This system had detected a power supply fault condition.
.1.3.6.1.4.1.476.1.42.3.2.1.36.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPowerSupply1Fault,,,,,,The system has detected power supply 1 is in a fault condition.
.1.3.6.1.4.1.476.1.42.3.2.1.36.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPowerSupply2Fault,,,,,,The system has detected power supply 2 is in a fault condition.
.1.3.6.1.4.1.476.1.42.3.2.1.37,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPowerSupplyFailure,,,,,,This system has detected a power supply failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.37.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPowerSupply1Failure,,,,,,The system has detected power supply 1 has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.37.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPowerSupply2Failure,,,,,,The system has detected power supply 2 has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.37.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1PowerSupplyInputFailure,,,,,,The system has detected the source 1 Power supply input has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.37.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2PowerSupplyInputFailure,,,,,,The system has detected the source 2 Power supply input has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.37.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPowerSupplyLogicFailure,,,,,,The system has detected a power supply logic failure.
.1.3.6.1.4.1.476.1.42.3.2.1.37.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressorPowerSupplyFailure,,,,,,The system has detected the power supply to the compressors has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.38,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOverVoltage,,,,,,This system has detected an over voltage condition.
.1.3.6.1.4.1.476.1.42.3.2.1.38.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1OverVoltage,,,,,,The system has detected an over voltage condition on source 1. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.38.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2OverVoltage,,,,,,The system has detected an over voltage condition on source 2. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.38.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadOverVoltage,,,,,,The system has detected the output to load is in an over-voltage condition. The voltage for the load has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.38.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputOverVoltage,,,,,,The system has detected an input over voltage condition. The voltage measurement has risen above a pre-determined threshold for a specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.38.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassOverVoltage,,,,,,The system has detected an over voltage condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.38.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassOverVoltageFailure,,,,,,The system has detected an over voltage failure condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.38.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryOverVoltage,,,,,,The system has detected a battery over voltage condition.
.1.3.6.1.4.1.476.1.42.3.2.1.38.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcBusOverVoltage,,,,,,This system has detected a DC Bus over voltage condition.
.1.3.6.1.4.1.476.1.42.3.2.1.38.8.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcBus1OverVoltage,,,,,,The system has detected an over voltage condition on DC Bus 1.
.1.3.6.1.4.1.476.1.42.3.2.1.38.8.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcBus2OverVoltage,,,,,,The system has detected an over voltage condition on DC Bus 2.
.1.3.6.1.4.1.476.1.42.3.2.1.38.8.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcBus1OverVoltageFailure,,,,,,The system has detected an over voltage failure condition on DC Bus 1.
.1.3.6.1.4.1.476.1.42.3.2.1.38.8.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcBus2OverVoltageFailure,,,,,,The system has detected an over voltage failure condition on DC Bus 2.
.1.3.6.1.4.1.476.1.42.3.2.1.39,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnderVoltage,,,,,,This system has detected an under voltage condition.
.1.3.6.1.4.1.476.1.42.3.2.1.39.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1UnderVoltage,,,,,,The system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.39.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2UnderVoltage,,,,,,The system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.39.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadUnderVoltage,,,,,,The system has detected the output to load is in an under-voltage condition. The voltage for the load has fallen below a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.39.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1UnderVoltageRMS,,,,,,The system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.39.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2UnderVoltageRMS,,,,,,The system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.39.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputUnderVoltage,,,,,,The system has detected an input under voltage condition. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.39.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassUnderVoltage,,,,,,The system has detected an under voltage condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.39.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassUnderVoltageFailure,,,,,,The system has detected an under voltage failure condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.39.9,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryUnderVoltage,,,,,,The system has detected a battery under voltage condition.
.1.3.6.1.4.1.476.1.42.3.2.1.39.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcBusUnderVoltage,,,,,,This system has detected a DC bus under voltage condition
.1.3.6.1.4.1.476.1.42.3.2.1.39.10.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcBus1UnderVoltage,,,,,,The system has detected an under voltage condition on DC Bus 1.
.1.3.6.1.4.1.476.1.42.3.2.1.39.10.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcBus2UnderVoltage,,,,,,The system has detected an under voltage condition on DC Bus 2.
.1.3.6.1.4.1.476.1.42.3.2.1.39.10.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcBus1UnderVoltageFailure,,,,,,The system has detected an under voltage failure condition on DC Bus 1.
.1.3.6.1.4.1.476.1.42.3.2.1.39.10.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcBus2UnderVoltageFailure,,,,,,The system has detected an under voltage failure condition on DC Bus 2.
.1.3.6.1.4.1.476.1.42.3.2.1.40,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOverload,,,,,,This system has detected an overload condition.
.1.3.6.1.4.1.476.1.42.3.2.1.40.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1Overload,,,,,,The system has detected an overload condition on source 1. The power requirement for this source has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.40.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSystemOverload,,,,,,The system has detected an overload condition.
.1.3.6.1.4.1.476.1.42.3.2.1.40.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1PeakCurrentOverLoad,,,,,,The system has detected source 1 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for a specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.40.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2PeakCurrentOverLoad,,,,,,The system has detected source 2 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for a specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.40.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadOverLimit,,,,,,The system had detected that the output to the load has exceeded the lgpPwrOutputToLoadUserOverloadLimit.
.1.3.6.1.4.1.476.1.42.3.2.1.40.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadOverload,,,,,,The system has detected an output overload condition.
.1.3.6.1.4.1.476.1.42.3.2.1.40.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionParallelSysOverload,,,,,,The parallel system has detected an overload condition.
.1.3.6.1.4.1.476.1.42.3.2.1.40.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassCurrentOverload,,,,,,With the load on bypass static switch, the measured output RMS current has exceeded a specified percentage of the nominal RMS current.
.1.3.6.1.4.1.476.1.42.3.2.1.40.8.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassCurrentOverloadPhsA,,,,,,With the load on bypass static switch, the measured phase A output RMS current has exceeded a specified percentage of the nominal per-phase RMS current.
.1.3.6.1.4.1.476.1.42.3.2.1.40.8.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassCurrentOverloadPhsB,,,,,,With the load on bypass static switch, the measured phase B output RMS current has exceeded a specified percentage of the nominal per-phase RMS current.
.1.3.6.1.4.1.476.1.42.3.2.1.40.8.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassCurrentOverloadPhsC,,,,,,With the load on bypass static switch, the measured phase C output RMS current has exceeded a specified percentage of the nominal per-phase RMS current.
.1.3.6.1.4.1.476.1.42.3.2.1.41,LIEBERT-GP-CONDITIONS-MIB::lgpConditionScrShort,,,,,,This system has detected a Silicon Controlled Rectifier (SCR) short condition.
.1.3.6.1.4.1.476.1.42.3.2.1.41.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1ScrShort,,,,,,The system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition.
.1.3.6.1.4.1.476.1.42.3.2.1.41.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2ScrShort,,,,,,The system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition.
.1.3.6.1.4.1.476.1.42.3.2.1.41.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassScrShort,,,,,,The system has detected a Silicon Controlled Rectifier (SCR) short condition on the bypass.
.1.3.6.1.4.1.476.1.42.3.2.1.41.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInvStaticSwScrShort,,,,,,The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCRs).
.1.3.6.1.4.1.476.1.42.3.2.1.41.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1NeutralScrShort,,,,,,The system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition on the neutral line.
.1.3.6.1.4.1.476.1.42.3.2.1.41.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2NeutralScrShort,,,,,,The system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition on the neutral line.
.1.3.6.1.4.1.476.1.42.3.2.1.42,LIEBERT-GP-CONDITIONS-MIB::lgpConditionScrOpen,,,,,,This system has detected a Silicon Controlled Rectifier (SCR) open condition.
.1.3.6.1.4.1.476.1.42.3.2.1.42.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1ScrOpen,,,,,,The system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition.
.1.3.6.1.4.1.476.1.42.3.2.1.42.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2ScrOpen,,,,,,The system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition.
.1.3.6.1.4.1.476.1.42.3.2.1.42.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassScrOpen,,,,,,The system has detected a Silicon Controlled Rectifier (SCR) open condition on the bypass.
.1.3.6.1.4.1.476.1.42.3.2.1.42.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1NeutralScrOpen,,,,,,The system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition on the neutral line.
.1.3.6.1.4.1.476.1.42.3.2.1.42.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2NeutralScrOpen,,,,,,The system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition on the neutral line.
.1.3.6.1.4.1.476.1.42.3.2.1.43,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFanFailure,,,,,,This system has detected a fan failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.43.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFan1Failure,,,,,,The system has detected a fan 1 failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.43.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRedundantFanFailure,,,,,,A failure has occurred in a fan that cools the system's internal components and has resulted in a loss of fan redundancy.
.1.3.6.1.4.1.476.1.42.3.2.1.43.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMultipleFanFailure,,,,,,Multiple fans have failed resulting in a decreased ability to cool the system's internal components.
.1.3.6.1.4.1.476.1.42.3.2.1.43.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBlowerFanFailure,,,,,,The system has detected a problem with one or more of the blower fans. These are not the system internal cooling fans.
.1.3.6.1.4.1.476.1.42.3.2.1.43.4.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBottomBlowerFanFailure,,,,,,The bottom environmental unit blower fan is not operating within its normal parameters.
.1.3.6.1.4.1.476.1.42.3.2.1.43.4.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionTopBlowerFanFailure,,,,,,The top environmental unit blower fan is not operating within its normal parameters.
.1.3.6.1.4.1.476.1.42.3.2.1.43.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCondenserFanVFDFailure,,,,,,The system has detected a problem with the Variable Frequency Drive system for the condenser fan.
.1.3.6.1.4.1.476.1.42.3.2.1.43.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFanPowerFailure,,,,,,The system has detected a power failure on one or more fans.
.1.3.6.1.4.1.476.1.42.3.2.1.44,LIEBERT-GP-CONDITIONS-MIB::lgpConditionTransferInhibited,,,,,,The system is preventing a transfer of the load to the alternate source.
.1.3.6.1.4.1.476.1.42.3.2.1.45,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAutoReTransferPrimed,,,,,,The system is capable to retransfer to the preferred source.
.1.3.6.1.4.1.476.1.42.3.2.1.46,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSourcesOutOfSync,,,,,,The system has detected that the input sources are not within the specified phase difference (synchronization window).
.1.3.6.1.4.1.476.1.42.3.2.1.47,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSourceFailure,,,,,,This system has detected an input source failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.47.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1Failure,,,,,,The system has detected source 1 has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.47.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2Failure,,,,,,The system has detected source 2 has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.48,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAutoReTransferInhibited,,,,,,The system is preventing a retransfer of the load back to the preferred source.
.1.3.6.1.4.1.476.1.42.3.2.1.49,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAutoReTransferFailed,,,,,,The system is failing to automatically retransfer the load back to the preferred source.
.1.3.6.1.4.1.476.1.42.3.2.1.50,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFuseOpen,,,,,,This system has detected an open fuse condition.
.1.3.6.1.4.1.476.1.42.3.2.1.50.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlFuse1Open,,,,,,The system has detected a control power fuse 1 open condition.
.1.3.6.1.4.1.476.1.42.3.2.1.50.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlFuse2Open,,,,,,The system has detected a control power fuse 2 open condition.
.1.3.6.1.4.1.476.1.42.3.2.1.50.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRectifierFuseOpen,,,,,,The system has detected a rectifier fuse open condition.
.1.3.6.1.4.1.476.1.42.3.2.1.50.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterFuseOpen,,,,,,The system has detected an inverter fuse open condition.
.1.3.6.1.4.1.476.1.42.3.2.1.50.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadFuseOpen,,,,,,The system has detected an output to load fuse open condition.
.1.3.6.1.4.1.476.1.42.3.2.1.50.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcCapacitorFuseOpen,,,,,,The system has detected a DC capacitor fuse open condition.
.1.3.6.1.4.1.476.1.42.3.2.1.51,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDisconnect,,,,,,The system has detected a disconnect condition.
.1.3.6.1.4.1.476.1.42.3.2.1.51.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1DisconnectOpen,,,,,,The system has detected the source 1 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2DisconnectOpen,,,,,,The system has detected the source 2 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1PduDisconnectOpen,,,,,,The system has detected the source 1 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2PduDisconnectOpen,,,,,,The system has detected the source 2 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadDisconnect1Open,,,,,,The system has detected Output to load disconnect 1 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadDisconnect2Open,,,,,,The system has detected Output to load disconnect 2 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1BypassDisconnectClosed,,,,,,The system has detected the source 1 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2BypassDisconnectClosed,,,,,,The system has detected the source 2 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.9,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadNeutralDisconnectOpen,,,,,,The system has detected the output to load neutral disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryDisconnectOpen,,,,,,The system has detected the battery disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.10.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryDiscOpenCab01,,,,,,The system has detected the cabinet 1 battery disconnect is open.
.1.3.6.1.4.1.476.1.42.3.2.1.51.10.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryDiscOpenCab02,,,,,,The system has detected the cabinet 2 battery disconnect is open.
.1.3.6.1.4.1.476.1.42.3.2.1.51.10.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryDiscOpenCab03,,,,,,The system has detected the cabinet 3 battery disconnect is open.
.1.3.6.1.4.1.476.1.42.3.2.1.51.10.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryDiscOpenCab04,,,,,,The system has detected the cabinet 4 battery disconnect is open.
.1.3.6.1.4.1.476.1.42.3.2.1.51.10.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryDiscOpenCab05,,,,,,The system has detected the cabinet 5 battery disconnect is open.
.1.3.6.1.4.1.476.1.42.3.2.1.51.10.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryDiscOpenCab06,,,,,,The system has detected the cabinet 6 battery disconnect is open.
.1.3.6.1.4.1.476.1.42.3.2.1.51.10.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryDiscOpenCab07,,,,,,The system has detected the cabinet 7 battery disconnect is open.
.1.3.6.1.4.1.476.1.42.3.2.1.51.10.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryDiscOpenCab08,,,,,,The system has detected the cabinet 8 battery disconnect is open.
.1.3.6.1.4.1.476.1.42.3.2.1.51.11,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputDisconnectOpen,,,,,,The system has detected the input disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.12,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadDisconnectOpen,,,,,,The system has detected the Output to load disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.13,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassDisconnectOpen,,,,,,The system has detected the bypass disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.14,LIEBERT-GP-CONDITIONS-MIB::lgpConditionStaticSwitchDisconnectOpen,,,,,,The system has detected the static switch disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.51.15,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBreakerOpenFailure,,,,,,A breaker in the system has failed to respond to an Open signal.
.1.3.6.1.4.1.476.1.42.3.2.1.51.16,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBreakerCloseFailure,,,,,,A breaker in the system has failed to respond to a Close signal.
.1.3.6.1.4.1.476.1.42.3.2.1.52,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFrequencyDeviation,,,,,,This system has detected a frequency deviation condition. The frequency of a source is outside of the pre-determined thresholds for a specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.52.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1FrequencyDeviation,,,,,,The frequency for source 1 has been outside of the pre-determined thresholds for a specified period of time.
.1.3.6.1.4.1.476.1.42.3.2.1.52.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2FrequencyDeviation,,,,,,The frequency for source 2 has been outside of the pre-determined thresholds for a specified period of time.
.1.3.6.1.4.1.476.1.42.3.2.1.52.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputFrequencyDeviation,,,,,,The frequency for the input has been outside of the pre-determined thresholds for a specified period of time.
.1.3.6.1.4.1.476.1.42.3.2.1.52.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadFrequencyDeviation,,,,,,The frequency for the output has been outside of the pre-determined thresholds for a specified period of time.
.1.3.6.1.4.1.476.1.42.3.2.1.52.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassFrequencyDeviation,,,,,,The frequency for the bypass input has been outside of the pre-determined thresholds for a specified period of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOverCurrent,,,,,,This system has detected an over-current condition. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1OverCurrent,,,,,,The system has detected an over current condition on source 1. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2OverCurrent,,,,,,The system has detected an over current condition on source 2. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadOverCurrent,,,,,,The system has detected the output to load is in an over-current condition. The current for the load has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.3.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadOverCurrentPhsA,,,,,,The system has detected the output to load on phase A is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.3.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadOverCurrentPhsB,,,,,,The system has detected the output to load on phase B is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.3.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadOverCurrentPhsC,,,,,,The system has detected the output to load on phase C is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionGroundOverCurrent,,,,,,A ground source is experiencing an over-current condition. The current for the ground line has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRectifierOverCurrent,,,,,,The system has detected a rectifier over current condition. The current for the rectifier has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterOverCurrent,,,,,,The system has detected an inverter over current condition. The current for the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.6.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterOverCurrentPhsA,,,,,,The system has detected an inverter over current condition on phase A. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.6.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterOverCurrentPhsB,,,,,,The system has detected an inverter over current condition on phase B. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.6.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterOverCurrentPhsC,,,,,,The system has detected an inverter over current condition on phase C. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryConverterOverCurrent,,,,,,The system has detected an over current condition on the battery converter. The current of the converter has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryBalancerOverCurrent,,,,,,The system has detected a battery balancer over current condition. The current at this point has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.9,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHumidifierOverCurrent,,,,,,The system has detected an over current condition on the humidifier. The current of the humidifier has risen above a pre-determined threshold for a defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputOverCurrent,,,,,,There is an over current condition on the system input power. The input current has risen above a pre-determined threshold for a pre-defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.11,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1NeutralOverCurrent,,,,,,The system has detected an over current condition on the neutral line of source 1. The neutral current at source 1 has risen above a pre-determined threshold for a pre-defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.53.12,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2NeutralOverCurrent,,,,,,The system has detected an over current condition on the neutral line of source 2. The neutral current at source 2 has risen above a pre-determined threshold for a pre-defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.54,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSensorFailure,,,,,,This system has detected a sensor failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.54.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadVoltageSensorFailure,,,,,,The system had detected an output to load voltage sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1VoltageSensorFailure,,,,,,The system had detected a source 1 voltage sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2VoltageSensorFailure,,,,,,The system had detected a source 2 voltage sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1ScrSensorFailure,,,,,,The system had detected a source 1 SCR (Silicon Controlled Rectifier) sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2ScrSensorFailure,,,,,,The system had detected a source 2 SCR (Silicon Controlled Rectifier) sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1CurrentSensorFailure,,,,,,The system has detected a source 1 current sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2CurrentSensorFailure,,,,,,The system has detected a source 2 current sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRoomTempHumiditySensorFailure,,,,,,The system has detected a device temperature and humidity sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.9,LIEBERT-GP-CONDITIONS-MIB::lgpConditionGlycolTempSensorFailure,,,,,,The system has detected a glycol temperature sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLocal1SensorFailure,,,,,,The system has detected a local 1 sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.11,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor1SensorFailure,,,,,,The system has detected a compressor 1 digital scroll sensor failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.54.12,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor2SensorFailure,,,,,,The system has detected a compressor 2 digital scroll sensor failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.54.13,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSupplySensorFailure,,,,,,The system has detected a supply sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.14,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCabinetTemperatureSensorFailure,,,,,,The system has detected a cabinet temperature sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.15,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCabinetHumiditySensorFailure,,,,,,The system has detected a cabinet humidity sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.16,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRoomTempSensorFailure,,,,,,The system has detected a room temperature sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.17,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryTempSensorFailure,,,,,,The system has detected a battery temperature sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.1.54.18,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAirSensorAFailure,,,,,,The system has detected a failure with air sensor A. The sensor may have been disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.19,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAirSensorBFailure,,,,,,The system has detected a failure with air sensor B. The sensor may have been disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.20,LIEBERT-GP-CONDITIONS-MIB::lgpConditionChilledWaterSupplySensorFailure,,,,,,The system has detected a failure with the chilled water supply sensor. The sensor may have been disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.21,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRefrigerantSupplySensorFailure,,,,,,The system has detected a failure with the refrigerant supply sensor. The sensor may have been disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.22,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFluidSupplySensorFailure,,,,,,The system has detected a failure with the fluid supply sensor. The sensor may have been disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.23,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressorLowPressureSensorFailure,,,,,,The system has detected that a compressor low pressure transducer is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.23.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor1LowPressureSensorFailure,,,,,,The system has detected that compressor 1 low pressure transducer is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.24,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRemoteSensorFailure,,,,,,The system has detected that a remote sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.25,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAirSupplyTempSensorFailure,,,,,,The system has detected that the supply air temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.26,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAirReturnTempSensorFailure,,,,,,The system has detected that the return air temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.27,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressorHighPressureSensorFailure,,,,,,The system has detected that a compressor high pressure transducer is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.27.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor2HighPressureSensorFailure,,,,,,The system has detected that compressor 2 high pressure transducer is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.27.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor3HighPressureSensorFailure,,,,,,The system has detected that compressor 3 high pressure transducer is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.54.27.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressor4HighPressureSensorFailure,,,,,,The system has detected that compressor 4 high pressure transducer is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.55,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInternalCommunicationFailure,,,,,,This system has detected an internal communication failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.56,LIEBERT-GP-CONDITIONS-MIB::lgpConditionExternalCommunicationFailure,,,,,,This system has detected an external communication failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.57,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSourceGateDriveFailure,,,,,,This system has detected a source gate drive failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.57.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1GateDriveFailure,,,,,,The system has detected a source 1 gate drive failure.
.1.3.6.1.4.1.476.1.42.3.2.1.57.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2GateDriveFailure,,,,,,The system has detected a source 2 gate drive failure.
.1.3.6.1.4.1.476.1.42.3.2.1.58,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDisconnectFailure,,,,,,This system has detected a disconnect failure condition. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.58.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadNeutralDisconnectFailure,,,,,,The system has detected the output to load neutral disconnect has failed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.58.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1DisconnectShuntTripFailure,,,,,,The system has detected a shunt trip failure of a disconnecting device on source 1. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.58.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2DisconnectShuntTripFailure,,,,,,The system has detected a shunt trip failure of a disconnecting device on source 2. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.58.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterDisconnectFailure,,,,,,The system has detected an inverter disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.58.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryDisconnectFailure,,,,,,The system has detected a battery disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.58.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRectifierDisconnectFailure,,,,,,The system has detected a rectifier disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
.1.3.6.1.4.1.476.1.42.3.2.1.59,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOverTemperature,,,,,,This system has detected an over temperature condition.
.1.3.6.1.4.1.476.1.42.3.2.1.59.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHeatSink1OverTemperature,,,,,,The system has detected a heat sink 1 over temperature condition.
.1.3.6.1.4.1.476.1.42.3.2.1.59.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAmbient1OverTemperature,,,,,,The system has detected an ambient over temperature condition at location 1.
.1.3.6.1.4.1.476.1.42.3.2.1.59.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSystemOverTemperature,,,,,,The system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.59.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionTransformerOverTemperature,,,,,,The transformer is experiencing an over temperature condition. The transformer's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.59.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryOverTemperature,,,,,,The battery is experiencing an over temperature condition. The battery's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.59.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRectifierOverTemperature,,,,,,The system has detected a rectifier over temperature condition. The rectifier's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.59.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterOverTemperature,,,,,,The system has detected an inverter over temperature condition. The inverter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.59.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRectifierInductorOverTemperature,,,,,,The system has detected a rectifier inductor over temperature condition. The rectifier's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.59.9,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterInductorOverTemperature,,,,,,The system has detected an inverter inductor over temperature condition. The inverter's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.59.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryConverterOverTemperature,,,,,,The system has detected a battery converter over temperature condition. The battery converter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.59.11,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryBalancerInductorOverTemperature,,,,,,The system has detected a battery balancer Inductor over temperature condition. The battery balancer Inductor's temperature has exceeded a pre-determined threshold for a specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.59.12,LIEBERT-GP-CONDITIONS-MIB::lgpConditionChilledWaterOverTemperature,,,,,,The system has detected a chilled water over temperature condition.
.1.3.6.1.4.1.476.1.42.3.2.1.59.13,LIEBERT-GP-CONDITIONS-MIB::lgpConditionElectricHeatersOverTemperature,,,,,,The system has detected an electric heater over temperature condition.
.1.3.6.1.4.1.476.1.42.3.2.1.59.14,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInletAirOverTemperature,,,,,,The system has detected an inlet air over temperature condition.
.1.3.6.1.4.1.476.1.42.3.2.1.59.15,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSystemOverTempWarning,,,,,,The system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a normal operating range for a device, or system, defined amount of time. The system is still operational but a threshold has been exceeded.
.1.3.6.1.4.1.476.1.42.3.2.1.59.16,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureBattString,,,,,,The system has detected a high temperature on a battery string. The temperature has exceeded a specified temperature threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.60,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLoadOnAlternateSource,,,,,,The system has detected that the load is being supplied by the alternate source.
.1.3.6.1.4.1.476.1.42.3.2.1.61,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPhaseRotationError,,,,,,This system has detected a phase rotation error condition.
.1.3.6.1.4.1.476.1.42.3.2.1.61.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource1PhaseRotationError,,,,,,The system has detected a phase rotation error on source 1.
.1.3.6.1.4.1.476.1.42.3.2.1.61.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSource2PhaseRotationError,,,,,,The system has detected a phase rotation error on source 2.
.1.3.6.1.4.1.476.1.42.3.2.1.61.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassPhaseRotationError,,,,,,The system has detected a phase rotation error on the bypass.
.1.3.6.1.4.1.476.1.42.3.2.1.61.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputPhaseRotationError,,,,,,The system has detected a phase rotation error on the input.
.1.3.6.1.4.1.476.1.42.3.2.1.62,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlModuleFailure,,,,,,This system has detected a control module failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.62.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlModule1Failure,,,,,,The system has detected a control module 1 failure.
.1.3.6.1.4.1.476.1.42.3.2.1.63,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHistoryLogFull,,,,,,The system has detected the history log is full.
.1.3.6.1.4.1.476.1.42.3.2.1.64,LIEBERT-GP-CONDITIONS-MIB::lgpConditionConfigurationModified,,,,,,The system has detected the configuration has been modified.
.1.3.6.1.4.1.476.1.42.3.2.1.65,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPasswordModified,,,,,,The system has detected the password has been modified.
.1.3.6.1.4.1.476.1.42.3.2.1.66,LIEBERT-GP-CONDITIONS-MIB::lgpConditionTimeModified,,,,,,The system has detected the time has been modified.
.1.3.6.1.4.1.476.1.42.3.2.1.67,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDateModified,,,,,,The system has detected the date has been modified.
.1.3.6.1.4.1.476.1.42.3.2.1.68,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEventLogCleared,,,,,,The system has detected the event log has been cleared.
.1.3.6.1.4.1.476.1.42.3.2.1.69,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHistoryLogCleared,,,,,,The system has detected the history log has been cleared.
.1.3.6.1.4.1.476.1.42.3.2.1.70,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUtilityFailure,,,,,,The system has detected a utility failure.
.1.3.6.1.4.1.476.1.42.3.2.1.71,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryTestInProgress,,,,,,The system is performing a battery test at this time.
.1.3.6.1.4.1.476.1.42.3.2.1.72,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLoadOnBattery,,,,,,The system load is being supported by the battery.
.1.3.6.1.4.1.476.1.42.3.2.1.74,LIEBERT-GP-CONDITIONS-MIB::lgpConditionReplaceBattery,,,,,,The system has detected the batteries are due to be replaced.
.1.3.6.1.4.1.476.1.42.3.2.1.75,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUpsShutdownPending,,,,,,The system is in a shutdown pending condition.
.1.3.6.1.4.1.476.1.42.3.2.1.76,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryChargerFailed,,,,,,The system has detected the battery charger has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.77,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassVoltageUnqualified,,,,,,The system has detected the bypass voltage is unqualified. The voltage measurement is outside a pre-determined threshold range for a specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.78,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCheckAirFilter,,,,,,The system has detected it is time to check the air filter.
.1.3.6.1.4.1.476.1.42.3.2.1.79,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBrownOut,,,,,,The system has detected a brown out condition.
.1.3.6.1.4.1.476.1.42.3.2.1.80,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMultipleTransferLockout,,,,,,The system has locked out transfers to bypass. Too many transfers have occurred over a specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.81,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassPhaseLost,,,,,,The system has detected one or more bypass phases are missing.
.1.3.6.1.4.1.476.1.42.3.2.1.82,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMaintenceBypassInhibited,,,,,,The system is preventing a transfer of the load to maintenance bypass.
.1.3.6.1.4.1.476.1.42.3.2.1.83,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLoadLockedOnBypass,,,,,,An error has been detected requiring the system to be put into a 'locked on bypass' state.
.1.3.6.1.4.1.476.1.42.3.2.1.84,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadShort,,,,,,The system has detected an output to load short circuit condition.
.1.3.6.1.4.1.476.1.42.3.2.1.85,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEmergencyTransferToInverter,,,,,,The system has detected an emergency transfer of the load to inverter.
.1.3.6.1.4.1.476.1.42.3.2.1.86,LIEBERT-GP-CONDITIONS-MIB::lgpConditonEmergencyPowerOff,,,,,,The system has detected an Emergency Power Off (EPO) condition. An external EPO switch has cut off the power source to the system.
.1.3.6.1.4.1.476.1.42.3.2.1.87,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterBackFeed,,,,,,The system has detected an inverter back-feed condition. The inverter is feeding power through the bypass back to the input.
.1.3.6.1.4.1.476.1.42.3.2.1.88,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcGroundFault,,,,,,The system has detected a DC ground fault.
.1.3.6.1.4.1.476.1.42.3.2.1.88.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcGroundFaultPos,,,,,,Ground fault current has been detected in the positive DC link to ground.
.1.3.6.1.4.1.476.1.42.3.2.1.88.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDcGroundFaultNeg,,,,,,Ground fault current has been detected in the negative DC link to ground.
.1.3.6.1.4.1.476.1.42.3.2.1.89,LIEBERT-GP-CONDITIONS-MIB::lgpConditionStaticTransferSwitchInhibited,,,,,,The system is preventing the use of the static transfer switch.
.1.3.6.1.4.1.476.1.42.3.2.1.90,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryLogFullWarning,,,,,,The system has detected the battery log is approaching the maximum record limit.
.1.3.6.1.4.1.476.1.42.3.2.1.91,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputCurrentUnbalanced,,,,,,The system has detected an unbalanced input current condition. The currents of input phases are out of tolerance.
.1.3.6.1.4.1.476.1.42.3.2.1.92,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSelfTestFailed,,,,,,The system has detected a self-test failure.
.1.3.6.1.4.1.476.1.42.3.2.1.93,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterOutOfSynchronization,,,,,,The system has detected an Inverter out of sync condition.
.1.3.6.1.4.1.476.1.42.3.2.1.94,LIEBERT-GP-CONDITIONS-MIB::lgpConditionModuleAlarm,,,,,,This system has detected an alarm within the multi-module system.
.1.3.6.1.4.1.476.1.42.3.2.1.94.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditioniModuleUnit1Alarm,,,,,,The multi-module system has detected an alarm condition on unit 1.
.1.3.6.1.4.1.476.1.42.3.2.1.94.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditioniModuleUnit2Alarm,,,,,,The multi-module system has detected an alarm condition on unit 2.
.1.3.6.1.4.1.476.1.42.3.2.1.94.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditioniModuleUnit3Alarm,,,,,,The multi-module system has detected an alarm condition on unit 3.
.1.3.6.1.4.1.476.1.42.3.2.1.94.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditioniModuleUnit4Alarm,,,,,,The multi-module system has detected an alarm condition on unit 4.
.1.3.6.1.4.1.476.1.42.3.2.1.94.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditioniModuleUnit5Alarm,,,,,,The multi-module system has detected an alarm condition on unit 5.
.1.3.6.1.4.1.476.1.42.3.2.1.94.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditioniModuleUnit6Alarm,,,,,,The multi-module system has detected an alarm condition on unit 6.
.1.3.6.1.4.1.476.1.42.3.2.1.94.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditioniModuleUnit7Alarm,,,,,,The multi-module system has detected an alarm condition on unit 7.
.1.3.6.1.4.1.476.1.42.3.2.1.94.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditioniModuleUnit8Alarm,,,,,,The multi-module system has detected an alarm condition on unit 8.
.1.3.6.1.4.1.476.1.42.3.2.1.95,LIEBERT-GP-CONDITIONS-MIB::lgpConditionActiveModuleAlarm,,,,,,The system has detected an active alarm in one, or more, of the sub-modules of the multi-module system.
.1.3.6.1.4.1.476.1.42.3.2.1.96,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlFailure,,,,,,This system has detected a control failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.96.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMainControlFailure,,,,,,The system has detected a main control failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.96.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRedundantControlFailure,,,,,,The system has detected a redundant control failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.96.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionParallelSysControlFailure,,,,,,The parallel system has detected a control failure condition with one of the controls.
.1.3.6.1.4.1.476.1.42.3.2.1.96.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMainControlCommFailure,,,,,,One or more communications failures have occurred in the main control.
.1.3.6.1.4.1.476.1.42.3.2.1.96.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlBoardFailure,,,,,,The system has detected a control board failure.
.1.3.6.1.4.1.476.1.42.3.2.1.96.5.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHumidifierControlBdFailure,,,,,,Humidifier control board is required to be connected, but no signal is detected.
.1.3.6.1.4.1.476.1.42.3.2.1.97,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlWarning,,,,,,This system has detected a control warning conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.97.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMainControlWarning,,,,,,The system has detected a main control warning condition.
.1.3.6.1.4.1.476.1.42.3.2.1.97.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRedundantControlWarning,,,,,,The system has detected a redundant control warning condition.
.1.3.6.1.4.1.476.1.42.3.2.1.98,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUserInterfaceFailure,,,,,,The system has detected a user interface control failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.99,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLostPowerRedundancy,,,,,,The system has detected the number of redundant power modules has fallen below the minimum redundant power module setting.
.1.3.6.1.4.1.476.1.42.3.2.1.100,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPowerModuleFailure,,,,,,The system has detected a power module failure condition in the system.
.1.3.6.1.4.1.476.1.42.3.2.1.101,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryModuleFailure,,,,,,The system has detected a battery module failure condition in the system.
.1.3.6.1.4.1.476.1.42.3.2.1.102,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadOff,,,,,,The system has detected that there is no power being supplied to the load.
.1.3.6.1.4.1.476.1.42.3.2.1.103,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSystemOff,,,,,,The system is off.
.1.3.6.1.4.1.476.1.42.3.2.1.104,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRectifierStartupFailure,,,,,,The system has detected a rectifier under voltage start-up failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.105,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRectifierFault,,,,,,The system has detected a rectifier fault condition.
.1.3.6.1.4.1.476.1.42.3.2.1.106,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterShutdownLowDc,,,,,,The system has shutdown the inverter due to a DC bus under voltage.
.1.3.6.1.4.1.476.1.42.3.2.1.107,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterFault,,,,,,The system has detected an inverter fault condition.
.1.3.6.1.4.1.476.1.42.3.2.1.108,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterDcOffsetOverrun,,,,,,The system has detected an over run of the inverter DC offset voltage.
.1.3.6.1.4.1.476.1.42.3.2.1.109,LIEBERT-GP-CONDITIONS-MIB::lgpConditionParallelSysLowBatteryWarning,,,,,,The parallel system has detected a low battery warning condition.
.1.3.6.1.4.1.476.1.42.3.2.1.110,LIEBERT-GP-CONDITIONS-MIB::lgpConditionParallelSysLoadShareFault,,,,,,The parallel system has detected a load share fault condition.
.1.3.6.1.4.1.476.1.42.3.2.1.111,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryFault,,,,,,The system has detected a battery fault condition. The battery conductors are either reversed or disconnected.
.1.3.6.1.4.1.476.1.42.3.2.1.112,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryConverterFailure,,,,,,The system has detected a battery converter failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.113,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryBalancerFault,,,,,,The system has detected a battery balancer fault condition.
.1.3.6.1.4.1.476.1.42.3.2.1.114,LIEBERT-GP-CONDITIONS-MIB::lgpConditionpsUpsOperationFault,,,,,,The system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence.
.1.3.6.1.4.1.476.1.42.3.2.1.115,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadOnJointMode,,,,,,The system load is being supported by both the battery and rectifier.
.1.3.6.1.4.1.476.1.42.3.2.1.116,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputNeutralLost,,,,,,The system had detected the main input neutral is disconnected.
.1.3.6.1.4.1.476.1.42.3.2.1.117,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowBatteryWarning,,,,,,The battery's remaining charge is less than or equal to the configured low threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.118,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInternalFault,,,,,,The system has detected an internal fault.
.1.3.6.1.4.1.476.1.42.3.2.1.119,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryTestFailed,,,,,,The system has detected a battery self-test failure.
.1.3.6.1.4.1.476.1.42.3.2.1.120,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPowerModuleWarning,,,,,,The system has detected an alarm condition on one, or more, power modules.
.1.3.6.1.4.1.476.1.42.3.2.1.121,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryModuleWarning,,,,,,The system has detected an alarm condition on one, or more, battery modules.
.1.3.6.1.4.1.476.1.42.3.2.1.122,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlModuleWarning,,,,,,The system has detected a control module warning.
.1.3.6.1.4.1.476.1.42.3.2.1.123,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUpsOperationFault,,,,,,The system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence.
.1.3.6.1.4.1.476.1.42.3.2.1.124,LIEBERT-GP-CONDITIONS-MIB::lgpConditionActiveAlarm,,,,,,The system has detected an alarm condition.
.1.3.6.1.4.1.476.1.42.3.2.1.125,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRectifierCommunicationFailure,,,,,,The system has detected an internal communication failure condition with the rectifier.
.1.3.6.1.4.1.476.1.42.3.2.1.126,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterCommunicationFailure,,,,,,The system has detected an internal communication failure condition with the inverter.
.1.3.6.1.4.1.476.1.42.3.2.1.127,LIEBERT-GP-CONDITIONS-MIB::lgpConditionParallelSysConnectionFault,,,,,,The parallel system has detected a connection fault. One or more of the devices are not properly connected.
.1.3.6.1.4.1.476.1.42.3.2.1.128,LIEBERT-GP-CONDITIONS-MIB::lgpConditionParallelSysCommunicationFailure,,,,,,The parallel system has detected a communication failure.
.1.3.6.1.4.1.476.1.42.3.2.1.129,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLostBatteryRedundancy,,,,,,The system has detected the number of redundant battery modules has fallen below the configured redundant battery module threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.130,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompPumpDownFailure,,,,,,The system has detected that a compressor has failed to pump down.
.1.3.6.1.4.1.476.1.42.3.2.1.130.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionComp1PumpDownFailure,,,,,,The system has detected that compressor 1 has failed to pump down.
.1.3.6.1.4.1.476.1.42.3.2.1.130.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionComp2PumpDownFailure,,,,,,The system has detected that compressor 2 has failed to pump down.
.1.3.6.1.4.1.476.1.42.3.2.1.130.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionComp3PumpDownFailure,,,,,,The system has detected that compressor 3 has failed to pump down.
.1.3.6.1.4.1.476.1.42.3.2.1.130.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionComp4PumpDownFailure,,,,,,The system has detected that compressor 4 has failed to pump down.
.1.3.6.1.4.1.476.1.42.3.2.1.131,LIEBERT-GP-CONDITIONS-MIB::lgpConditionChilledWaterLowWaterFlow,,,,,,The system has detected a chilled water low water flow condition.
.1.3.6.1.4.1.476.1.42.3.2.1.131.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionChilledWaterLowWaterFlowCircuit2,,,,,,The system has detected a chilled water low water flow condition for circuit 2.
.1.3.6.1.4.1.476.1.42.3.2.1.132,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAirFilterClogged,,,,,,The system has detected a air filter clogged condition.
.1.3.6.1.4.1.476.1.42.3.2.1.133,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHumidifierFailure,,,,,,The system has detected a humidifier failure condition.
.1.3.6.1.4.1.476.1.42.3.2.1.134,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRunHoursExceeded,,,,,,The system has detected a pre-determined run hours threshold has been exceeded.
.1.3.6.1.4.1.476.1.42.3.2.1.134.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitRunHrsExceeded,,,,,,The system has detected the system run hours has exceeded the pre-determined threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.134.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionComp1RunHrsExceeded,,,,,,The system has detected the compressor 1 run hours has exceeded the pre-determined threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.134.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionComp2RunHrsExceeded,,,,,,The system has detected the compressor 2 run hours has exceeded the pre-determined threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.134.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFreeCoolRunHrsExceeded,,,,,,The system has detected the free cooling run hours has exceeded the pre-determined threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.134.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionElectricalHeater1RunHrsExceeded,,,,,,The system has detected the electrical heater's run hours have exceeded the pre-determined threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.134.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionElectricalHeater2RunHrsExceeded,,,,,,The system has detected the electrical heater's run hours have exceeded the pre-determined limit.
.1.3.6.1.4.1.476.1.42.3.2.1.134.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionElectricalHeater3RunHrsExceeded,,,,,,The system has detected the electrical heater's run hours have exceeded the pre-determined limit.
.1.3.6.1.4.1.476.1.42.3.2.1.134.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHotWaterRunHrsExceeded,,,,,,The system has detected the hot water run hours have exceeded the pre-determined threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.134.9,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHotGasRunHrsExceeded,,,,,,The system has detected the hot gas run hours have exceeded the pre-determined threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.134.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHumidifierRunHrsExceeded,,,,,,The system has detected the humidifier run hours have exceeded the pre-determined threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.134.11,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDehumidiferRunHrsExceeded,,,,,,The system has detected the dehumidifier run hours have exceeded the pre-determined threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.134.12,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFanRunHrsExceeded,,,,,,The system has detected the unit blower fan run hours have exceeded the pre-determined threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.135,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarning,,,,,,The system has detected a loss of communications with another module.
.1.3.6.1.4.1.476.1.42.3.2.1.135.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit1,,,,,,The system has detected a loss of communications with unit 1.
.1.3.6.1.4.1.476.1.42.3.2.1.135.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit2,,,,,,The system has detected a loss of communications with unit 2.
.1.3.6.1.4.1.476.1.42.3.2.1.135.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit3,,,,,,The system has detected a loss of communications with unit 3.
.1.3.6.1.4.1.476.1.42.3.2.1.135.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit4,,,,,,The system has detected a loss of communications with unit 4.
.1.3.6.1.4.1.476.1.42.3.2.1.135.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit5,,,,,,The system has detected a loss of communications with unit 5.
.1.3.6.1.4.1.476.1.42.3.2.1.135.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit6,,,,,,The system has detected a loss of communications with unit 6.
.1.3.6.1.4.1.476.1.42.3.2.1.135.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit7,,,,,,The system has detected a loss of communications with unit 7.
.1.3.6.1.4.1.476.1.42.3.2.1.135.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit8,,,,,,The system has detected a loss of communications with unit 8.
.1.3.6.1.4.1.476.1.42.3.2.1.135.9,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit9,,,,,,The system has detected a loss of communications with unit 9.
.1.3.6.1.4.1.476.1.42.3.2.1.135.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit10,,,,,,The system has detected a loss of communications with unit 10.
.1.3.6.1.4.1.476.1.42.3.2.1.135.11,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit11,,,,,,The system has detected a loss of communications with unit 11.
.1.3.6.1.4.1.476.1.42.3.2.1.135.12,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit12,,,,,,The system has detected a loss of communications with unit 12.
.1.3.6.1.4.1.476.1.42.3.2.1.135.13,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit13,,,,,,The system has detected a loss of communications with unit 13.
.1.3.6.1.4.1.476.1.42.3.2.1.135.14,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit14,,,,,,The system has detected a loss of communications with unit 14.
.1.3.6.1.4.1.476.1.42.3.2.1.135.15,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit15,,,,,,The system has detected a loss of communications with unit 15.
.1.3.6.1.4.1.476.1.42.3.2.1.135.16,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCommWarningUnit16,,,,,,The system has detected a loss of communications with unit 16.
.1.3.6.1.4.1.476.1.42.3.2.1.136,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitOn,,,,,,The unit is on.
.1.3.6.1.4.1.476.1.42.3.2.1.137,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitOff,,,,,,The unit is off.
.1.3.6.1.4.1.476.1.42.3.2.1.138,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSleepModeOff,,,,,,The system sleep mode operation has been turned off.
.1.3.6.1.4.1.476.1.42.3.2.1.139,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPowerOn,,,,,,The system power is on.
.1.3.6.1.4.1.476.1.42.3.2.1.140,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSystemOnStanby,,,,,,The system is on standby.
.1.3.6.1.4.1.476.1.42.3.2.1.141,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPowerOff,,,,,,The system power is off.
.1.3.6.1.4.1.476.1.42.3.2.1.142,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureGroup,,,,,,The system has detected a high temperature condition. This group contains various high temperature conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.142.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureSensor1,,,,,,The temperature has exceeded the high temperature threshold for sensor 1.
.1.3.6.1.4.1.476.1.42.3.2.1.142.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureDigitalScroll1,,,,,,The system has detected a high temperature event on Digital Scroll Compressor 1. The temperature has exceeded a specified temperature threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.142.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureDigitalScroll2,,,,,,The system has detected a high temperature event on Digital Scroll Compressor 2. The temperature has exceeded a specified temperature threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.142.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureUser1,,,,,,The temperature has exceeded the high temperature threshold for user configured temperature sensor 1.
.1.3.6.1.4.1.476.1.42.3.2.1.142.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureInternal,,,,,,The system has detected a high internal temperature condition. The temperature has exceeded a specified temperature threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.142.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureExternalAirSensorA,,,,,,The temperature has exceeded the high temperature threshold for external air sensor A.
.1.3.6.1.4.1.476.1.42.3.2.1.142.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureExternalAirSensorB,,,,,,The temperature has exceeded the high temperature threshold for external air sensor B.
.1.3.6.1.4.1.476.1.42.3.2.1.142.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureRefrigerantSupply,,,,,,The temperature has exceeded the high temperature threshold for the refrigerant supply.
.1.3.6.1.4.1.476.1.42.3.2.1.142.9,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureFluidSupply,,,,,,The temperature has exceeded the high temperature threshold for the fluid supply.
.1.3.6.1.4.1.476.1.42.3.2.1.142.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureSupplyAir,,,,,,The temperature has exceeded the high temperature threshold for the supply air.
.1.3.6.1.4.1.476.1.42.3.2.1.142.11,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighTemperatureReturnAir,,,,,,The temperature has exceeded the high temperature threshold for the return air.
.1.3.6.1.4.1.476.1.42.3.2.1.143,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowTemperatureGroup,,,,,,The system has detected a low temperature condition. This group contains various low temperature conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.143.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowTemperatureSensor1,,,,,,The temperature is below the low temperature threshold for sensor 1.
.1.3.6.1.4.1.476.1.42.3.2.1.143.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowTemperatureInternal,,,,,,The system has detected a low internal temperature condition. The temperature is below a specified temperature threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.143.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowTemperatureExternalAirSensorA,,,,,,The temperature is below the low temperature threshold for external air sensor A.
.1.3.6.1.4.1.476.1.42.3.2.1.143.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowTemperatureExternalAirSensorB,,,,,,The temperature is below the low temperature threshold for external air sensor B.
.1.3.6.1.4.1.476.1.42.3.2.1.143.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowTemperatureRefrigerantSupply,,,,,,The temperature is below the low temperature threshold for the refrigerant supply.
.1.3.6.1.4.1.476.1.42.3.2.1.143.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowTemperatureFluidSupply,,,,,,The temperature is below the low temperature threshold for the fluid supply.
.1.3.6.1.4.1.476.1.42.3.2.1.143.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowTemperatureSupplyAir,,,,,,The temperature is below the low temperature threshold for the supply air.
.1.3.6.1.4.1.476.1.42.3.2.1.144,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighHumidityGroup,,,,,,The system has detected a high humidity condition. This group contains various high humidity conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.144.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighHumiditySensor1,,,,,,The humidity has exceeded the high humidity threshold for sensor 1.
.1.3.6.1.4.1.476.1.42.3.2.1.144.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighHumidityReturnAir,,,,,,The humidity has exceeded the high humidity threshold for the return air.
.1.3.6.1.4.1.476.1.42.3.2.1.145,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowHumidityGroup,,,,,,The system has detected a low humidity condition. This group contains various high humidity conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.145.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowHumiditySensor1,,,,,,The humidity is below the low humidity threshold for sensor 1.
.1.3.6.1.4.1.476.1.42.3.2.1.145.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowHumidityReturnAir,,,,,,The humidity is below the low humidity threshold for the return air.
.1.3.6.1.4.1.476.1.42.3.2.1.146,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPeerNetworkNoMaster,,,,,,The system is unable to communicate with the master on the peer to peer network.
.1.3.6.1.4.1.476.1.42.3.2.1.147,LIEBERT-GP-CONDITIONS-MIB::lgpConditionNoOnOffPermissions,,,,,,The system lacks the permissions to execute the on/off operation.
.1.3.6.1.4.1.476.1.42.3.2.1.148,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPeerNetworkFailure,,,,,,The system has detected a communication failure on the peer to peer network.
.1.3.6.1.4.1.476.1.42.3.2.1.149,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitDisabled,,,,,,The unit is disabled.
.1.3.6.1.4.1.476.1.42.3.2.1.150,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitShutdown,,,,,,The system has shutdown.
.1.3.6.1.4.1.476.1.42.3.2.1.151,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPeerNetworkDiscovered,,,,,,The system has established communications on the peer to peer network.
.1.3.6.1.4.1.476.1.42.3.2.1.152,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLossOfWaterFlow,,,,,,The system has detected a loss of water flow condition.
.1.3.6.1.4.1.476.1.42.3.2.1.153,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCondensatePumpHighWater,,,,,,The system has detected high water in the condensate pump.
.1.3.6.1.4.1.476.1.42.3.2.1.154,LIEBERT-GP-CONDITIONS-MIB::lgpConditionGeneralAlarm,,,,,,The system has detected a general alarm condition.
.1.3.6.1.4.1.476.1.42.3.2.1.155,LIEBERT-GP-CONDITIONS-MIB::lgpConditionProductSpecific,,,,,,The system has detected a product specific condition. This condition is not currently available via the agent card.
.1.3.6.1.4.1.476.1.42.3.2.1.156,LIEBERT-GP-CONDITIONS-MIB::lgpConditionReheatLockout,,,,,,The system has locked out the electrical reheat operation for a specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.157,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHumidifierLockout,,,,,,The system has locked out the humidifier operation for a specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.158,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCompressorsLockout,,,,,,The system has locked out compressor operation for a specified amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.159,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCallService,,,,,,The system has detected a condition that requires a service representative be contacted.
.1.3.6.1.4.1.476.1.42.3.2.1.160,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowMemoryGroup,,,,,,This group contains various low memory conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.160.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLowMemory1,,,,,,The system has detected a low memory condition. The control board is low in memory resources.
.1.3.6.1.4.1.476.1.42.3.2.1.161,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMemoryFailureGroup,,,,,,This group contains various memory device failure conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.161.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMemory1Failure,,,,,,The system has detected a memory 1 module failure.
.1.3.6.1.4.1.476.1.42.3.2.1.161.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMemory2Failure,,,,,,The system has detected a memory 2 module failure.
.1.3.6.1.4.1.476.1.42.3.2.1.162,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCodeErrorGroup,,,,,,This group contains various memory device failure conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.162.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCodeNotConfigured,,,,,,The system has detected the unit code is not configured. The unit code must be configured before system start-up.
.1.3.6.1.4.1.476.1.42.3.2.1.162.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode01OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode02OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode03OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode04OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode05OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode06OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode07OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.9,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode08OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode09OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.11,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode10OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.12,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode11OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.13,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode12OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.14,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode13OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.15,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode14OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.16,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode15OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.17,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode16OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.18,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode17OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.162.19,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnitCode18OutOfRange,,,,,,The system has detected a unit code error. This digit of the unit code value is out of range.
.1.3.6.1.4.1.476.1.42.3.2.1.163,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHighExternalDewPoint,,,,,,The system has detected a high external dew point condition. The room dew point has exceeded the specified threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.164,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHcbDisconnected,,,,,,The system has detected the humidifier control board is disconnected or not installed.
.1.3.6.1.4.1.476.1.42.3.2.1.165,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBmsResetTimerExpired,,,,,,The BMS fan speed control reset counter has timed out.
.1.3.6.1.4.1.476.1.42.3.2.1.166,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAgentFirmwareCorrupt,,,,,,The firmware update to the agent card has failed and the firmware is now corrupt.
.1.3.6.1.4.1.476.1.42.3.2.1.175,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSystemAccessGroup,,,,,,This group contains various system access conditions. An examples is an open access panel.
.1.3.6.1.4.1.476.1.42.3.2.1.175.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFrontAccessOpen,,,,,,The system has detected the front access panel/door is open.
.1.3.6.1.4.1.476.1.42.3.2.1.175.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRearAccessOpen,,,,,,The system has detected the rear access panel/door is open.
.1.3.6.1.4.1.476.1.42.3.2.1.176,LIEBERT-GP-CONDITIONS-MIB::lgpConditionsDamperFailure,,,,,,This group contains various damper failure conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.176.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEmergencyDamperFailure,,,,,,The system has detected an emergency damper failure. The damper is in the wrong position.
.1.3.6.1.4.1.476.1.42.3.2.1.177,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRemoteShutdown,,,,,,A remote shutdown occurred.
.1.3.6.1.4.1.476.1.42.3.2.1.178,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFireAlarm,,,,,,Fire Alarm.
.1.3.6.1.4.1.476.1.42.3.2.1.179,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHeatersOverheated,,,,,,Heaters Overheated.
.1.3.6.1.4.1.476.1.42.3.2.1.180,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCondenserFailureGroup,,,,,,This group contains condenser failure conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.180.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCondenser1Failure,,,,,,Condenser 1 Failure.
.1.3.6.1.4.1.476.1.42.3.2.1.180.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCondenser2Failure,,,,,,Condenser 2 Failure.
.1.3.6.1.4.1.476.1.42.3.2.1.180.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCondenserTVSSFailure,,,,,,The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.181,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHumidifierCyclinderWorn,,,,,,The system has detected the humidifier cylinder is worn.
.1.3.6.1.4.1.476.1.42.3.2.1.182,LIEBERT-GP-CONDITIONS-MIB::lgpConditionUnderCurrent,,,,,,The system has detected a low current condition. The current of one or more sources in the system has fallen below a threshold for a specified amount of time. The threshold and time that triggered this condition is system dependent.
.1.3.6.1.4.1.476.1.42.3.2.1.182.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHumidifierUnderCurrent,,,,,,The system has detected a low current condition on the humidifier. The current of the humidifier has fallen below a pre-determined threshold for a defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.182.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputUnderCurrent,,,,,,There is a low current condition on the input power source. The current of the input power source has fallen below a pre-determined threshold for a defined amount of time.
.1.3.6.1.4.1.476.1.42.3.2.1.183,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHeatRejectorGroup,,,,,,This group contains failure conditions for the heat rejection unit.
.1.3.6.1.4.1.476.1.42.3.2.1.183.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHeatRejectorFanFailure,,,,,,The heat rejecter fan has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.183.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHeatRejectorVoltageSuppressionFailure,,,,,,The heat rejecter voltage suppression has failed and is no longer able to protect the unit from power fluctuations.
.1.3.6.1.4.1.476.1.42.3.2.1.184,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFreeCoolLockout,,,,,,The free cooling capability has been disabled.
.1.3.6.1.4.1.476.1.42.3.2.1.185,LIEBERT-GP-CONDITIONS-MIB::lgpConditionWaterLeakSensorFailure,,,,,,The sensor used to detect water leaks is not connected or has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.186,LIEBERT-GP-CONDITIONS-MIB::lgpConditionNoLoadDetectedWarning,,,,,,There is no load detected on the output. This can be an indication that the output is being powered by an external bypass source and has inadvertently been left on external bypass. This warning is triggered after a delay. The delay is specified by the object 'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output current falls below a certain threshold specified by the object 'lgpPwrNoLoadWarningLimit'
.1.3.6.1.4.1.476.1.42.3.2.1.187,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFirmwareGroup,,,,,,Grouping level for firmware related conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.187.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionFirmwareUpdateRequired,,,,,,The firmware on the system or one or more components of the system must be updated. This typically indicates that one or more components of the system contain corrupted firmware or the firmware on one or more components are incompatible with one another. When this condition is active the system may not be able to function to its full capacity or may not be able to function at all.
.1.3.6.1.4.1.476.1.42.3.2.1.188,LIEBERT-GP-CONDITIONS-MIB::lgpConditionTestGroup,,,,,,Objects in this group of conditions are related to testing or test events. This object is never active.
.1.3.6.1.4.1.476.1.42.3.2.1.188.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionTest01,,,,,,This is a 'test' condition. It is a generic test event that can be utilized to evaluate system handling of events. Some products will support the activation of this event upon user request so that user management stations can execute end-to-end event handling tests.
.1.3.6.1.4.1.476.1.42.3.2.1.190,LIEBERT-GP-CONDITIONS-MIB::lgpConditionReceptacleBranchGroup,,,,,,Grouping level for receptacle branch conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.190.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRcpBranchFailure,,,,,,The receptacle branch module or control system has failed. Service is required.
.1.3.6.1.4.1.476.1.42.3.2.1.190.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRcpBranchBreakerOpen,,,,,,The receptacle branch breaker is open.
.1.3.6.1.4.1.476.1.42.3.2.1.192,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputUnqualified,,,,,,The input is not qualified to provide power to the system. This may be due to system input over-voltage, system input under-voltage, system input frequency out of range, or other similar issues.
.1.3.6.1.4.1.476.1.42.3.2.1.193,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassUnavailable,,,,,,This summary event is asserted when the bypass is not available. Possible causes include: Bypass Sync Error, Bypass Line Fail, Bypass Overvoltage, Bypass Undervoltage, Bypass Phase Rotation Error, or other similar causes.
.1.3.6.1.4.1.476.1.42.3.2.1.194,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAutoTransferFailed,,,,,,The system is failing to automatically transfer the load to the alternate source.
.1.3.6.1.4.1.476.1.42.3.2.1.195,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSBSUnavailable,,,,,,A Static Bypass Switch (SBS) Failure has been detected. Possible causes include: SBS Phase Open, SBS SCR (Silicon Controlled Rectifier) Shorted, SBS Overload Exceeded, Bypass Power Supply Fail, Static Bypass Switch Fuse Failure, or other similar causes.
.1.3.6.1.4.1.476.1.42.3.2.1.196,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSBSOverload,,,,,,On at least one phase of the static bypass switch (SBS), the power dissipation limit has been exceeded.
.1.3.6.1.4.1.476.1.42.3.2.1.197,LIEBERT-GP-CONDITIONS-MIB::lgpConditionExcessPulseParallel,,,,,,The system has performed too many pulse parallel operations within the specified time interval. A pulse parallel operation is a momentary operation of the static bypass switch (SBS) in parallel with the inverter.
.1.3.6.1.4.1.476.1.42.3.2.1.198,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRemoteBypassSwitchOffExt,,,,,,The static bypass switch is off due to the state of an external signal.
.1.3.6.1.4.1.476.1.42.3.2.1.199,LIEBERT-GP-CONDITIONS-MIB::lgpConditionManTransferInhibited,,,,,,Manual transfer from inverter to bypass is inhibited. Bypass is not qualified.
.1.3.6.1.4.1.476.1.42.3.2.1.200,LIEBERT-GP-CONDITIONS-MIB::lgpConditionManReTransferInhibited,,,,,,Manual retransfer from bypass to inverter is inhibited.
.1.3.6.1.4.1.476.1.42.3.2.1.201,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryChargeError,,,,,,The battery is not charging properly. Some reasons for this condition include, but are not limited to: battery charger failure, battery failure, etc.
.1.3.6.1.4.1.476.1.42.3.2.1.202,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryAutoTestInhibited,,,,,,Automatic (scheduled) battery tests are inhibited.
.1.3.6.1.4.1.476.1.42.3.2.1.203,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryChargeReducedExt,,,,,,A reduced battery charging algorithm is being used due to an external signal.
.1.3.6.1.4.1.476.1.42.3.2.1.204,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryCapacityLow,,,,,,The battery capacity is low. Some reasons for this condition include, but are not limited to: a battery is offline, the battery age has reduced its capabilities, etc.
.1.3.6.1.4.1.476.1.42.3.2.1.205,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryTempImbalance,,,,,,The temperature difference between two batteries in the system exceeds the predefined threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.206,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryEqualize,,,,,,The rectifier output voltage has been increased to equalize the battery voltage level.
.1.3.6.1.4.1.476.1.42.3.2.1.207,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryChargeInhibitedExt,,,,,,Battery charging is inhibited due to an external inhibit signal.
.1.3.6.1.4.1.476.1.42.3.2.1.208,LIEBERT-GP-CONDITIONS-MIB::lgpConditionServiceExtBatteryMonitorGroup,,,,,,This group contains battery monitor service conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.208.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionServiceExtBatteryMonitor1,,,,,,External battery monitor 1 indicates battery maintenance is required.
.1.3.6.1.4.1.476.1.42.3.2.1.208.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionServiceExtBatteryMonitor2,,,,,,External battery monitor 2 indicates battery maintenance is required.
.1.3.6.1.4.1.476.1.42.3.2.1.209,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryGroundFault,,,,,,Battery system ground fault amperage exceeds the threshold.
.1.3.6.1.4.1.476.1.42.3.2.1.210,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBatteryLowShutdown,,,,,,With the battery breaker closed, the battery voltage has dropped below the calculated End-Of-Discharge (EOD) limit.
.1.3.6.1.4.1.476.1.42.3.2.1.211,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEmergencyPowerOffLocal,,,,,,The system has detected an Emergency Power Off (EPO) condition. The local EPO switch has cut off the power source to the system.
.1.3.6.1.4.1.476.1.42.3.2.1.212,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputLowPFLagging,,,,,,The system has detected a lagging output power factor below the threshold, resulting in reduced load capacity.
.1.3.6.1.4.1.476.1.42.3.2.1.213,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputLowPFLeading,,,,,,The system has detected a leading output power factor below the threshold, resulting in reduced load capacity.
.1.3.6.1.4.1.476.1.42.3.2.1.214,LIEBERT-GP-CONDITIONS-MIB::lgpConditionOutputToLoadFault,,,,,,The system has detected an output to load fault. This could be caused by over or under voltage, or by over or under frequency.
.1.3.6.1.4.1.476.1.42.3.2.1.215,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInvRestartInhibitedExt,,,,,,Restart of the inverter is inhibited by an external signal.
.1.3.6.1.4.1.476.1.42.3.2.1.216,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterShutdownOverload,,,,,,The system has shutdown the inverter due to a sustained overload. This event does not indicate if the load has been dropped or transferred to bypass. At least one phase of the inverter power dissipation limit has been exceeded.
.1.3.6.1.4.1.476.1.42.3.2.1.217,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInverterOffExt,,,,,,The inverter is off due to the state of an external signal.
.1.3.6.1.4.1.476.1.42.3.2.1.218,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContactGroup,,,,,,The system has detected an active input contact.
.1.3.6.1.4.1.476.1.42.3.2.1.218.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact01,,,,,,The system has detected that input contact 1 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact02,,,,,,The system has detected that input contact 2 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact03,,,,,,The system has detected that input contact 3 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact04,,,,,,The system has detected that input contact 4 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact05,,,,,,The system has detected that input contact 5 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact06,,,,,,The system has detected that input contact 6 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact07,,,,,,The system has detected that input contact 7 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact08,,,,,,The system has detected that input contact 8 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.9,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact09,,,,,,The system has detected that input contact 9 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact10,,,,,,The system has detected that input contact 10 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.11,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact11,,,,,,The system has detected that input contact 11 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.12,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact12,,,,,,The system has detected that input contact 12 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.13,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact13,,,,,,The system has detected that input contact 13 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.14,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact14,,,,,,The system has detected that input contact 14 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.15,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact15,,,,,,The system has detected that input contact 15 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.218.16,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputContact16,,,,,,The system has detected that input contact 16 is active.
.1.3.6.1.4.1.476.1.42.3.2.1.219,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRectifierOperInhibited,,,,,,The operation of the rectifier is inhibited by an external signal.
.1.3.6.1.4.1.476.1.42.3.2.1.220,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBypassBackFeedBrkrOpen,,,,,,The bypass backfeed breaker is in the open position.
.1.3.6.1.4.1.476.1.42.3.2.1.221,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAutoRestartInProgress,,,,,,Auto restart is in progress. Becomes inactive when auto restart completes or fails.
.1.3.6.1.4.1.476.1.42.3.2.1.222,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAutoRestartInhibitedExt,,,,,,Auto restart is inhibited due to an external signal.
.1.3.6.1.4.1.476.1.42.3.2.1.223,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAutoRestartFailed,,,,,,Auto restart has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.224,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputOnGenerator,,,,,,A generator is supplying the power to the system.
.1.3.6.1.4.1.476.1.42.3.2.1.225,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputFilterCycleLock,,,,,,The input filter disconnect has opened too many times within a given period of time.
.1.3.6.1.4.1.476.1.42.3.2.1.226,LIEBERT-GP-CONDITIONS-MIB::lgpConditionServiceCodeActive,,,,,,The system is in an operational mode intended for testing. In normal operating conditions, the system should not be in this state.
.1.3.6.1.4.1.476.1.42.3.2.1.227,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLoadBusSyncActive,,,,,,Load Bus Sync Operation is active. This synchronizes the UPS output with the output of another UPS.
.1.3.6.1.4.1.476.1.42.3.2.1.228,LIEBERT-GP-CONDITIONS-MIB::lgpConditionLoadBusSyncInhibited,,,,,,The system has detected that conditions to perform Load Bus Sync Operation are not satisfied.
.1.3.6.1.4.1.476.1.42.3.2.1.229,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlsResetRequired,,,,,,A controls reset is required because one or more critical settings have changed.
.1.3.6.1.4.1.476.1.42.3.2.1.230,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEquipTempSensorFailed,,,,,,A temperature sensor is reporting a value outside the bounds of a properly operating sensor.
.1.3.6.1.4.1.476.1.42.3.2.1.231,LIEBERT-GP-CONDITIONS-MIB::lgpConditionInputCurrentImbalance,,,,,,The current on one input phase is much greater or lower than the average current of all the phases. This may indicate improper operation of the rectifier or input filter.
.1.3.6.1.4.1.476.1.42.3.2.1.232,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPumpGroup,,,,,,The system has detected an alarm with one of the pumps.
.1.3.6.1.4.1.476.1.42.3.2.1.232.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPumpFlowLoss,,,,,,The system has detected a loss of flow with one or more pumps.
.1.3.6.1.4.1.476.1.42.3.2.1.232.1.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPump1FlowLoss,,,,,,The system has detected a loss of flow with pump 1.
.1.3.6.1.4.1.476.1.42.3.2.1.232.1.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPump2FlowLoss,,,,,,The system has detected a loss of flow with pump 2.
.1.3.6.1.4.1.476.1.42.3.2.1.232.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPumpShortCycle,,,,,,The system has detected a short cycling of the pumps. One or more of the pumps has been turned on and off a number of times within a specified time period.
.1.3.6.1.4.1.476.1.42.3.2.1.232.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPumpInverterShortCycle,,,,,,The system has detected a short cycling of one or more pump inverters and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
.1.3.6.1.4.1.476.1.42.3.2.1.232.3.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPump1InverterShortCycle,,,,,,The system has detected a short cycling of the inverter for pump 1 and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
.1.3.6.1.4.1.476.1.42.3.2.1.232.3.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionPump2InverterShortCycle,,,,,,The system has detected a short cycling of the inverter for pump 2 and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
.1.3.6.1.4.1.476.1.42.3.2.1.233,LIEBERT-GP-CONDITIONS-MIB::lgpConditionValveGroup,,,,,,The system has detected an alarm with one of the valves.
.1.3.6.1.4.1.476.1.42.3.2.1.233.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionChilledWaterValvePosition,,,,,,The system has detected a problem with the chilled water valve position. The position of the chilled water control valve does not match an expected value.
.1.3.6.1.4.1.476.1.42.3.2.1.234,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCondensationDetected,,,,,,The system has detected condensation.
.1.3.6.1.4.1.476.1.42.3.2.1.235,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMaintenanceGroup,,,,,,The system has detected a maintenance condition. This group contains various maintenance conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.235.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMaintenanceDue,,,,,,System is due for maintenance.
.1.3.6.1.4.1.476.1.42.3.2.1.235.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionMaintenanceComplete,,,,,,The system maintenance has been completed.
.1.3.6.1.4.1.476.1.42.3.2.1.236,LIEBERT-GP-CONDITIONS-MIB::lgpConditionExternalEventSignalGroup,,,,,,This group contains various conditions signalled by external inputs. Each event is deactivated when the signal is inactive.
.1.3.6.1.4.1.476.1.42.3.2.1.236.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionExternalFireDetect,,,,,,Fire detected, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.1.236.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionExternalFlowLoss,,,,,,Loss of flow is detected, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.1.236.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionExternalReheatLockout,,,,,,The reheater is shut down and disabled by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.1.236.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionExternalOverTemp,,,,,,A temperature has exceeded its threshold, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.1.236.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionExternalCompLockout,,,,,,The compressor is shut down and disabled by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.1.236.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionExternalHumidifierLockout,,,,,,The humidifier is shut down and disabled by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.1.237,LIEBERT-GP-CONDITIONS-MIB::lgpConditionComponentShutdownGroup,,,,,,This group contains conditions signaling shutdown of various system components.
.1.3.6.1.4.1.476.1.42.3.2.1.237.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionComponentShutdownPartial,,,,,,An event has occurred requiring some system components to be shutdown and disabled.
.1.3.6.1.4.1.476.1.42.3.2.1.237.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionComponentShutdownHighPower,,,,,,Supply to high power components has been shutdown.
.1.3.6.1.4.1.476.1.42.3.2.1.238,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCondenserProblemGroup,,,,,,This group contains condenser conditions.
.1.3.6.1.4.1.476.1.42.3.2.1.238.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCondenser1Problem,,,,,,Condenser 1 is not operating within its normal parameters.
.1.3.6.1.4.1.476.1.42.3.2.1.239,LIEBERT-GP-CONDITIONS-MIB::lgpConditionHumidityOutOfPropBand,,,,,,The system has detected a humidity reading that remained outside of the proportional control band for an extended period of time.
.1.3.6.1.4.1.476.1.42.3.2.1.240,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEnvRemoteSensorGroup,,,,,,This group contains remote sensors.
.1.3.6.1.4.1.476.1.42.3.2.1.240.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEnvRemoteSensor1Issue,,,,,,Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
.1.3.6.1.4.1.476.1.42.3.2.1.240.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEnvRemoteSensor2Issue,,,,,,Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
.1.3.6.1.4.1.476.1.42.3.2.1.240.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEnvRemoteSensor3Issue,,,,,,Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
.1.3.6.1.4.1.476.1.42.3.2.1.240.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEnvRemoteSensor4Issue,,,,,,Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
.1.3.6.1.4.1.476.1.42.3.2.1.240.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEnvRemoteSensor5Issue,,,,,,Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
.1.3.6.1.4.1.476.1.42.3.2.1.240.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEnvRemoteSensor6Issue,,,,,,Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
.1.3.6.1.4.1.476.1.42.3.2.1.240.7,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEnvRemoteSensor7Issue,,,,,,Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
.1.3.6.1.4.1.476.1.42.3.2.1.240.8,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEnvRemoteSensor8Issue,,,,,,Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
.1.3.6.1.4.1.476.1.42.3.2.1.240.9,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEnvRemoteSensor9Issue,,,,,,Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
.1.3.6.1.4.1.476.1.42.3.2.1.240.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEnvRemoteSensor10Issue,,,,,,Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
.1.3.6.1.4.1.476.1.42.3.2.1.241,LIEBERT-GP-CONDITIONS-MIB::lgpConditionNeutralSnubberBoardCommFailure,,,,,,The Neutral Snubber board has stopped communicating.
.1.3.6.1.4.1.476.1.42.3.2.1.242,LIEBERT-GP-CONDITIONS-MIB::lgpConditionRedundantChargerFailure,,,,,,The redundant charger has failed.
.1.3.6.1.4.1.476.1.42.3.2.1.243,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBoardInputContactorPowerFailure,,,,,,Board input contactor power failure.
.1.3.6.1.4.1.476.1.42.3.2.1.243.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBoard1InputContactorPowerFailure,,,,,,Board1 input contactor power failure.
.1.3.6.1.4.1.476.1.42.3.2.1.243.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionBoard2InputContactorPowerFailure,,,,,,Board2 input contactor power failure.
.1.3.6.1.4.1.476.1.42.3.2.1.5423,LIEBERT-GP-CONDITIONS-MIB::lgpConditionTooManySensors,,,,,,The number of sensors installed on the device has exceeded the
.1.3.6.1.4.1.476.1.42.3.2.1.5471,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDoorSwitchOpen,,,,,,An open door has been detected.
.1.3.6.1.4.1.476.1.42.3.2.1.5479,LIEBERT-GP-CONDITIONS-MIB::lgpConditionContactClosureOpen,,,,,,An open circuit has been detected.
.1.3.6.1.4.1.476.1.42.3.2.1.5480,LIEBERT-GP-CONDITIONS-MIB::lgpConditionContactClosureClosed,,,,,,A closed circuit has been detected.
.1.3.6.1.4.1.476.1.42.3.2.1.6119,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSensorsNotDisplayed,,,,,,The number of sensors that can be displayed (monitored) on the device has exceeded the pre-determined limit. Note this condition differs from the lgpConditionTooManySensors in that the system may currently have less than the maximum of installed sensors present but one or more of those sensors can not be displayed because the display order table (lgpPduAuxMeasOrderTable) contains entries for sensors that are not currently installed. This condition effectively prevents one or more installed sensors from being presented in the lgpPduAuxMeasTable. It is possible for both this condition and the lgpConditionTooManySensors condition to be active at the same time.
.1.3.6.1.4.1.476.1.42.3.2.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionsPresent,Gauge32,read-only,,current,,The present number of conditions (rows) in the lgpConditionsTable.
.1.3.6.1.4.1.476.1.42.3.2.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionsTable,,not-accessible,,current,,A list of condition table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions in effect. The number of rows in the table is given by (lgpConditionsPresent). The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row subject to the following rules: Rows are removed from the table based on the following rules: 1. If a condition does not require acknowledgement (see 'lgpConditionAckReq') the condition is removed as soon as the issue clears (see 'lgpConditionCurrentState'). 2. If a condition requires acknowledgement (see 'lgpConditionAckReq') the condition is removed as soon as the issue clears (see 'lgpConditionCurrentState') AND the condition is acknowledged (see 'lgpConditionAcknowledged'). 3. If the columns 'lgpConditionCurrentState' and 'lgpConditionAcknowledged' are not present for the condition then the condition will be removed as soon as the issue causing the condition clears. The agent creates the first row with lgpConditionId equal to 1, and increments the value of 'lgpConditionId' each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of lgpConditionId would otherwise be exceeded. The number of rows in the table at any given time is reflected by the value of 'lgpConditionsPresent'. 
.1.3.6.1.4.1.476.1.42.3.2.3.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionEntry,,not-accessible,lgpConditionId,current,,This entry defines the contents of the rows for the table 'lgpConditionsTable'. A row in this table cannot be created or deleted by SNMP operations on columns of the table.
.1.3.6.1.4.1.476.1.42.3.2.3.1.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionId,Unsigned32,read-only,,current,,A unique identifier for a condition. This value must remain constant between agent initializations. This OID is used as an index to identify a row in the table 'lgpConditionsTable'.
.1.3.6.1.4.1.476.1.42.3.2.3.1.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDescr,OBJECT,read-only,,current,,A reference to a condition description object. The object referenced should not be accessible, but rather be used to provide a unique description.
.1.3.6.1.4.1.476.1.42.3.2.3.1.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionTime,TimeTicks,read-only,,current,,The value of sysUpTime when the condition occurred (became active).
.1.3.6.1.4.1.476.1.42.3.2.3.1.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionTableRef,OBJECT,read-only,,current,,This object will be included as a varbind in some rows of the table. It is a reference to a table object in the MIB. The value of this object will be the OID of a table that the object that the condition applies to is defined. The table row corresponding to this object will also contain a varbind 'lgpConditionTableRowRef' that will specify which instance (row) in the referenced table the object is defined in. Example: TABLE ROW: lgpConditionId 5 lgpConditionDescr lgpConditionRcpBranchBreakerOpen lgpConditionTime 393884848 lgpConditionTableRef lgpPduRbTable lgpConditionTableRowRef lgpPduRbEntryId.1.4 lgpConditionType alarm lgpConditionCurrentState active lgpConditionSeverity major lgpConditionAcknowledged acknowledged lgpConditionAckReq required In the above example the breaker opened for a Receptacle branch. The specific receptacle branch is specified by the additional varbind (lgpEventParmTableRowRef). In this case the notification is for the 4th receptacle branch on the 1st PDU in the cluster. 
.1.3.6.1.4.1.476.1.42.3.2.3.1.6,LIEBERT-GP-CONDITIONS-MIB::lgpConditionTableRowRef,OBJECT,read-only,,current,,This is a reference to the (cell) in the table specified by the companion varbind (lgpConditionTableRef) in this condition. The row in the table where this cell exists represents the object that this condition applies to. Example: TABLE ROW: lgpConditionId 5 lgpConditionDescr lgpConditionRcpBranchBreakerOpen lgpConditionTime 393884848 lgpConditionTableRef lgpPduRbTable lgpConditionTableRowRef lgpPduRbEntryId.1.4 lgpConditionType lgpConditionCurrentState active lgpConditionSeverity major lgpConditionAcknowledged acknowledged lgpConditionAckReq required The table containing the definition of the receptacle branch (lgpPduRbTable) is given by the varbind (lgpConditionTableRef) The specific receptacle branch (instance) is specified by the varbind (lgpConditionTableRowRef). In this case the condition is for the 4th receptacle branch on the 1st PDU in the PDU cluster. If one wanted to retrieve the serial number for this receptacle branch the OID would be: lgpPduRbEntrySerialNum.1.4. 
.1.3.6.1.4.1.476.1.42.3.2.3.1.10,LIEBERT-GP-CONDITIONS-MIB::lgpConditionType,INTEGER,read-only,,current,not-specified(0):message(2):warning(4):alarm(6):fault(8),The type of condition in this row in the table.
.1.3.6.1.4.1.476.1.42.3.2.3.1.12,LIEBERT-GP-CONDITIONS-MIB::lgpConditionCurrentState,INTEGER,read-only,,current,active(1):inactive(2),Indication of the current state of the event. If the state is 'active' then the condition currently exists. If the state is 'inactive' then the condition no longer exists (i.e. the situation causing the condition has cleared or been resolved). The behavior of some devices is to remove the condition from this table when the condition clears. The behavior of other devices is to leave the condition entry in the table until the condition is acknowledged ( see lgpConditionAcknowledged and lgpConditionAckReq).
.1.3.6.1.4.1.476.1.42.3.2.3.1.14,LIEBERT-GP-CONDITIONS-MIB::lgpConditionSeverity,INTEGER,read-only,,current,not-applicable(0):minor(3):major(6):critical(9),This represents the relative severity of the condition.
.1.3.6.1.4.1.476.1.42.3.2.3.1.18,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAcknowledged,INTEGER,read-write,,current,notAcknowledged(1):acknowledged(2),This indicates if the condition has been acknowledged. If the value is 'notAcknowledged' then the condition has not been acknowledged. If the value is 'acknowledged' then the condition has been acknowledged. Writing a value of 'acknowledged' to this object acknowledges the condition and the value will be changed to 'acknowledged'. If the current state of the condition is 'active' (see lgpConditionCurrentState) the condition will, for all devices remain in the table regardless of the state of the 'lgpConditionAcknowledged' object. If the 'lgpConditionAckReq' is 'notRequired' or this column does not exist for the row then this object has no affect on the duration the condition stays in the lgpConditionsTable. If the 'lgpConditionAckReq' is 'required' then the condition will remain in the condition table until both the 'lgpConditionCurrentState' is 'inactive' AND 'lgpConditionAcknowledged' is 'acknowledged'. 
.1.3.6.1.4.1.476.1.42.3.2.3.1.19,LIEBERT-GP-CONDITIONS-MIB::lgpConditionAckReq,INTEGER,read-only,,current,required(1):notRequired(2),This indicates if the corresponding condition does or does not require user acknowledgement. Conditions that require user acknowledgement will have a value of 'required'. Those conditions that do not require user acknowledgement will have a value of 'notRequired' or in some devices the column may not be present at all. If a condition requires acknowledgement it will remain in the table until both the 'lgpConditionCurrentState' and 'lgpConditionAcknowledged' are 'inactive' and 'acknowledged' respectively (see lgpConditionAcknowledged). If a condition does not require acknowledgement it will be removed from the table as soon as its 'lgpConditionCurrentState' is 'inactive'. 
.1.3.6.1.4.1.476.1.42.3.2.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControl,,,,,,
.1.3.6.1.4.1.476.1.42.3.2.4.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlEventReset,INTEGER,read-write,,current,noAction(1):resetAll(2),Event Reset Command. This command will reset all of the device's events. On some units, when an event is activated, a 'set' field is also marked and maintained even when the event has become inactive. The 'set' field is only cleared when the user clears it and the event is no longer active. This item will clear the 'set' field for all events that are not active.
.1.3.6.1.4.1.476.1.42.3.2.4.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlEventAck,INTEGER,read-write,,current,noAction(1):ackAll(2),Event Acknowledge Command. This command will acknowledge all of the device's events.
.1.3.6.1.4.1.476.1.42.3.2.4.20,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlTable,,not-accessible,,current,,A list of condition control table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions that are controllable by the unit. This table does not necessarily contain all conditions supported by the unit. This table only contains conditions that are end-user modifiable.
.1.3.6.1.4.1.476.1.42.3.2.4.20.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlEntry,,not-accessible,lgpConditionControlIndex,current,,This entry defines the contents of the rows for the table 'lgpConditionControlTable'. A row in this table cannot be created or deleted by user initiated SNMP operations on columns of the table.
.1.3.6.1.4.1.476.1.42.3.2.4.20.1.1,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlIndex,Unsigned32,not-accessible,,current,,This is the index indicating the nth element of the table.
.1.3.6.1.4.1.476.1.42.3.2.4.20.1.2,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlDescr,OBJECT,read-only,,current,,A reference to an Object Identifier (OID) representing a unique condition. The referenced OID is used solely for identification purposes. The object identifier referenced here will be the same object identifier referenced in the lgpConditionsTable (column: lgpConditionDescr) when the condition is activated.
.1.3.6.1.4.1.476.1.42.3.2.4.20.1.3,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlEnableStatus,INTEGER,read-write,,current,not-specified(0):enabled(1):disabled(2),The value in this column determines if the device is currently capable of generating this event. If the value is 'enabled' then the event will be generated if the condition indicated by lgpConditionControlDescr becomes active. If the value is 'disabled' the device will never generate the event. This value is stored on the managed device. Some devices do not allow write access to some entries in this column. The 'lgpConditionControlEnableCapability' column indicates whether this entry can be written.
.1.3.6.1.4.1.476.1.42.3.2.4.20.1.4,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlType,INTEGER,read-write,,current,not-specified(0):message(2):warning(4):alarm(6):fault(8),The 'type' assigned or configured for this condition. The value assigned to the condition here is displayed in the lgpConditionsTable (column: lgpConditionType). For some units this is user configurable. This value is stored on the managed device.
.1.3.6.1.4.1.476.1.42.3.2.4.20.1.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionControlEnableCapability,INTEGER,read-only,,current,not-specified(0):readonly(1):readwrite(2),Some devices do not allow write access to some entries in the 'lgpConditionControlEnableStatus' column. This column indicates whether the 'lgpConditionControlEnableStatus' entry for this row can be written.
.1.3.6.1.4.1.476.1.42.3.2.5,LIEBERT-GP-CONDITIONS-MIB::lgpConditionDescription,OCTET,read-only,,current,,The ASCII text description for the condition.
.1.3.6.1.4.1.476.1.42.3.2.6,LIEBERT-GP-CONDITIONS-MIB::lgpNetworkName,OCTET,read-only,,current,,The network name in a node.domain.com like format. This object is intended to be used as a varbind object by other notifications that have a context of a network address. As an example the lgpAgentDnsLookupFailure trap which describes a network name that is failing or has failed to be resolved from a Domain Name Service (DNS) lookup. Refer to RFC 952 for further information.
.1.3.6.1.4.1.476.1.42.3.2.7,LIEBERT-GP-CONDITIONS-MIB::lgpFlexConditions,,,,,,
.1.3.6.1.4.1.476.1.42.3.2.7.1,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpFlexConditionsWellKnown,,,,,,
.1.3.6.1.4.1.476.1.42.3.2.7.1.4122,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4122SystemInputPowerProblem,,,,,,The input is not qualified to provide power to the system.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4132,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4132BypassOverloadPhaseA,,,,,,An overload exists on output phase A while operating on the bypass.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4133,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4133BypassOverloadPhaseB,,,,,,An overload exists on output phase B while operating on the bypass.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4134,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4134BypassOverloadPhaseC,,,,,,An overload exists on output phase C while operating on the bypass.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4135,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4135BypassNotAvailable,,,,,,A problem associated with the bypass has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4137,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4137BypassAutoRetransferPrimed,,,,,,Automatic retransfer from bypass to inverter is possible.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4138,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4138BypassAutoRetransferFailed,,,,,,After performing a recoverable transfer to bypass, an attempt to auto retransfer from bypass to inverter failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4139,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4139BypassExcessAutoRetransfers,,,,,,The number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4140,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4140BypassRestartInhibitExternal,,,,,,Restart of the bypass is inhibited by the state of an external signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4141,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4141BypassBreakerClosed,,,,,,The bypass breaker is closed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4142,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4142BypassStaticSwitchOverload,,,,,,Bypass off due to static switch overload.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4143,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4143BypassStaticSwitchUnavailable,,,,,,The static bypass is unavailable to support the critical load.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4144,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4144BypassExcessivePulseParallel,,,,,,The system has performed too many pulse parallel operations within a specified time interval.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4145,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4145BypassAutoTransferFailed,,,,,,An automatic transfer to static bypass failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4146,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4146SystemInputPhsRotationError,,,,,,The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C).
.1.3.6.1.4.1.476.1.42.3.2.7.1.4147,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4147SystemInputCurrentLimit,,,,,,The RMS input current has reached the input current limit threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4162,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4162BatteryLow,,,,,,The calculated battery time remaining has reached the low battery threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4163,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4163OutputOffEndofDischarge,,,,,,Output turned off due to battery reaching end-of-discharge.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4164,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4164BatteryChargingError,,,,,,The battery is not charging properly.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4165,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4165BatteryChargingReducedExtrnl,,,,,,Using a reduced battery charging algorithm due to an external signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4166,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4166BatteryCapacityLow,,,,,,Battery capacity is low.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4167,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4167OutputOff,,,,,,Output is off.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4168,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4168BatteryDischarging,,,,,,The battery is discharging.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4169,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4169BatteryTemperatureImbalance,,,,,,Excessive temperature differences between battery sensors detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4170,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4170BatteryEqualize,,,,,,The rectifier output voltage is increased to equalize the battery voltage level.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4171,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4171BatteryManualTestInProgress,,,,,,Manual battery test is in progress.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4172,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4172BatteryAutoTestInProgress,,,,,,Automatic battery test is in progress.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4173,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4173MainBatteryDisconnectOpen,,,,,,Main battery disconnect is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4174,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4174BatteryTemperatureSensorFault,,,,,,A battery temperature sensor fault has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4175,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4175BypassFrequencyError,,,,,,The bypass frequency is outside the inverter synchronization limits.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4176,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4176BatteryCircuitBreaker1Open,,,,,,Battery circuit breaker 1 is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4177,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4177BatteryBreaker1OpenFailure,,,,,,Battery circuit breaker 1 failed to open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4178,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4178BatteryBreaker1CloseFailure,,,,,,Battery circuit breaker 1 failed to close.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4179,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4179BatteryCircuitBreaker2Open,,,,,,Battery circuit breaker 2 is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4180,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4180BatteryBreaker2OpenFailure,,,,,,Battery circuit breaker 2 failed to open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4181,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4181BatteryBreaker2CloseFailure,,,,,,Battery circuit breaker 2 failed to close.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4182,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4182BatteryCircuitBreaker3Open,,,,,,Battery circuit breaker 3 is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4183,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4183BatteryBreaker3OpenFailure,,,,,,Battery circuit breaker 3 failed to open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4184,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4184BatteryBreaker3CloseFailure,,,,,,Battery circuit breaker 3 failed to close.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4185,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4185BatteryCircuitBreaker4Open,,,,,,Battery circuit breaker 4 is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4186,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4186BatteryBreaker4OpenFailure,,,,,,Battery circuit breaker 4 failed to open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4187,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4187BatteryBreaker4CloseFailure,,,,,,Battery circuit breaker 4 failed to close.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4188,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4188BatteryCircuitBreaker5Open,,,,,,Battery circuit breaker 5 is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4189,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4189BatteryBreaker5OpenFailure,,,,,,Battery circuit breaker 5 failed to open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4190,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4190BatteryBreaker5CloseFailure,,,,,,Battery circuit breaker 5 failed to close.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4191,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4191BatteryCircuitBreaker6Open,,,,,,Battery circuit breaker 6 is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4192,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4192BatteryBreaker6OpenFailure,,,,,,Battery circuit breaker 6 failed to open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4193,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4193BatteryBreaker6CloseFailure,,,,,,Battery circuit breaker 6 failed to close.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4194,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4194BatteryCircuitBreaker7Open,,,,,,Battery circuit breaker 7 is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4195,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4195BatteryBreaker7OpenFailure,,,,,,Battery circuit breaker 7 failed to open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4196,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4196BatteryBreaker7CloseFailure,,,,,,Battery circuit breaker 7 failed to close.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4197,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4197BatteryCircuitBreaker8Open,,,,,,Battery circuit breaker 8 is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4198,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4198BatteryBreaker8OpenFailure,,,,,,Battery circuit breaker 8 failed to open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4199,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4199BatteryBreaker8CloseFailure,,,,,,Battery circuit breaker 8 failed to close.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4200,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4200BatteryChargingInhibited,,,,,,Battery charging is inhibited due to an external inhibit signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4213,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4213SystemShutdownEPO,,,,,,System shutdown due to Emergency Power Off (EPO).
.1.3.6.1.4.1.476.1.42.3.2.7.1.4214,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4214SystemShutdownREPO,,,,,,System shutdown due to Remote Emergency Power Off (REPO).
.1.3.6.1.4.1.476.1.42.3.2.7.1.4215,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4215SystemOutputOff,,,,,,The system output is off.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4216,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4216BypassBackfeedDetected,,,,,,The system detected a voltage on the bypass when none was expected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4217,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4217BypassManualXfrInhibited,,,,,,Manual transfer from inverter to bypass is inhibited - bypass not qualified.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4218,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4218BypassManualRexfrInhibited,,,,,,Manual transfer from bypass to inverter is inhibited - inverter output not qualified.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4219,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4219BatteryOverTemperature,,,,,,A battery temperature sensor is reporting a value above a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4220,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4220BatteryExternalMonitor1,,,,,,External battery monitor 1 - battery maintenance required.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4221,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4221BatteryExternalMonitor2,,,,,,External battery monitor 2 - battery maintenance required.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4222,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4222BatteryGroundFault,,,,,,Battery system ground fault amperage exceeds the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4229,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4229EmergencyPowerOffLatched,,,,,,System output is off - 'Emergency Power Off (EPO) - latched' requires manual reset.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4230,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4230SystemOutputLowPowerFactor,,,,,,The system output power factor is low, resulting in reduced output capacity.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4231,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4231OutputCurrentExceedsThreshold,,,,,,Output current for one or more phases exceeds a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4233,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4233InverterFailure,,,,,,Inverter failure - inverter output is off.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4234,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4234InverterOverloadPhaseA,,,,,,Inverter is operating with an overload on phase A.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4235,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4235InverterOverloadPhaseB,,,,,,Inverter is operating with an overload on phase B.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4236,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4236InverterOverloadPhaseC,,,,,,Inverter is operating with an overload on phase C.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4237,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4237InverterInhibitExternal,,,,,,Restart of the inverter is inhibited by an external signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4238,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4238InverterOutBreakerOpenFail,,,,,,Inverter output breaker failed to open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4239,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4239InverterOutBreakerCloseFail,,,,,,Inverter output breaker failed to close.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4270,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4270InputContact01,,,,,,The external input contact 1.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4271,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4271InputContact02,,,,,,The external input contact 2.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4272,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4272InputContact03,,,,,,The external input contact 3.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4273,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4273InputContact04,,,,,,The external input contact 4.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4274,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4274InputContact05,,,,,,The external input contact 5.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4275,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4275InputContact06,,,,,,The external input contact 6.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4276,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4276InputContact07,,,,,,The external input contact 7.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4277,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4277InputContact08,,,,,,The external input contact 8.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4278,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4278InputContact09,,,,,,The external input contact 9.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4279,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4279InputContact10,,,,,,The external input contact 10.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4280,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4280InputContact11,,,,,,The external input contact 11.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4281,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4281InputContact12,,,,,,The external input contact 12.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4282,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4282InputContact13,,,,,,The external input contact 13.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4283,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4283InputContact14,,,,,,The external input contact 14.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4284,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4284InputContact15,,,,,,The external input contact 15.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4285,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4285InputContact16,,,,,,The external input contact 16.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4286,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4286OutputAmpOverUserLimitPhsA,,,,,,The phase A output has exceeded the user amperage threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4287,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4287OutputAmpOverUserLimitPhsB,,,,,,The phase B output has exceeded the user amperage threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4288,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4288OutputAmpOverUserLimitPhsC,,,,,,The phase C output has exceeded the user amperage threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4289,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4289InverterTransferInhibitExt,,,,,,Transfer of critical bus source to inverter is inhibited by an external signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4290,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4290InverterShutdownOverload,,,,,,The inverter has shutdown due to a sustained overload.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4294,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4294InletAirOverTemperature,,,,,,The inlet air exceeds the maximum temperature threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4295,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4295RectifierFailure,,,,,,Rectifier failure - rectifier is off.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4296,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4296RectifierOperationInhibitExt,,,,,,The operation of the rectifier is inhibited by an external signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4297,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4297UPSOutputonInverter,,,,,,The output power is supplied by the inverter.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4298,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4298UPSOutputonBypass,,,,,,The output power is supplied by the bypass.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4299,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4299OutputLoadonMaintBypass,,,,,,The output power is supplied by the maintenance bypass.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4300,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4300InternalCommunicationsFailure,,,,,,The control has detected a communication failure of a component on the internal communication bus.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4308,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4308DCBusGroundFaultPositive,,,,,,A ground fault has been detected on the positive DC Bus link.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4309,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4309DCBusGroundFaultNegative,,,,,,A ground fault has been detected on the negative DC Bus link.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4310,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4310EquipmentOverTemperature,,,,,,Equipment over temperature summary event.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4311,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4311SystemFanFailure,,,,,,System fan failure - one or more fans have failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4313,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4313PasswordChanged,,,,,,Password changed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4314,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4314PowerSupplyFailure,,,,,,Power supply failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4315,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4315OnGenerator,,,,,,A generator is supplying the power to the system.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4316,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4316AutoRestartInProgress,,,,,,Auto restart is in progress.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4317,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4317AutoRestartInhibitedExt,,,,,,Auto restart inhibited due to an external signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4320,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4320InitiatedTransfertoBypass,,,,,,User initiated manual transfer to bypass.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4321,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4321InitiatedTransfertoInverter,,,,,,User initiated manual transfer to inverter.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4322,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4322BatteryTestPassed,,,,,,Battery test passed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4323,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4323BatteryTestFailed,,,,,,Battery test failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4324,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4324BatteryTestManuallyStopped,,,,,,The battery test was manually stopped prior to completion.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4325,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4325BackfeedBreakerOpen,,,,,,The backfeed breaker is in the open position.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4341,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4341VelocityAuthenticationFailure,,,,,,Notification of a message rejected by Velocity due to an authentication failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4360,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4360ReceptacleOverCurrent,,,,,,The system has detected a receptacle over current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4361,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4361ReceptacleUnderCurrent,,,,,,The system has detected a receptacle under current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4382,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4382SystemInputCurrentImbalance,,,,,,System Input Currents are Imbalanced.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4383,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4383BypassStaticSwitchOffExtrnl,,,,,,Bypass static switch is off due to the state of an external signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4384,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4384BatteryEoDDisconnect,,,,,,Battery disconnect due to end-of-discharge.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4389,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4389SystemOutputFault,,,,,,A fault has been detected in the system output.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4390,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4390InverterOffExternal,,,,,,Inverter is off (operation is inhibited) due to external signal state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4391,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4391InverterStaticSwitchSCRShort,,,,,,The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCR).
.1.3.6.1.4.1.476.1.42.3.2.7.1.4392,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4392TemperatureSensorError,,,,,,One or more temperature sensors cannot provide a valid temperature reading (i.e. sensor failure, wiring failure, sense circuit failure, etc).
.1.3.6.1.4.1.476.1.42.3.2.7.1.4406,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4406BranchOverCurrent,,,,,,The system has detected a module over current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4407,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4407BranchUnderCurrent,,,,,,The system has detected a module under current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4416,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4416BranchOverCurrent,,,,,,The system has detected a module over current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4417,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4417BranchUnderCurrent,,,,,,The system has detected a module under current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4421,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4421BranchFailure,,,,,,One or more conditions indicate a Branch Receptacle Module failure , service is required.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4436,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4436PDUOverCurrent,,,,,,The system has detected a module over current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4437,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4437PDUUnderCurrent,,,,,,The system has detected a module under current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4438,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4438SystemInternalTemperatureRise,,,,,,Excessive temperature rise internal to the system (i.e. difference between the output versus input temperature is too large).
.1.3.6.1.4.1.476.1.42.3.2.7.1.4439,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4439AutomaticRestartFailed,,,,,,Automatic restart failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4440,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4440FuseFailure,,,,,,A summary event indicating one or more fuse failures.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4441,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4441SystemControllerError,,,,,,System controller internal error.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4442,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4442SystemBreakersOpenFailure,,,,,,One or more breakers in the system failed to open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4448,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4448PDUOverCurrent,,,,,,The system has detected a module over current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4449,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4449PDUUnderCurrent,,,,,,The system has detected a module under current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4468,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4468PDUOverCurrentL1,,,,,,The system has detected a module over current condition on line 1.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4469,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4469PDUOverCurrentL2,,,,,,The system has detected a module over current condition on line 2.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4470,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4470PDUOverCurrentL3,,,,,,The system has detected a module over current condition on line 3.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4471,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4471PDUUnderCurrentL1,,,,,,The system has detected a module under current condition on line 1.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4472,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4472PDUUnderCurrentL2,,,,,,The system has detected a module under current condition on line 2.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4473,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4473PDUUnderCurrentL3,,,,,,The system has detected a module under current condition on line 3.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4492,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4492ReceptaclePowerStateOn,,,,,,The receptacle power state changed to the ON state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4493,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4493ReceptaclePowerStateOff,,,,,,The receptacle power state changed to the OFF state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4494,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4494BranchBreakerOpen,,,,,,The Branch Receptacle Module's input breaker is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4495,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4495DeviceConfigurationChange,,,,,,Device Configuration Change.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4496,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4496BasicDisplayModuleRemoved,,,,,,Basic Display Module Removed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4497,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4497BasicDisplayModuleDiscovered,,,,,,Basic Display Module Discovered.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4500,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4500PDUOverCurrent,,,,,,The system has detected a power module over current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4501,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4501PDUUnderCurrent,,,,,,The system has detected a power module under current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4502,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4502PDUFailure,,,,,,One or more conditions indicate a power module failure, service is required.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4503,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4503PDUCommunicationFail,,,,,,Internal communications failure with the Power Module.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4504,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4504BranchRemoved,,,,,,Branch Receptacle Module Removed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4505,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4505BranchDiscovered,,,,,,Branch Receptacle Module Discovered.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4506,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4506BranchOverCurrent,,,,,,The system has detected a Branch Receptacle Module over current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4507,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4507BranchCurrent,,,,,,The system has detected a Branch Receptacle Module under current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4508,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4508ReceptacleLoadRemoved,,,,,,The receptacle's load stopped drawing power.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4509,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4509ReceptacleLoadAdded,,,,,,The receptacle's load started to draw power.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4523,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4523ModuleRemoved,,,,,,Module Removed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4524,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4524ModuleAdded,,,,,,Module Added.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4550,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4550FirmwareUpdateRequired,,,,,,Module compatibility error requires a system firmware update to resolve.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4551,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4551GenericTestEvent,,,,,,A generic test event designed to evaluate system handling of events.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4580,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4580OverTemperature,,,,,,An over temperature condition was detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4581,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4581UnderTemperature,,,,,,An under temperature condition was detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4588,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4588OverRelativeHumidity,,,,,,An over relative humidity condition was detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4589,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4589UnderRelativeHumidity,,,,,,An under relative humidity condition was detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4601,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4601ExternalAirSensorAOverTemperature,,,,,,[Ext Air Sensor A Temperature] has exceeded [External Air Over Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.4604,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4604ExternalAirSensorBOverTemperature,,,,,,[Ext Air Sensor B Temperature] has exceeded [External Air Over Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.4608,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4608ExtAirSensorAUnderTemperature,,,,,,[Ext Air Sensor A Temperature] has dropped below [Ext Air Under Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.4611,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4611ExtAirSensorBUnderTemperature,,,,,,[Ext Air Sensor B Temperature] has dropped below [Ext Air Under Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.4615,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4615ExtDewPointOverTemperature,,,,,,At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.4618,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4618ExternalAirSensorAIssue,,,,,,The external air sensor A is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4621,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4621ExternalAirSensorBIssue,,,,,,The external air sensor B is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4626,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4626SupplyChilledWaterOverTemp,,,,,,[Supply Fluid Temperature] has exceeded [High Supply Fluid Temperature Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.4629,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4629SupplyChilledWaterTempSensorIssue,,,,,,The supply chilled water temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4634,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4634SupplyRefrigerantOverTemp,,,,,,Event that is activated when [Supply Refrigerant Temperature] exceeds [Supply Refrig Over Temp Threshold]. The event is deactivated when the temperature drops below the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4637,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4637SupplyRefrigerantUnderTemp,,,,,,[Supply Refrigerant Temperature] has dropped below a specified threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4640,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4640SupplyRefrigerantTempSensorIssue,,,,,,The supply refrigeramt temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4645,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4645SupplyFluidOverTemp,,,,,,[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.4648,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4648SupplyFluidUnderTemp,,,,,,[Supply Fluid Temperature] has dropped below a specified threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4651,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4651SupplyFluidTempSensorIssue,,,,,,The supply fluid temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4656,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4656Pump1LossofFlow,,,,,,Loss of flow is detected in pump 1. The loss of flow condition occurs when no differential pressure is detected across the pump.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4659,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4659Pump2LossofFlow,,,,,,Loss of flow is detected in pump 2. The loss of flow condition occurs when no differential pressure is detected across the pump.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4662,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4662PumpShortCycle,,,,,,Pumps have short cycled. A short cycle is defined as turning on and off a number of times over a set time period.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4669,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4669Compressor1AHighHeadPressure,,,,,,Compressor 1A high head pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4672,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4672Compressor1BHighHeadPressure,,,,,,Compressor 1B high head pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4675,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4675Compressor2AHighHeadPressure,,,,,,Compressor 2A high head pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4678,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4678Compressor2BHighHeadPressure,,,,,,Compressor 2B high head pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4681,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4681Compressor1AShortCycle,,,,,,Compressor 1A short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4684,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4684Compressor1BShortCycle,,,,,,Compressor 1B short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4687,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4687Compressor2AShortCycle,,,,,,Compressor 2A short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4690,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4690Compressor2BShortCycle,,,,,,Compressor 2B short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4693,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4693Tandem1LowSuctionPressure,,,,,,'Tandem compressors' 1 low suction pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4696,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4696Tandem2LowSuctionPressure,,,,,,'Tandem compressors' 2 low suction pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4703,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4703ChilledWaterControlValvePosition,,,,,,Chilled water valve out of position. Chilled water control valve position does not match expected value.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4711,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4711SystemCondensationDetected,,,,,,System condensation detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4714,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4714ShutdownLossOfPower,,,,,,System lost power. This event becomes active when the unit is powered on following an unexpected loss of power.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4720,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4720SmokeDetected,,,,,,Smoke detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4723,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4723WaterUnderFloor,,,,,,Water under the floor is detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4726,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4726ServiceRequired,,,,,,Unit requires servicing.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4729,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4729FanIssue,,,,,,One or more fans are not operating within their operational parameters.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4732,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4732ReceptacleLoadDropped,,,,,,The receptacle's load is not drawing power.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4740,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4740BatteryAutomaticTestInhibited,,,,,,Automatic (scheduled) battery tests are inhibited.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4741,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4741BatterySelfTest,,,,,,Battery self test is in progress.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4742,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4742BatteryLowShutdown,,,,,,Battery disconnect due to end-of-discharge.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4747,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4747EquipmentTemperatureSensorFail,,,,,,One or more temperature sensors report a temperature outside of the range of expected operation.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4749,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4749SystemFanFailureRedundant,,,,,,Redundant system fan failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4750,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4750MultipleFanFailure,,,,,,Multiple fan failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4753,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4753MainControllerFault,,,,,,A Main Controller fault has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4754,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4754SystemBreakersCloseFailure,,,,,,One or more breakers in the system failed to close.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4755,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4755InputFilterCycleLock,,,,,,The input filter disconnect is open due to exceeding the maximum number of cycles.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4756,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4756ServiceCodeActive,,,,,,Service code is running.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4757,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4757LBSActive,,,,,,The Load Bus Sync option is active.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4758,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4758LBSInhibited,,,,,,The system has detected that conditions to perform Load Bus Sync are not satisfied.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4759,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4759LeadingPowerFactor,,,,,,The leading output Power Factor has fallen below a specified value.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4760,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4760ControlsResetRequired,,,,,,A controls reset is required due to one or more critical settings changing.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4823,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4823ParallelCommWarning,,,,,,Parallel communication bus warning.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4824,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4824SystemCommFail,,,,,,Failure of a device on the multi-module system communication bus.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4825,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4825LossofRedundancy,,,,,,The multi-module collection doesn't have enough modules to satisfy the redundancy configuration.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4826,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4826BPSSStartupInhibit,,,,,,The Bypass Static Switch startup is inhibited.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4827,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4827MMSTransferInhibit,,,,,,The critical load can not be manually transferred from inverter to bypass.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4828,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4828MMSRetransferInhibit,,,,,,The critical load can not be manually retransferred from bypass to inverter.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4830,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4830MMSLossofSyncPulse,,,,,,Multi-module system loss of sync pulse.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4831,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4831MMSOverload,,,,,,Multi-module system overload.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4834,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4834MMSOnBattery,,,,,,The multi-module system is on battery.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4835,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4835MMSLowBatteryWarning,,,,,,Multi-module system low battery warning.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4906,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4906LowAmbientTemperature,,,,,,The system has detected a low ambient temperature condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4907,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4907HighAmbientTemperature,,,,,,The system has detected a high ambient temperature condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4908,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4908LowOverallVoltage,,,,,,The system has detected a low battery string overall voltage condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4909,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4909HighOverallVoltage,,,,,,The system has detected a high battery string overall voltage condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4910,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4910HighBatteryStringCurrent,,,,,,The system has detected a high battery string current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4911,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4911LowBatteryStringFloatCurrent,,,,,,The system has detected a low battery string float current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4912,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4912HighBatteryStringFloatCurrent,,,,,,The system has detected a high battery string float current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4913,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4913HighBatteryStringRippleCurrent,,,,,,The system has detected a high battery string ripple current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4914,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4914BatteryStringDischargeDetected,,,,,,The system has detected a battery string discharge condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4915,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4915MaximumDischargeTimeExceeded,,,,,,The system has detected an excessive discharge time condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4916,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4916DischargeLowOverallVoltage,,,,,,The system has detected a low battery string overall voltage condition during a discharge.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4917,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4917DischargeLowCellVoltage,,,,,,The system has detected a low cell voltage condition during a discharge.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4918,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4918DischargeHighBatteryStringCurrent,,,,,,The system has detected a high battery string current condition during a discharge.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4919,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4919ExcessiveCelltoCellTemperatureDeviation,,,,,,The system has detected an excessive cell to cell temperature deviation condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4920,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4920ExcessiveCelltoAmbientTemperatureDeviation,,,,,,The system has detected an excessive cell to ambient temperature deviation condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4964,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4964LowCellVoltage,,,,,,The system has detected a low cell voltage condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4965,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4965HighCellVoltage,,,,,,The system has detected a high cell voltage condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4966,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4966LowCellTemperature,,,,,,The system has detected a low cell temperature condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4967,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4967HighCellTemperature,,,,,,The system has detected a high cell temperature condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4968,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4968LowInternalResistance,,,,,,The system has detected a low internal resistance condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4969,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4969HighInternalResistance,,,,,,The system has detected a high internal resistance condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4970,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4970HighIntercellResistance,,,,,,The system has detected a high intercell resistance condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4978,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4978IntertierResistanceHigh,,,,,,The system has detected a high intertier resistance condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4980,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4980SupplyChilledWaterLossofFlow,,,,,,Supply chilled water or glycol flow is too low.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4983,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4983SupplyRefrigOverTempBand1,,,,,,[Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 1].
.1.3.6.1.4.1.476.1.42.3.2.7.1.4986,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4986SupplyRefrigUnderTempBand1,,,,,,[Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 1].
.1.3.6.1.4.1.476.1.42.3.2.7.1.4990,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4990SupplyRefrigOverTempBand2,,,,,,[Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 2].
.1.3.6.1.4.1.476.1.42.3.2.7.1.4993,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4993SupplyRefrigUnderTempBand2,,,,,,[Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 2].
.1.3.6.1.4.1.476.1.42.3.2.7.1.4996,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4996Inverter1ShortCycle,,,,,,Inverter for pump 1 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
.1.3.6.1.4.1.476.1.42.3.2.7.1.4999,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId4999Inverter2ShortCycle,,,,,,Inverter for pump 2 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5015,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5015SupplyAirOverTemperature,,,,,,[Supply Air Temperature] has exceeded [High Supply Air Temperature Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5019,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5019SupplyAirUnderTemperature,,,,,,[Supply Air Temperature] has dropped below [Low Supply Air Temperature Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5023,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5023ReturnAirOverTemperature,,,,,,[Return Air Temperature] has exceeded [High Return Air Temperature Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5026,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5026SupplyAirSensorIssue,,,,,,The air sensor at the outlet of the unit is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5034,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5034HighReturnHumidity,,,,,,[Return Humidity] has exceeded [High Return Humidity Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5036,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5036LowReturnHumidity,,,,,,[Return Humidity] has dropped below [Low Return Humidity Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5037,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5037HumidifierHoursExceeded,,,,,,Operating hours for the humidifier have exceeded the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5038,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5038DehumidifierHoursExceeded,,,,,,Operating hours for the dehumidifier have exceeded the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5039,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5039HumidifierUnderCurrent,,,,,,The electrical current to the humidifier has dropped below its lower threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5040,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5040HumidifierOverCurrent,,,,,,The electrical current to the humidifier has exceeded its upper threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5041,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5041HumidifierLowWater,,,,,,The water level in the humidifier has dropped below its threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5042,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5042HumidifierCylinderWorn,,,,,,Humidifier cylinder is not operating properly and needs to be replaced.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5043,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5043HumidifierIssue,,,,,,Humidifier issue detected, causing it to be locked out.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5044,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5044ExtHumidifierLockout,,,,,,The humidifier is shut down and disabled by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5045,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5045HumidifierControlBoardNotDetected,,,,,,Humidifier control board is required to be connected, but no signal is detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5046,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5046ReturnHumidityOutOfProportionalBand,,,,,,[Return Humidity] has exceeded the upper limit of [Dehumidification Proportional Band], or has dropped below the lower limit of [Humidification Proportional Band] ], for an extended period of time.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5053,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5053LossofAirFlow,,,,,,No air flow through the unit due to failure of all fans.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5054,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5054FanHoursExceeded,,,,,,Operating hours for the unit blower fan have exceeded the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5055,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5055TopFanIssue,,,,,,The top fan is not operating within its normal parameters.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5056,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5056BottomFanIssue,,,,,,The bottom fan is not operating within its normal parameters.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5060,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5060RemoteSensorIssue,,,,,,Remote sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5062,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5062Compressor1LowSuctionPressure,,,,,,Compressor 1 low suction pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5063,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5063Compressor1HoursExceeded,,,,,,Operating hours for compressor 1 have exceeded the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5064,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5064DigScrollComp1TempSensorIssue,,,,,,Digital scroll compressor 1 temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5065,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5065DigScrollComp1OverTemp,,,,,,Digital scroll compressor 1 shut off because its head temperature has exceeded the upper threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5066,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5066Compressor1LowPressureTransducerIssue,,,,,,Compressor 1 low pressure transducer is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5067,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5067ExtCompressorLockout,,,,,,The compressor is shut down and disabled by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5068,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5068ReheaterOverTemperature,,,,,,The temperature of the reheater has exceeded its threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5069,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5069ElectricReheater1HoursExceeded,,,,,,Operating hours for electric reheater 1 have exceeded the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5070,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5070ExtReheatLockout,,,,,,The reheater is shut down and disabled by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5071,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5071Condenser1Issue,,,,,,Condenser 1 is not operating within its normal parameters.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5072,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5072CondenserVFDIssue,,,,,,The condenser fan Variable Frequency Drive is offline.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5073,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5073CondenserTVSSIssue,,,,,,The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5104,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5104ExtOverTemperature,,,,,,A temperature has exceeded its threshold, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5105,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5105ExtLossofFlow,,,,,,Loss of flow is detected, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5106,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5106ExtCondenserPumpHighWater,,,,,,High water is detected in the condensate pump by the auxiliary float, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5107,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5107ExtStandbyGlycolPumpOn,,,,,,The standby glycol pump is on, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5108,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5108ExternalFireDetected,,,,,,Fire detected, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5109,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5109UnitOn,,,,,,Unit was turned on.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5110,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5110UnitOff,,,,,,Unit was turned off.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5111,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5111UnitStandby,,,,,,Unit was placed in standby mode.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5112,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5112UnitPartialShutdown,,,,,,An event has occurred requiring some system components to be shutdown and disabled.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5113,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5113UnitShutdown,,,,,,An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5114,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5114WaterLeakageDetectorSensorIssue,,,,,,The water leakage detector sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5115,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5115BMSCommunicationsTimeout,,,,,,Building Management System (or external monitoring system) has not communicated with the system within the expected timeframe.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5116,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5116MaintenanceDue,,,,,,The calculated maintenance date has been reached.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5117,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5117MaintenanceCompleted,,,,,,Maintenance has been completed on the unit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5118,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5118CloggedAirFilter,,,,,,Air filter is dirty and needs to be (cleaned or) replaced.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5119,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5119RAMBatteryIssue,,,,,,RAM or RAM backup battery is not operating correctly.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5120,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5120MasterUnitCommunicationLost,,,,,,Communication with master unit has been lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5121,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5121HighPowerShutdown,,,,,,Supply to high power components has been shutdown.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5126,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5126DigScrollComp2OverTemp,,,,,,Digital scroll compressor 2 shut off because its head temperature has exceeded the upper threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5144,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5144OutputOfUf,,,,,,The output frequency has exceeded a specified range for a specified period of time.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5145,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5145MMSModuleAlarmActive,,,,,,Active alarm or fault of any module in a multi-module system.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5146,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5146CompressorPumpDownIssue,,,,,,Unable to pump down suction-side pressure during compressor shutdown.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5147,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5147ReturnAirSensorIssue,,,,,,The air sensor at the inlet of the unit is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5148,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5148CompressorHighPressureTransducerIssue,,,,,,Compressor high pressure transducer is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5149,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5149BatteryNotQualified,,,,,,The UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5150,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5150BatteryTerminalsReversed,,,,,,The measured battery voltage is a negative value due to reverse battery terminal connections.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5151,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5151BatteryConverterFailure,,,,,,Battery converter failure. This is a summary event caused by one or more power sub-modules in a UPS module.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5152,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5152InverterSCROpen,,,,,,The system has detected an open across one or more inverter static switch Silicon Controlled Rectifiers.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5153,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5153LoadSharingFault,,,,,,Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal current.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5154,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5154DCBusAbnormal,,,,,,The system has detected an abnormal DC Bus Voltage.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5155,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5155MainsInputNeutralLost,,,,,,Loss of neutral in the input source is detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5156,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5156LoadImpactTransfer,,,,,,On bypass as result of load impact.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5157,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5157UserOperationInvalid,,,,,,User attempted an invalid operation.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5158,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5158PowerSubModuleFault,,,,,,One or more failures detected in power module, inverter or rectifier.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5178,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5178OutputOvervoltage,,,,,,One or more of the output phase voltages has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5179,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5179OutputUndervoltage,,,,,,One or more of the output phase voltages has dropped below the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5180,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5180OutputOvercurrent,,,,,,One or more of the phase currents has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5181,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5181NeutralOvercurrent,,,,,,The system's neutral current has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5182,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5182GroundOvercurrent,,,,,,System ground current has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5183,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5183OutputVoltageTHD,,,,,,The Total Harmonic Distortion of the voltage on one or more of the output phases has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5184,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5184OutputFrequencyError,,,,,,The output frequency is outside a specified range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5185,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5185TransformerOvertemperature,,,,,,Indicates a unit transformer overtemperature condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5212,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5212PanelSummaryStatus,,,,,,The status for the panel. Detects and annunciates upon occurrence of any branch or panelboard main breaker active event.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5213,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5213PanelOvervoltage,,,,,,One or more of the phase voltages of this panel has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5214,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5214PanelUndervoltage,,,,,,One or more of the phase voltages of this panel is less than the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5215,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5215PanelOvercurrent,,,,,,One or more of the phase currents of this panel has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5216,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5216PanelNeutralOvercurrent,,,,,,The Neutral current of this panel has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5217,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5217PanelGroundOvercurrent,,,,,,The Ground current of this panel has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5226,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5226BranchOvercurrent,,,,,,The current in one or more phases of this branch exceeds the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5227,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5227BranchUndercurrent,,,,,,The current in one or more phases of this branch is less than the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5245,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5245SubfeedPhaseOvercurrent,,,,,,One or more of the phase currents in this subfeed has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5246,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5246SubfeedNeutralOvercurrent,,,,,,The Neutral current in this subfeed has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5247,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5247SubfeedGroundOvercurrent,,,,,,The Ground current of this subfeed has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5249,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5249EventState,,,,,,The present state of this digital event input.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5263,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5263CompressorNotStopping,,,,,,Compressor commanded to stop, but continues to run.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5269,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5269CompressorHoursExceeded,,,,,,[Compressor Hours] has exceeded [Compressor Hours Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5270,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5270CompressorHighHeadPressure,,,,,,Compressor is shut down due to high head pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5271,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5271CompressorLowSuctionPressure,,,,,,Compressor is shut down due to low suction pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5272,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5272CompressorThermalOverload,,,,,,Compressor is shut down due to thermal overload.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5273,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5273CompressorLowOilPressure,,,,,,Compressor low oil pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5274,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5274CompressorHeadPressureOverThreshold,,,,,,Compressor head pressure has exceeded an upper threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5275,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5275CompressorLossofDifferentialPressure,,,,,,Compressor is shut down due to low differential pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5277,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5277CondenserFanIssue,,,,,,Condenser fan is not operating within its operational parameters.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5278,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5278LowCondenserRefrigerantPressure,,,,,,Refrigerant pressure in condenser coil is too low.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5280,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5280LowFluidPressure,,,,,,[Fluid Pressure] has dropped below a specified threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5293,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5293ReturnFluidOverTemp,,,,,,[Return Fluid Temperature] has exceeded a specified threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5294,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5294ReturnFluidUnderTemp,,,,,,[Return Fluid Temperature] has dropped below a specified threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5295,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5295ReturnFluidTempSensorIssue,,,,,,The return fluid temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5296,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5296TeamworkReturnFluidTempSensorIssue,,,,,,The return fluid temperature sensors for all Teamwork units are disconnected or the signals are out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5297,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5297AllPumpsLossofFlow,,,,,,System is shut down due to loss of flow in all available pumps.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5300,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5300PumpHoursExceeded,,,,,,[Pump Hours] has exceeded [Pump Hours Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5306,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5306FreeCoolingValveHoursExceeded,,,,,,[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5308,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5308EvaporatorInletTempSensorIssue,,,,,,The evaporator inlet temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5309,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5309TeamworkEvaporatorInletTempSensorIssue,,,,,,The evaporator inlet temperature sensors for all Teamwork units are disconnected or the signals are out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5310,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5310EvaporatorFluidFreezeAutoReset,,,,,,Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down, but will restart when the temperature rises above the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5311,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5311EvaporatorFluidFreezeManualResetRequired,,,,,,Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down and requires a manual reset.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5315,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5315SubgroupEventOccurredDuringCommunicationLoss,,,,,,While subgroup unit communication was lost, an event occurred on the subgroup unit. Please check subgroup unit event log.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5335,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5335ReturnAirUnderTemperature,,,,,,[Return Air Temperature] has dropped below [Low Return Air Temperature Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5349,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5349ExtAirSensorAHighHumidity,,,,,,[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5351,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5351ExtAirSensorALowHumidity,,,,,,[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5352,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5352CompressorShortCycle,,,,,,Compressor short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5354,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5354DigScrollCompDischargeTempSensorIssue,,,,,,Digital scroll compressor discharge temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5355,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5355DigScrollCompOverTemp,,,,,,Digital scroll compressor is shut down due to head temperature exceeding an upper threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5361,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5361ExtFreeCoolingLockout,,,,,,Free cooling is disabled by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5362,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5362FreeCoolingTempSensorIssue,,,,,,The free cooling fluid temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5365,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5365HotWaterHotGasValveHoursExceeded,,,,,,[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5368,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5368ElectricReheaterHoursExceeded,,,,,,[Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5376,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5376MainFanOverload,,,,,,Main fan is shut down due to thermal overload.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5377,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5377Condenser,,,,,,Condenser is not operating within its operational parameters.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5415,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5415ExtLossofAirBlower,,,,,,Loss of air blower is detected, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5416,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5416ExtStandbyUnitOn,,,,,,Standby unit is on, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5417,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5417DigitalOutputBoardNotDetected,,,,,,Digital output board is required to be connected, but no signal is detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5418,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5418UnitCodeMissing,,,,,,Unit code has not been entered and saved.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5419,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5419UnitCommunicationLost,,,,,,Master has lost communication with one or more networked units.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5422,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5422OvertemperaturePowerOff,,,,,,Power turned off because equipment over temperature limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5423,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5423TooManySensors,,,,,,The number of sensors connected to the PDU exceeds the allowable limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5432,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5432TransformerOvertemperaturePowerOff,,,,,,Output power shutdown due to high transformer temperature.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5433,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5433TransformerOvertemperature,,,,,,Transformer temperature has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5434,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5434TransformerTemperatureSensorFail,,,,,,Transformer temperature sensor has failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5436,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5436LowAmbientTemperatureProbeTwo,,,,,,The system has detected a low ambient temperature condition on temperature probe 2.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5437,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5437HighAmbientTemperatureProbeTwo,,,,,,The system has detected a high ambient temperature condition on temperature probe 2.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5438,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5438ThermalRunawayDetected,,,,,,The system has detected a thermal runaway condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5439,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5439BatteryStringEqualize,,,,,,The system has detected a battery string equalize condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5440,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5440BatteryStringOffline,,,,,,The system has detected the battery string is offline.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5442,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5442DischargeLowCellVoltage,,,,,,The system has detected a low cell voltage condition during a discharge.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5447,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5447MMSPowerSharing,,,,,,A module is not sharing power with the other modules in a multi -module system.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5453,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5453ModuleInStandbyIntelligentParalleling,,,,,,Module is placed into standby operation per Intelligent Paralleling.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5456,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5456ECOModeActive,,,,,,Conditions for Activation or Automatic Reactivation have been satisfied.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5457,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5457ECOModeSuspended,,,,,,ECO Mode session is suspended.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5458,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5458ExcessECOSuspends,,,,,,Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto Suspensions setting.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5471,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5471DoorOpen,,,,,,An open door was detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5472,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5472DoorSensorDisconnected,,,,,,Door sensor disconnect detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5479,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5479ContactClosureOpen,,,,,,An open circuit was detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5480,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5480ContactClosureClosed,,,,,,A closed circuit was detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5492,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5492ExtSystemCondensationDetected,,,,,,External system condensation detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5495,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5495ExtFanIssue,,,,,,One or more fans are not operating within their operational parameters.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5500,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5500ExtRemoteShutdown,,,,,,Unit is shut down by a remote signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5505,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5505HotAisleTempOutofRange,,,,,,The air temperature in the Hot aisle is either above [Hot Aisle Over Temp Threshold] or below [Hot Aisle Under Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5508,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5508ColdAisleTempOutofRange,,,,,,The air temperature in the cold aisle is either above [Cold Aisle Over Temp Threshold] or below [Cold Aisle Under Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5512,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5512RemoteShutdown,,,,,,Unit is shut down by a remote signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5513,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5513CompressorCapacityReduced,,,,,,Compressor capacity has been reduced.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5514,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5514CompressorLowPressureTransducerIssue,,,,,,Compressor low pressure transducer is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5524,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5524PDUNeutralOverCurrent,,,,,,The system has detected a neutral over current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5531,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5531CondenserCommunicationLost,,,,,,Communication with condenser unit has been lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5535,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5535CondenserOutsideAirTempSensorIssue,,,,,,Condenser outside air temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5536,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5536CondenserOutsideAirTempOutofOperatingRange,,,,,,[Condenser Outside Air Temperature] is either above an upper threshold or below a lower threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5537,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5537CondenserControlBoardIssue,,,,,,The condenser control board is reporting an issue.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5539,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5539CondenserRefrigerantPressureOverThreshold,,,,,,Condenser refrigerant pressure has exceeded a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5540,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5540CondenserRefrigerantPressureUnderThreshold,,,,,,Condenser refrigerant pressure has dropped below a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5541,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5541CondenserRefrigerantPressureSensorIssue,,,,,,Condenser refrigerant pressure sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5542,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5542CondenserSupplyRefrigerantOverTemp,,,,,,Condenser supply refrigerant temperature has exceeded a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5543,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5543CondenserSupplyRefrigerantUnderTemp,,,,,,Condenser supply refrigerant temperature has dropped below a specified threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5544,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5544CondenserSupplyRefrigerantTempSensorIssue,,,,,,Condenser supply refrigerant temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5545,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5545CondenserMaxFanSpeedOverride,,,,,,Fan speed exceeding the maximum set point in order to alleviate a high temperature or pressure condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5559,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5559EvaporatorReturnFluidOverTemp,,,,,,[Evaporator Return Fluid Temperature] has exceeded a threshold. The event is deactivated when the temperature drops below the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5560,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5560EvaporatorReturnFluidUnderTemp,,,,,,[Evaporator Return Fluid Temperature] has dropped below a threshold. The event is deactivated when the temperature rises above the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5561,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5561LBSActiveMaster,,,,,,This UPS system has been selected as the functional Master Load Bus Synchronization (LBS) system.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5562,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5562LBSActiveSlave,,,,,,This UPS system is synchronized to the output bus of the UPS system that has been selected as the Master Load Bus Synchronization (LBS) system.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5563,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5563DCBusLowFault,,,,,,The DC Bus voltage has reached a critical low level.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5564,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5564FanContactorOpen,,,,,,The fan contactor is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5565,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5565FanContactorOpenFail,,,,,,The fan contactor failed to open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5566,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5566FanContactorCloseFail,,,,,,The fan contactor failed to close.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5567,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5567IPInhibit,,,,,,The intelligent paralleling operation is inhibited.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5568,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5568InputUndervoltage,,,,,,One or more of the input phase voltages has dropped below the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5569,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5569InputOvervoltage,,,,,,One or more of the input phase voltages has exceeded the limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5573,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5573AmbientAirSensorIssue,,,,,,Ambient air sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5577,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5577ExtDewPointUnderTemperature,,,,,,At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped below [Ext Dew Point Under Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5578,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5578DewPointOverTemperature,,,,,,Dew point temperature reading has exceeded the upper threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5579,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5579DewPointUnderTemperature,,,,,,Dew point temperature reading has dropped below the lower threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5588,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5588UnspecifiedGeneralEvent,,,,,,One or more unspecified events active. See local unit display for further details.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5593,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5593RemoteSensorAverageOverTemperature,,,,,,[Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5594,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5594RemoteSensorAverageUnderTemperature,,,,,,[Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5595,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5595RemoteSensorSystemAverageOverTemperature,,,,,,[Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5596,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5596RemoteSensorSystemAverageUnderTemperature,,,,,,[Remote Sensor System Average Temperature] has dropped below [Remote Sensor Under Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5597,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5597RemoteSensorOverTemperature,,,,,,[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5598,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5598RemoteSensorUnderTemperature,,,,,,[Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5600,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5600AirEconomizerEmergencyOverride,,,,,,Indoor room temperature has exceeded its upper threshold and the outdoor air damper has been opened for emergency cooling.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5601,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5601AirEconomizerReducedAirflow,,,,,,Air economizer filter is dirty and needs to be cleaned or replaced.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5604,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5604CompressorSuperheatOverThreshold,,,,,,Compressor discharge refrigerant superheat temperature has exceeded an upper threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5609,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent,,,,,,The delta temperature between a cell temperature and the ambient temperature has exceeded the thermal runaway cell to ambient temperature threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5610,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5610ThermalRunawayCelltoCellTemperatureEvent,,,,,,The delta temperature between two cells has exceeded the thermal runaway cell to cell temperature threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5611,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5611ThermalRunawayChargerCurrentLevelOneEvent,,,,,,The Battery-String charger current has exceeded the thermal runaway charger current level one threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5612,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5612ThermalRunawayChargerCurrentLevelTwoEvent,,,,,,The Battery-String charger current has exceeded the thermal runaway charger current level two threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5617,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5617TemperatureControlSensorIssue,,,,,,The air sensor selected for cooling control is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5621,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5621EEVSuperheatBelowThreshold,,,,,,Electronic expansion valve refrigerant low superheat event.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5622,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5622EEVDischargeTempAboveThreshold,,,,,,Electronic expansion valve refrigerant high discharge temperature event.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5623,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5623EEVBatteryIssue,,,,,,Electronic expansion valve battery cannot be recharged and needs to be replaced.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5624,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5624EEVPowerIssue,,,,,,Electronic expansion valve lost power and is running on battery backup.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5625,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5625EEVUnspecifiedGeneralEvent,,,,,,One or more unspecified electronic expansion valve events active. See local unit display for further details.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5629,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5629StaticPressureSensorIssue,,,,,,The static pressure sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5630,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5630HighStaticPressure,,,,,,High static pressure event.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5631,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5631LowStaticPressure,,,,,,Low static pressure event.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5636,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5636PumpUnspecifiedGeneralEvent,,,,,,One or more unspecified pump events active. See local unit display for further details.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5637,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5637CondenserUnitUnspecifiedGeneralEvent,,,,,,One or more unspecified condenser unit events active. See local unit display for further details.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5638,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5638CondenserCircuitUnspecifiedGeneralEvent,,,,,,One or more unspecified condenser circuit events active. See local unit display for further details.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5642,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5642SFAReservedEvent1,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5643,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5643SFAReservedEvent2,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5644,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5644SFAReservedEvent3,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5645,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5645SFAReservedEvent4,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5646,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5646SFAReservedEvent5,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5647,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5647SFAReservedEvent6,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5648,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5648SFAReservedEvent7,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5649,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5649SFAReservedEvent8,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5650,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5650SFAReservedEvent9,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5651,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5651SFAReservedEvent10,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5652,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5652SFAReservedEvent11,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5653,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5653SFAReservedEvent12,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5654,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5654SFAReservedEvent13,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5655,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5655SFAReservedEvent14,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5656,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5656SFAReservedEvent15,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5657,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5657SFAReservedEvent16,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5658,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5658SFAReservedEvent17,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5659,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5659SFAReservedEvent18,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5660,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5660SFAReservedEvent19,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5661,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5661SFAReservedEvent20,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5662,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5662SFAReservedEvent21,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5663,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5663SFAReservedEvent22,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5664,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5664SFAReservedEvent23,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5665,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5665SFAReservedEvent24,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5666,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5666SFAReservedEvent25,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5768,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5768OutletAirOvertemperatureLimit,,,,,,The difference between the outlet air temperature and inlet air temperature exceeds a specified maximum temperature.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5769,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5769EMOShutdown,,,,,,An Emergency Module Off command has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5770,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5770TopOutletFanFault,,,,,,Top outlet fan fault - one or more top outlet fans have failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5771,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5771MMSOverCapacity,,,,,,The multi-module system load is larger than the apparent power limit setting.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5773,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5773CompressorCapacityNormal,,,,,,Compressor has returned to normal load capacity.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5774,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5774CompressorContactorIssue,,,,,,Compressor contactor is not closing during compressor startup or is not opening during compressor shutdown.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5775,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5775UnitShutdownUnspecifiedGeneralEvent,,,,,,One or more unspecified unit shutdown events active. See local unit display for further details.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5776,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5776PDULowVoltageLN,,,,,,The system has detected a module under voltage condition (LN).
.1.3.6.1.4.1.476.1.42.3.2.7.1.5777,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5777PDULowVoltageLL,,,,,,The system has detected a module under voltage condition (LL).
.1.3.6.1.4.1.476.1.42.3.2.7.1.5778,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5778PDULowVoltageL1L2,,,,,,The system has detected a line-to-line under voltage condition (L1 -L2).
.1.3.6.1.4.1.476.1.42.3.2.7.1.5779,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5779PDULowVoltageL2L3,,,,,,The system has detected a line-to-line under voltage condition (L2 -L3).
.1.3.6.1.4.1.476.1.42.3.2.7.1.5780,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5780PDULowVoltageL3L1,,,,,,The system has detected a line-to-line under voltage condition (L3 -L1).
.1.3.6.1.4.1.476.1.42.3.2.7.1.5781,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5781PDULowVoltageL1N,,,,,,The system has detected a line to neutral under voltage condition (L1-N).
.1.3.6.1.4.1.476.1.42.3.2.7.1.5782,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5782PDULowVoltageL2N,,,,,,The system has detected a line to neutral under voltage condition (L2-N).
.1.3.6.1.4.1.476.1.42.3.2.7.1.5783,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5783PDULowVoltageL3N,,,,,,The system has detected a line to neutral under voltage condition (L3-N).
.1.3.6.1.4.1.476.1.42.3.2.7.1.5784,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5784BranchLowVoltageLN,,,,,,The system has detected a module under voltage condition (LN).
.1.3.6.1.4.1.476.1.42.3.2.7.1.5785,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5785BranchLowVoltageLL,,,,,,The system has detected a module under voltage condition (LL).
.1.3.6.1.4.1.476.1.42.3.2.7.1.5786,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5786BranchLowVoltage,,,,,,The system has detected a module under voltage condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5788,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5788ContTieActive,,,,,,Continuous Power Tie Active.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5792,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5792UserkWhReset,,,,,,The user kWh accumulator was reset to zero by the operator.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5796,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5796PeakkWReset,,,,,,The Peak kW was reset.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5798,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5798BypassOverload,,,,,,Bypass overloaded, reduce load immediately.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5801,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5801LowBatteryShutdownImminent,,,,,,If active and guaranteed shutdown is enabled, a low battery reserve condition exists that will shutdown the UPS.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5806,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5806OutputOverload,,,,,,An overload exists on the output.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5807,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5807OutputOffPending,,,,,,Output off pending - shutdown imminent.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5808,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5808SystemShutdownOutputShort,,,,,,Shutdown was due to a short on the output.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5809,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5809SystemShutdownLowBattery,,,,,,Shutdown was due to a low battery condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5810,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5810SystemShutdownRemoteShutdown,,,,,,Shutdown was due to a remote communications shutdown command.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5811,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5811SystemShutdownHardwareFault,,,,,,Shutdown was due to an externally applied hardware control signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5817,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5817LossofRedundancy,,,,,,The system has an insufficient number of power modules to provide redundancy.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5818,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5818PowerModuleFailure,,,,,,One or more conditions indicate a power module failure, service is required.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5819,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5819PowerModuleWarning,,,,,,One or more power modules is reporting a warning condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5838,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5838PowerModuleFanFault,,,,,,The Power Module has detected a fan fault.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5839,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5839PowerModuleOverTemperature,,,,,,The Power Module has detected an over temperature condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5840,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5840PowerModuleShutdownOverTemperature,,,,,,Power Module has shutdown due to over temperature.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5842,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5842ChargerModuleFanFault,,,,,,The Charger Module has detected a fan fault.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5847,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5847BatteryModuleTemperatureSensorFault,,,,,,A Battery Module temperature sensor fault has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5848,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5848BatteryModuleOverTemperature,,,,,,The Battery Module has detected an over temperature condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5849,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5849ReplaceBatteryModule,,,,,,The Battery Module needs to be replaced.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5850,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5850SystemShutdownTransformerOverTemperature,,,,,,System shutdown due to transformer over temperature.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5851,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5851MaximumLoadAlarm,,,,,,Maximum load alarm indicating load setting has been exceeded.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5856,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5856BatteryModuleFault,,,,,,One or more battery modules are reporting a fault condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5857,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5857BatteryModuleWarning,,,,,,One or more battery modules are reporting a warning condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5862,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5862CheckAirFilter,,,,,,Please check air filter, it may need to be cleaned or replaced.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5863,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5863TransformerFanFault,,,,,,The transformer fan has failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5865,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5865NoLoadWarning,,,,,,Indicates the UPS has output voltage but the output current is below a set threshold [No Load Warning Current Threshold] for a set period of time [No Load Warning Delay].
.1.3.6.1.4.1.476.1.42.3.2.7.1.5871,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5871BatteryOverTemperatureLimit,,,,,,A battery temperature sensor is reporting a value above a predetermined limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5873,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5873UnexpectedMainBatteryDisconnectClosure,,,,,,The main battery disconnect has closed unexpectedly.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5874,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5874BatteryOverVoltage,,,,,,The system has detected that the battery voltage has exceeded a predetermined limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5875,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5875BatteryFuseFault,,,,,,One or more battery fuse faults has occurred.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5878,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5878MainBatteryDisconnectForcedToUnlock,,,,,,The main battery disconnect is forced to the unlocked state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5879,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5879VdcBackfeed,,,,,,The voltage between battery and DC bus measurements is out of tolerance.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5880,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5880RectifierConfigurationChangeRequest,,,,,,This event indicates that the battery is not configured and PFC is not enabled.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5881,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5881RegenerationActive,,,,,,Regeneration operation is active.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5882,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5882RegenerationOperationTerminated,,,,,,Regeneration operation is not active.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5883,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5883RegenerationOperationFailure,,,,,,Regeneration operation has been terminated due to bypass source instability or unit misoperation.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5884,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5884ProgramInputContact01,,,,,,When the signal from [Program Input Contact 01] is active the function assigned to this contact is executed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5885,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5885ProgramInputContact02,,,,,,When the signal from [Program Input Contact 02] is active the function assigned to this contact is executed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5886,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5886ProgramInputContact03,,,,,,When the signal from [Program Input Contact 03] is active the function assigned to this contact is executed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5887,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5887ProgramInputContact04,,,,,,When the signal from [Program Input Contact 04] is active the function assigned to this contact is executed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5888,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5888ProgramInputContact05,,,,,,When the signal from [Program Input Contact 05] is active the function assigned to this contact is executed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5889,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5889ProgramInputContact06,,,,,,When the signal from [Program Input Contact 06] is active the function assigned to this contact is executed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5890,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5890ProgramInputContact07,,,,,,When the signal from [Program Input Contact 07] is active the function assigned to this contact is executed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5891,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5891ProgramInputContact08,,,,,,When the signal from [Program Input Contact 08] is active the function assigned to this contact is executed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5892,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5892ProgramInputContact09,,,,,,When the signal from [Program Input Contact 09] is active the function assigned to this contact is executed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5893,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5893ProgramInputContact10,,,,,,When the signal from [Program Input Contact 10] is active the function assigned to this contact is executed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5894,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5894ProgramInputContact11,,,,,,When the signal from [Program Input Contact 11] is active the function assigned to this contact is executed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5895,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5895ProgramInputContact12,,,,,,When the signal from [Program Input Contact 12] is active the function assigned to this contact is executed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5896,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5896GroundFaultDetected,,,,,,The system has detected a ground fault on a Battery-String.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5902,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5902ReturnHumiditySensorIssue,,,,,,The humidity sensor at the inlet of the unit is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5903,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5903CompressorLowDifferentialPressureLockout,,,,,,Compressor exceeded maximum startup attempts due to low differential pressure. Compressor is shutdown and has been disabled.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5906,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5906AirflowSensorIssue,,,,,,Airflow sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5907,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5907ExtAirDamperPositionIssue,,,,,,Air damper position does not match expected value, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5908,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5908ExtPowerSourceAFailure,,,,,,Unit main power source A failure, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5909,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5909ExtPowerSourceBFailure,,,,,,Unit main power source B failure, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5910,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5910StaticPressureSensorOutofRange,,,,,,Static pressure sensor signal is out of its configured range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5911,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5911FluidTemperatureSensorIssue,,,,,,The fluid temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5912,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5912FluidFlowSensorIssue,,,,,,The fluid flow sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5914,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5914OverDifferentialPressure,,,,,,An over differential pressure condition was detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5915,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5915UnderDifferentialPressure,,,,,,An under differential pressure condition was detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5924,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5924MixedModeLockout,,,,,,Mixed mode has been entered too many times over a rolling time period and has been temporarily disabled. Mixed mode is defined as the use of a compressor on one refrigeration circuit and the use of a refrigerant pump on the other circuit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5928,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5928UnbalancedLoadCondition,,,,,,The system has detected a line-to-line unbalanced load condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5939,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5939BranchOverCurrentProtection,,,,,,The Branch Receptacle Module's over current protection is triggered.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5948,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5948BranchLowVoltageLL,,,,,,The system has detected a module under voltage condition (LL).
.1.3.6.1.4.1.476.1.42.3.2.7.1.5957,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5957BypassInputVoltageFault,,,,,,The system has detected the bypass voltage is unqualified.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5958,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5958BatteryTemperatureOutofRange,,,,,,Battery temperature is outside of acceptable range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5960,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5960InverterOverload,,,,,,Inverter in overload fault.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5966,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5966AuxAirTempDeviceCommunicationLost,,,,,,Communication with external auxiliary device providing an air temperature value has been lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5967,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5967ModbusPowerMeterCommunicationLost,,,,,,Communication with Modbus power meter has been lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5968,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5968InverterDesaturation,,,,,,Inverter Desaturation.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5969,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5969GenericDICFault,,,,,,The control board reports a fault - Service required.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5970,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5970GroundFault,,,,,,An AC phase to ground fault or three phase fault to ground exists on the output of the UPS.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5973,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5973InputBreakerOpen,,,,,,The main input breaker is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5974,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5974NeutralBreakerOpen,,,,,,The neutral breaker is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5975,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5975OutputBreakerOpen,,,,,,The output breaker is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5976,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5976MaintenanceBypassBreakerClosed,,,,,,The maintenance bypass breaker is closed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5977,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5977BatteryBreakerOpen,,,,,,The battery circuit is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5978,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5978RectifierIsolationBreakerRFBOpen,,,,,,The rectifier isolation breaker (RFB) indicates that it is in the open position.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5982,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5982BypassBreakerSBBOpen,,,,,,The bypass circuit breaker (SBB) indicates that it is in the open position.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5983,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5983BypassIsolationBreakerBIBOpen,,,,,,The bypass isolation breaker (BIB) indicates that it is in the open position.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5984,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5984BypassUndervoltageWarning,,,,,,The voltage on one or more bypass phases is less than a specified percentage of the nominal voltage.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5985,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5985BypassStaticSwitchBPSSOn,,,,,,The Bypass Static Switch has been turned on.
.1.3.6.1.4.1.476.1.42.3.2.7.1.5998,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId5998BattOvtempWarning,,,,,,A battery temperature sensor is reporting a value above the setpoint.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6009,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6009InverterOutputBreakerOpen,,,,,,The inverter output breaker indicates that it is in the open position.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6011,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6011EquipmentOverTempWarning,,,,,,Equipment over temperature warning is a summary event based on the detection of at least one measured temperature exceeding a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6012,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6012EquipmentOvertemperatureLimit,,,,,,The equipment air temperature has exceeded its maximum set point.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6045,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6045RectifierInputBreakerOpen,,,,,,The rectifier isolation breaker indicates that it is in the open position.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6046,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6046LoadonUPS,,,,,,The output is being supplied power from the inverter.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6047,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6047Core2CoreFuseFailure,,,,,,Core-2-core fuse failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6052,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6052SystemOutputBreakerOpen,,,,,,The system output breaker is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6059,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6059InverterRelayFault,,,,,,The inverter relay has malfunctioned.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6060,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6060TransfertoBypassSystemOverload,,,,,,The UPS System has transferred to bypass because the active power modules cannot support the critical load.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6061,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6061InputSourceBackfeed,,,,,,The battery is backfeeding the input source.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6062,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6062LossofSynchronization,,,,,,The inverter and bypass are no longer synchronized. .
.1.3.6.1.4.1.476.1.42.3.2.7.1.6063,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6063BatteryConverterCurrentLimit,,,,,,The battery converter has reached is maximum current limit. .
.1.3.6.1.4.1.476.1.42.3.2.7.1.6064,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6064LBSCableFailure,,,,,,Load Bus Sync communications is abnormal. A problem with the LBS cable may exist.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6065,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6065BatteryChargeEqualizationTimeout,,,,,,The battery equalizing is time out.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6066,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6066ParallelCableFailure,,,,,,The UPS parallel system communications is abnormal. A problem with the parallel cable may exist.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6067,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6067BatteryFault,,,,,,A short circuit exists in the battery system.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6068,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6068BatteryRoomAlarm,,,,,,The ambient temperature of the battery room is abnormal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6080,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6080UPSCCommunicationFailure,,,,,,The UPSC has failed to communicate in a designated time period.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6092,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6092Compressor1BThermalOverload,,,,,,Fixed compressor 1B is shut down due to thermal overload.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6093,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6093Compressor2BThermalOverload,,,,,,Fixed compressor 2B is shut down due to thermal overload.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6094,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6094Compressor1BHoursExceeded,,,,,,Fixed compressor 1B run hours have exceeded the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6095,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6095Compressor2BHoursExceeded,,,,,,Fixed compressor 2B run hours have exceeded the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6100,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6100CondenserRemoteShutdown,,,,,,Condenser is shut down by a remote signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6105,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6105ExternalCondenserTVSSIssue,,,,,,The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6106,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6106ExternalCondenserVFDIssue,,,,,,The condenser fan Variable Frequency Drive is offline, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6107,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6107ExternalCondenserIssue,,,,,,Condenser is not operating within its operational parameters, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6119,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6119Slotsnotavailable,,,,,,The number of sensors exceeds the number of allocated slots and cannot be displayed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6180,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6180BatteryUnderVoltage,,,,,,Battery voltage is too low.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6182,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6182ReplaceBattery,,,,,,The battery is due for replacement.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6186,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6186InputFrequencyDeviation,,,,,,The input frequency is outside of the normal range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6187,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6187ShutdownPending,,,,,,Shutdown is pending.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6194,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6194SystemRebootCommandIssued,,,,,,Reboot command issued to the system.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6203,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6203SensorAdded,,,,,,Sensor Added.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6204,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6204SensorRemoved,,,,,,Sensor Removed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6205,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6205WaterLeakDetected,,,,,,Water leak detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6210,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6210FirmwareUpdateInProgress,,,,,,Firmware update has started and is in progress.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6211,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6211FirmwareUpdateCompletedSuccessfully,,,,,,Firmware update has completed successfully.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6212,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6212FirmwareUpdateCompletedUnsuccessfully,,,,,,Firmware update has completed, but was not successful.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6216,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6216PrechargeCircuitFailed,,,,,,DC Bus precharge/discharge didn't reach specified level within a specified time.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6217,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6217MemoryCardRemoved,,,,,,The memory card on the control board has been removed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6218,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6218AutoCalibrationActive,,,,,,The system is automatically calibrating ADC channels.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6219,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6219AutoCalibrationFailed,,,,,,ADC channel calibration has failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6220,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6220ModuleOutputBreakerOpen,,,,,,The module output breaker is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6221,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6221NeutralVoltageFault,,,,,,Voltage observed on neutral line.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6222,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6222BranchLoadLoss,,,,,,Loss of load on branch detected. Branch circuit breaker might be open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6225,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6225RemoteSensorLowHumidity,,,,,,Remote sensor humidity has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6226,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6226RemoteSensorHighHumidity,,,,,,Remote sensor humidity has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6227,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6227RemoteSensorAverageLowHumidity,,,,,,The average humidity of multiple remote sensors on the cooling unit has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6228,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6228RemoteSensorAverageHighHumidity,,,,,,The average humidity of multiple remote sensors on the cooling unit has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6229,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6229RemoteSensorSystemAverageLowHumidity,,,,,,The average humidity of multiple remote sensors on interconnected cooling units in a single system has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6230,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6230RemoteSensorSystemAverageHighHumidity,,,,,,The average humidity of multiple remote sensors on interconnected cooling units in a single system has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6231,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6231LowCompressorSuperheat,,,,,,Compressor suction superheat has dropped below a lower threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6232,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6232SECUnspecifiedGeneralEvent,,,,,,One or more unspecified events active for the Superheat and Envelope Controller. See local unit display for further details.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6233,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6233SECCommunicationLost,,,,,,Communication with the Superheat and Envelope Controller has been lost. The event is deactivated when communication is re -established.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6236,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6236PowerSourceAIssue,,,,,,No power is detected at power source input 'A'.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6237,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6237PowerSourceBIssue,,,,,,No power is detected at power source input 'B'.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6239,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6239FluidValveHoursExceeded,,,,,,Operating hours for the fluid valve have exceeded the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6253,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6253BoosterFailure,,,,,,Booster failure - boost is off.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6254,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6254ChargerFailure,,,,,,Charger Failure - Charger is off.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6274,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6274UnitTopReturnAirSensorFailure,,,,,,Return air sensor at the top of the unit is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6275,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6275UnitMiddleReturnAirSensorFailure,,,,,,Return air sensor in the middle of the unit is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6276,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6276UnitBottomReturnAirSensorFailure,,,,,,Return air sensor at the bottom of the unit is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6277,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6277UnitTopSupplyAirSensorFailure,,,,,,Supply air sensor at the top of the unit is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6278,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6278UnitMiddleFirstSupplyAirSensorFailure,,,,,,First supply air sensor in the middle of the unit is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6279,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6279UnitBottomSupplyAirSensorFailure,,,,,,Supply air sensor at the bottom of the unit is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6284,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6284UnitMiddleSecondSupplyAirSensorFailure,,,,,,Second supply air sensor in the middle of the unit is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6293,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6293ChilledWaterControlActive,,,,,,Chilled water inlet temperature control function is enabled due to 'bad' water.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6294,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6294ChilledWaterFlowTransducerFailure,,,,,,Chilled water flow transducer is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6295,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6295ChilledWaterInletTemperatureSensorFailure,,,,,,Chilled water inlet temperature sensor is disconnected or the signal is out of range. The sensor is mandatory for the chilled water flow function.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6296,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6296ChilledWaterHighInletTemperature,,,,,,Chilled water inlet temperature has exceeded an upper threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6297,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6297Modbus010VModuleCommunicationFailure,,,,,,Modbus 0-10V module for managing the second Chilled Water circuit valve is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6299,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6299RackDoorsOpen,,,,,,Rack doors opened due to supply air temperature exceeding the [Rack Door Open High Supply Air Temperature Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.6303,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6303TeamStaticPressureSensorFailure,,,,,,The team static pressure sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6304,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6304HeatingLockout,,,,,,Heating is shut down and disabled.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6305,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6305FreeCoolingStoppedHighRoomTemp,,,,,,Free cooling is temporarily disabled due to room temperature exceeding a preset delta above the the set point.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6306,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailure,,,,,,Cold aisle team sensor measuring air temperature and humidity is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6309,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6309ColdAisleAirSensorFailure,,,,,,Cold aisle sensor measuring air temperature and humidity is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6310,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6310ChilledWaterInletTemperatureControlActive,,,,,,Chilled water inlet temperature control is active.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6313,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6313ChilledWaterInletTemperatureSensorFailure,,,,,,Chilled water inlet temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6314,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6314ChilledWaterOutletTemperatureSensorFailure,,,,,,Chilled water outlet temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6315,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6315ChilledWaterFlowMeterSensorFailure,,,,,,Chilled water flow meter sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6333,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6333Bypassoutofsync,,,,,,Bypass and Inverter inputs are not in sync.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6348,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6348SystemOutputoffasrequested,,,,,,The UPS has shutdown as requested, i.e., the output is off.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6349,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6349SystemOffasrequested,,,,,,The entire UPS has shutdown as commanded.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6350,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6350GeneralFault,,,,,,A general fault in the UPS has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6351,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6351UPSAwaitingPower,,,,,,The UPS output is off and the UPS is awaiting the return of input power.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6352,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6352AutonomyCalibration,,,,,,Calibration test occurred.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6353,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6353GeneralWarning,,,,,,A warning in the UPS has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6354,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6354BatteryCharging,,,,,,The UPS battery is charging (battery charge percentage lower than 98).
.1.3.6.1.4.1.476.1.42.3.2.7.1.6355,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6355BackfeedRelayFailure,,,,,,Bypass SCR is wrongly on or commutated.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6356,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6356BatteryCircuitOpen,,,,,,Battery Circuit Open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6357,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6357SystemRestartPending,,,,,,A request for UPS restart has been received.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6358,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6358PipeTemperatureSensorFailure,,,,,,Air temperature sensor located in the pipe is not sending a valid value.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6362,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6362SFAReservedEvent26,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6363,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6363SFAReservedEvent27,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6364,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6364SFAReservedEvent28,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6365,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6365SFAReservedEvent29,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6366,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6366SFAReservedEvent30,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6367,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6367SFAReservedEvent31,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6368,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6368SFAReservedEvent32,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6369,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6369SFAReservedEvent33,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6370,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6370SFAReservedEvent34,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6371,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6371SFAReservedEvent35,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6372,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6372SFAReservedEvent36,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6373,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6373SFAReservedEvent37,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6374,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6374SFAReservedEvent38,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6375,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6375SFAReservedEvent39,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6376,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6376SFAReservedEvent40,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6377,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6377SFAReservedEvent41,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6378,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6378SFAReservedEvent42,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6379,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6379SFAReservedEvent43,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6380,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6380SFAReservedEvent44,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6381,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6381SFAReservedEvent45,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6382,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6382SFAReservedEvent46,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6383,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6383SFAReservedEvent47,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6384,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6384SFAReservedEvent48,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6385,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6385SFAReservedEvent49,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6386,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6386SFAReservedEvent50,,,,,,Reserved event for SFA use.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6438,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6438PowerModuleInputCurrentAbnormal,,,,,,Input current of the power module is abnormal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6439,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6439PowerModuleBalancerofDCBusFailure,,,,,,Balancer of DC Bus in the power module has failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6440,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6440PowerModuleFuseFailure,,,,,,A summary event indicating one or more fuse failures in the power module.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6441,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6441PowerModulePowerSupplyFailure,,,,,,Power module power supply failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6450,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6450PDUPoweredOn,,,,,,The PDU was powered on.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6453,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6453InputWiringFault,,,,,,The neutral/ground conductors on the input wiring are not properly bonded, or the line/neutral conductors have been swapped.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6454,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6454DCtoDCConverterFault,,,,,,A failure has occurred in the battery discharge circuit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6455,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6455LeakSensorCableFault,,,,,,A fault is detected in the 'Leak Sensor' cable.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6464,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6464RebootMonitoringAgent,,,,,,Request from managed device to reboot the monitoring agent.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6474,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6474SaveIPv4SettingstoAgent,,,,,,Request from managed device for the monitoring agent to save/set IPv4 settings.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6488,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6488SaveIPv6SettingstoAgent,,,,,,Request from managed device for the monitoring agent to save/set IPv6 settings.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6508,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6508SaveLIFETMSettingstoAgent,,,,,,Request from managed device for the monitoring agent to save/set LIFE (TM) settings.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6518,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6518StandbyUnitActivatedDuetoChillerFailure,,,,,,External chiller unit has failed for this unit, so the standby cooling unit has been activated.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6522,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6522PDUResidualOverCurrent,,,,,,The system has detected a PDU residual over current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6527,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6527PDUOverCurrentProtection,,,,,,The PDU over current protection is triggered.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6528,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6528PowerModuleLeverUnlocked,,,,,,The power module is inactive because the lever is in the unlocked position.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6529,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6529HardwareMismatch,,,,,,The assigned system model settings do not match the actual installed hardware. The module count is wrong, or a module of the wrong type is installed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6530,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6530SupplyNTCAirSensorIssue,,,,,,The supply NTC air sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6531,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6531ExternalAirSensorCIssue,,,,,,The external air sensor C is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6532,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6532ExternalAirSensorDIssue,,,,,,The external air sensor D is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6533,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6533ExternalAirSensorEIssue,,,,,,The external air sensor E is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6534,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6534PumpThermalOverload,,,,,,Pump is shut down due to thermal overload.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6535,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6535XDModuleCommunicationLost,,,,,,Communication with XD Module has been lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6536,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6536MMSCapacityExceeded,,,,,,The critical load is larger than the redundant rating of a 1+N redundant multi-module system.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6538,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6538TSAControlInputIssue,,,,,,The analog input used to set the air temperature set point for cooling control is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6539,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6539ChilledWaterValveHoursExceeded,,,,,,[Chilled Water Valve Hours] has exceeded [Chilled Water Valve Operating Hours Threshold].
.1.3.6.1.4.1.476.1.42.3.2.7.1.6540,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6540FSAControlInputIssue,,,,,,The analog input used to set the air temperature set point for fan speed control is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6541,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6541AutoTuneLicenseExpiring,,,,,,License for the AutoTune feature has not been refreshed in 30 days and will be expiring soon.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6542,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6542AutoTuneLicenseExpired,,,,,,License for the AutoTune feature has expired.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6543,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6543UnitInStandbyDueToCoolingLoss,,,,,,Unit forced into standby because it is unable to provide any cooling.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6544,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6544ControlUnitsRemoteShutdownMismatch,,,,,,The remote shutdown status of the primary control unit does not match the remote shutdown status of the secondary control unit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6545,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6545SecondaryControlUnitCommunicationLost,,,,,,The primary control unit has lost Ethernet communications with the secondary control unit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6546,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6546ControlUnitsUnitCodeMismatch,,,,,,Unit codes for the primary and secondary control units do not match.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6547,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6547SSAControlInputIssue,,,,,,The analog input used to set the static pressure set point for fan speed control is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6587,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6587TransferCountCleared,,,,,,A system event indicating the transfer count has been cleared.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6588,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6588EnergyCounterCleared,,,,,,A system event indicating the energy counter (e.g. KWH) has been cleared.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6589,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6589HistoryLogsFull,,,,,,The history logs are full.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6590,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6590HistoryLogsCleared,,,,,,History logs have been cleared.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6591,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6591EventLogCleared,,,,,,All past alarms and faults have been cleared.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6592,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6592SystemDateChanged,,,,,,The system date has been updated.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6593,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6593SystemTimeChanged,,,,,,The system time has been updated.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6594,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6594AccessPasswordChanged,,,,,,The access password has been changed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6595,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6595ConfigModified,,,,,,A setpoint has been updated.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6612,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6612SCRShort,,,,,,The SCR is in a short condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6613,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6613SCROpen,,,,,,The SCR is in an open condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6614,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6614ACPowerSupplyFail,,,,,,A failure of the AC Power Supply has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6615,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6615DCPowerSupplyFail,,,,,,A failure of the DC Power Supply has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6616,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6616VoltageSensorFail,,,,,,A voltage sensor failure has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6617,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6617SCRSensorFail,,,,,,The SCR sensor module failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6618,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6618CurrentSensorFail,,,,,,The current sensor module failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6619,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6619GateDriveFail,,,,,,The Gate Drive module failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6620,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6620SurgeFail,,,,,,The surge module failed for the input source.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6621,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6621FastUnderVoltage,,,,,,Fast under voltage detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6622,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6622SlowUnderVoltage,,,,,,Slow under voltage detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6623,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6623OverVoltage,,,,,,Over voltage detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6624,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6624OverUnderFrequencyFail,,,,,,An over or under frequency condition has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6625,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6625GeneralSourceFailure,,,,,,A non-specific failure has been detected in the source.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6626,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6626OverCurrent,,,,,,An over current has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6627,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6627PeakCurrentOffLimit,,,,,,The peak current has exceeded the setpoint defined by I-PK Xfer Lockout.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6628,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6628SyncFail,,,,,,A phase rotation/out of synchronization failure has been detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6629,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6629InputOverVoltage,,,,,,Input over voltage.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6630,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6630InputUnderVoltage,,,,,,Input under voltage.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6631,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6631InputOverUnderFrequency,,,,,,Input over/under frequency.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6635,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6635VoltageSenseFail,,,,,,Output voltage sense failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6636,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6636LoadonAlternateSource,,,,,,The load is on the alternate source.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6637,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6637UnderVoltageFail,,,,,,Output under voltage failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6638,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6638OutputOverCurrent,,,,,,Output is over current.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6639,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6639GroundOverCurrent,,,,,,Ground is over current.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6640,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6640NeutralOverCurrent,,,,,,Neutral is over current.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6641,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6641LoadVoltageTHD,,,,,,Load voltage THD has exceeded the set limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6662,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6662ControlLogicFail,,,,,,A control logic module has failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6663,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6663PowerSupplyLogicFail,,,,,,A power supply module has failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6664,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6664ExternalCommsFailure,,,,,,External communications failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6665,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6665HeatSinkOverTemp,,,,,,The system heat sink temperature has exceeded design limits.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6666,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6666AutomaticTransferInhibited,,,,,,Automatic transfer is inhibited.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6667,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6667InputSourceTransferInhibited,,,,,,Input source transfer is inhibited.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6676,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6676CB1ShuntTrip,,,,,,CB1 Shunt Trip event.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6677,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6677CB2ShuntTrip,,,,,,CB2 Shunt Trip event.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6678,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6678CB6NeutralOpen,,,,,,CB6 neutral open event.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6679,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6679ContactorNeutralFail,,,,,,Contactor Neutral Fail event.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6680,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6680CB1BreakerOpen,,,,,,CB1 Breaker open event. Normal state is breaker closed. Latched state is breaker open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6681,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6681CB2BreakerOpen,,,,,,CB2 Breaker open event. Normal state is breaker closed. Latched state is breaker open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6682,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6682CB4BreakerClosed,,,,,,CB4 breaker closed event. Normal state is breaker open. Latched state is breaker closed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6683,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6683CB5BreakerClosed,,,,,,CB5 breaker closed event. Normal state is breaker open. Latched state is breaker closed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6684,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6684CB3BreakerOpen,,,,,,CB3 breaker open event. Normal state is breaker closed. Latched state is breaker open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6685,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6685CB3ABreakerOpen,,,,,,CB3A breaker open event. Normal state is breaker closed. Latched state is breaker open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6686,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6686CB6BreakerOpen,,,,,,CB6 breaker open event. Normal state is breaker closed. Latched state is breaker open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6687,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6687CB7BreakerOpen,,,,,,CB7 breaker open event. Normal state is breaker closed. Latched state is breaker open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6691,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6691GroupIndependentOn,,,,,,The group standby/cascade state for this unit has been overridden. The unit has been forced on.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6692,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6692GroupIndependentOff,,,,,,The group standby/cascade state for this unit has been overridden. The unit has been forced off.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6693,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6693BranchResidualOverCurrent,,,,,,The system has detected a branch residual over current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6694,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6694ReceptacleResidualOverCurrent,,,,,,The system has detected a receptacle residual over current condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6728,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6728BuckOn,,,,,,The input voltage is currently being bucked (lowered) by the inverter.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6729,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6729BoostOn,,,,,,The input voltage is currently being boosted (raised) by the inverter.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6739,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6739Compressor1HighPressure,,,,,,Compressor 1 High Pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6740,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6740Compressor2HighPressure,,,,,,Compressor 2 High Pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6741,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6741Compressor1ThermalOverload,,,,,,Compressor 1 Thermal Overload.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6742,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6742Compressor2ThermalOverload,,,,,,Compressor 2 Thermal Overload.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6758,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6758CompressorFreezeProtection,,,,,,Compressor has entered the freeze protection phase.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6773,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6773FanTemperatureCompensationLimitReached,,,,,,Unit is configured for fan temperature compensation, and the fan control set point cannot be reduced any further due to high remote air temperature sensor readings.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6774,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6774ModbusECFanCommunicationLost,,,,,,Communication with Modbus EC fan has been lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6785,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6785AnalogTemperatureControlIssue,,,,,,Analog input used for creating the control temperature (instead of reading a sensor) is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6786,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6786SubgroupFirmwareUpdateRequired,,,,,,Mismatch of subgroup firmware. Both the primary and secondary control boards must be running the same firmware version.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6787,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6787SubgroupSecondaryControlUnitIssue,,,,,,Subgroup secondary control unit is reporting an unspecified issue.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6788,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6788EEVCommunicationLost,,,,,,Communication with Electronic Expansion Valve unit has been lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6789,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6789EEVMotorIssue,,,,,,Electronic Expansion Valve stepper motor issue.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6790,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6790EEVFeedbackIssue,,,,,,Electronic Expansion Valve feedback error.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6791,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6791EEVPressureSensorIssue,,,,,,Electronic Expansion Valve refrigerant pressure sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6792,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6792EEVCoilTemperatureSensorIssue,,,,,,Electronic Expansion Valve coil temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6793,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6793EEVDischargeTemperatureSensorIssue,,,,,,Electronic Expansion Valve discharge temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6794,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6794EEVSumpTemperatureSensorIssue,,,,,,Electronic Expansion Valve sump temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6795,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6795EEVBatteryTestIssue,,,,,,Electronic Expansion Valve battery state cannot be determined.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6796,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6796EEVBatteryPersistentIssue,,,,,,Electronic Expansion Valve has continuously detected a 'bad' battery condition for an extended period of time.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6798,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6798PumpCycleLockOut,,,,,,Pump is locked out due to multiple pump-to-compressor transitions at cold ambient air temperature.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6799,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6799PumpBoardFirmwareUpdateRequired,,,,,,Mismatch of pump board firmware. All pump boards must be running the same firmware version.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6800,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6800PumpControlBoardIssue,,,,,,Pump is shut down due to a pump control board issue. Control board must be rebooted.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6801,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6801PumpInvalidDataShutdown,,,,,,Pump is shut down due to invalid data.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6802,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6802PumpInputPressureSensorIssue,,,,,,Pump input refrigerant pressure sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6803,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6803PumpInputTemperatureSensorIssue,,,,,,Pump input refrigerant temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6804,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6804PumpOutputPressureSensorIssue,,,,,,Pump output refrigerant pressure sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6805,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6805PumpOutputTemperatureSensorIssue,,,,,,Pump output refrigerant temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6806,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6806PumpCommunicationLost,,,,,,Communication with pump unit has been lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6807,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6807PumpRemoteShutdown,,,,,,Pump is shut down by a remote signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6808,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6808PumpUSBEthernetPortIssue,,,,,,Pump control board USB or Ethernet interface has failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6809,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6809PumpStartupFailure,,,,,,Multiple attempts to start the pump have failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6810,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6810PumpInverterFailure,,,,,,Pump inverter is reporting a failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6811,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6811PumpTVSSIssue,,,,,,Pump Transient Voltage Surge Suppressor or Surge Protection Device has failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6812,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6812PumpHighSuperheat,,,,,,Pump inlet refrigerant superheat temperature is too high, or the pump has been running too long with the condenser fan off.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6813,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6813CondenserHighAmbientAirTempDelta,,,,,,The difference between condenser measured ambient air temperatures has been too large for an extended period of time.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6814,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6814CondenserLeeTempOptionMismatch,,,,,,Lee-Temp option configured at a condenser unit does not match Lee -Temp option configured at the control unit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6815,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6815CondenserBoardFirmwareUpdateRequired,,,,,,Mismatch of condenser board firmware. All condenser boards must be running the same firmware version.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6816,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6816CondenserToPumpHighRefrigerantTempDelta,,,,,,Temperature delta between the condenser output refrigerant and pump inlet refrigerant is too large.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6817,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6817CondenserRefrigerantTypeMismatch,,,,,,Refrigerant type configured at condenser unit does not match refrigerant type configured at the control unit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6818,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6818ExternalSupplyFluidHighTemperature,,,,,,Supply fluid temperature has exceeded a threshold, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6819,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6819ExternalSupplyFluidTempSensorIssue,,,,,,Supply fluid temperature sensor is disconnected or the signal is out of range, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6822,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6822AuditLogUpdate,,,,,,Audit log has been updated.
.1.3.6.1.4.1.476.1.42.3.2.7.1.6824,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId6824ExternalSupplyFluidFlowIssue,,,,,,Supply fluid flow issue, as indicated by an external input signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7163,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7163ModbusAutomaticTransferSwitchCommunicationLost,,,,,,Communications with Modbus Automatic Transfer Switch has been lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7164,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7164BatteryDeepDischarge,,,,,,UPS depleted the batteries to the end of discharge(EOD) voltage.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7461,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7461BatteryBreakerOpenFailure,,,,,,Battery circuit breaker failed to open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7464,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7464LithiumIonBatterySystemAbnormal,,,,,,Lithium-Ion Battery System Abnormal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7465,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7465LithiumIonBatterySystemDisconnectRequest,,,,,,A request to disconnect the Lithium-Ion battery system was received.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7467,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7467ThermalMarginWarning,,,,,,The thermal margin has dropped below the threshold value.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7474,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7474FlowSensorFailure,,,,,,Fluid flow sensor failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7475,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7475CheckWaterSystem,,,,,,Fluid check water system.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7476,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7476PumpOperatingWithoutFlow,,,,,,Fluid pump operation with no flow.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7483,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7483PumpInverterFailure,,,,,,Fluid pump inverter failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7484,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7484PumpFlowFailure,,,,,,Fluid pump flow failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7485,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7485BatteryCircuitBreakerOpen,,,,,,Battery circuit breaker is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7486,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7486LithiumIonBatterySystemCommunicationAbnormal,,,,,,Lithium-Ion Battery System Communication Abnormal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7487,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7487LithiumIonBatterySystemWarning,,,,,,The Lithium-Ion Battery system has one or more warnings.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7488,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7488LithiumIonBatterySystemFault,,,,,,The Lithium-Ion Battery system has one or more faults.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7489,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7489LowSupplyAirHumidity,,,,,,Supply air humidity has dropped below a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7490,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7490HighSupplyAirHumidity,,,,,,Supply air humidity has exceeded a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7491,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7491LowRemoteAirHumidity,,,,,,Remote air humidity has dropped below a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7492,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7492HighRemoteAirHumidity,,,,,,Remote air humidity has exceeded a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7493,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7493SupplyHumiditySensorIssue,,,,,,The humidity sensor at the outlet of the unit is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7494,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7494ExternalHumiditySensorIssue,,,,,,The external humidity sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7495,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7495ExternalAirSensorIssue,,,,,,The external air sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7496,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7496CompressorDriverFailureLockout,,,,,,Compressor lockout occurred due to multiple failures of the compressor driver board.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7497,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7497CompressorDriverFailure,,,,,,Compressor driver board failure detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7498,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7498CompressorDriverCommunicationFailureLockout,,,,,,Compressor lockout occurred due to multiple communication failures with the compressor driver board.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7499,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7499CompressorPressureDifferenceLockout,,,,,,Compressor lockout occurred due to multiple compressor pressure differences.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7500,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7500CompressorDriverCommunicationFailure,,,,,,A communication failure occurred with the compressor driver board.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7501,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7501CompressorPressureDifference,,,,,,Compressor pressure difference is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7503,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7503ElectricalHeaterFailure,,,,,,The electric heater temperature exceeded a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7504,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7504WaterValveFailure,,,,,,There is an issue with the chilled water valve.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7506,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7506SupplyFluidLowFlow,,,,,,Supply fluid flow has dropped below a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7507,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7507InletFluidLowPressure,,,,,,Inlet fluid pressure has dropped below a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7508,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7508InletFluidHighPressure,,,,,,Inlet fluid pressure has exceeded a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7509,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7509OutletFluidUnderTemp,,,,,,Outlet fluid temperature has dropped below a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7510,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7510OutletFluidOverTemp,,,,,,Outlet fluid temperature has exceeded a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7511,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7511InletFluidOverTemp,,,,,,Inlet fluid temperature has exceeded a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7512,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7512InletFluidUnderTemp,,,,,,Inlet fluid temperature has dropped below a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7515,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7515FanDetectionBoardCommunicationFailure,,,,,,Communication with the fan detection board has failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7518,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7518SurgeProtectionDeviceAlarm,,,,,,Surge Protection Device Alarm.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7519,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7519PowerOppositePhase,,,,,,The power input phases are incorrectly connected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7520,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7520PowerLossOfPhase,,,,,,One of the input phases has been lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7522,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7522LossofAirflow,,,,,,Loss of airflow detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7523,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7523TeamworkMasterisofflineornotconnectedtothenetwork,,,,,,Loss of Teamwork Master.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7524,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7524LossofTeamworkSlave,,,,,,Teamwork Slave is offline or not connected to the network.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7525,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7525RepeatedTeamworkAddress,,,,,,The network address of two or more units in a teamwork are the same.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7526,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7526AirDamperFailure,,,,,,There is an issue with the air damper.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7537,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7537FilterMaintenanceDue,,,,,,The operating hours of the filter has exceeded the threshold and needs to be maintained or replaced.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7538,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7538HeaterMaintenanceDue,,,,,,The operating hours of the heater has exceeded the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7539,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7539HighCompressorPressure,,,,,,Compressor pressure has exceeded a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7540,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7540HighCompressorPresssureLockout,,,,,,Compressor lockout occurred due to high compressor pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7541,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7541LowCompressorPressure,,,,,,Compressor pressure has dropped below a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7542,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7542LowCompressorPressureLockout,,,,,,Compressor lockout occurred due to low compressor pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7543,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7543HighCompressorDischargeTemperature,,,,,,Compressor discharge temperature has exceeded a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7544,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7544HighCompressorDischargeTemperatureLockout,,,,,,Compressor Lockout occurred due to high compressor discharge temperature.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7545,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7545LowCompressorDischargeTemperature,,,,,,Compressor discharge temperature has dropped below a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7546,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7546LowCompressorDischargeTemperatureLockout,,,,,,Compressor lockout occurred due to low compressor discharge temperature.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7547,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7547LowCompressorDischargeSuperheat,,,,,,Compressor discharge superheat has dropped below a threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7548,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7548LowCompressorDischargeSuperheatLockout,,,,,,Compressor lockout occurred due to low compressor discharge superheat temperature.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7549,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7549HighCompressorPressureAbnormal,,,,,,Compressor pressure has exceeded a normal threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7550,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7550LowCompressorPressureAbnormal,,,,,,Compressor pressure has dropped below a normal threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7551,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7551EEVDriverCommunicationFailure,,,,,,A communication failure occurred with the EEV driver board.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7552,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7552EEVDriverFailure,,,,,,EEV driver board failure detected.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7553,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7553HighCompressorPressureSensorFailure,,,,,,High compressor pressure sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7554,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7554LowCompressorPressureSensorFailure,,,,,,Low compressor pressure sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7555,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7555LowCompressorPressureSensorFailureLockout,,,,,,Compressor lockout occurred due to low compressor pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7556,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7556CompressorDischargeTemperatureSensorFailure,,,,,,Compressor discharge temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7557,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7557CompressorSuctionTemperatureSensorFailure,,,,,,Compressor suction temperature sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7558,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7558WaterFlowSensorFailure,,,,,,Water flow sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7559,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7559LossofAirflowSensorFailure,,,,,,Airflow sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7560,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7560FilterPressureDifferenceSensorFailure,,,,,,Filter pressure difference sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7561,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7561CustomAlarm,,,,,,Custom Alarm.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7562,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7562WaterPressureSensorFailure,,,,,,Water pressure sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7563,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7563FanStaticPressureSensorFailure,,,,,,Fan static pressure sensor is disconnected or the signal is out of range.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7568,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7568SystemShutdownEPO,,,,,,Unit shutdown by Emergency Power Off (EPO) switch.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7569,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7569SystemShutdownUndervoltage,,,,,,System shutdown due to an undervoltage condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7570,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7570TransformerHighTemperature,,,,,,The transformer crossed the high temperature threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7571,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7571TransformerTemperatureSensorFailure,,,,,,The transformer temperature sensor is reporting an invalid state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7572,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7572MeteringBoardCommunicationFail,,,,,,The metering board(s) reported a communication failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7573,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7573AccessoryBoardCommunicationFail,,,,,,The accessory board(s) reported a communication failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7574,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7574SystemMisconfiguration,,,,,,The system reported a misconfiguration.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7575,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7575SystemFirmwareIncompatibility,,,,,,The system reported a firmware incompatibility.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7576,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7576MainInputBreaker1Tripped,,,,,,The main input circuit breaker 1 reported a tripped state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7577,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7577MainInputBreaker1AccessoryError,,,,,,The main input circuit breaker 1 reported an invalid state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7578,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7578MainInputBreaker1OpenFail,,,,,,The main input circuit breaker 1 failed to open as commanded.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7579,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7579MainInputBreaker2Tripped,,,,,,The main input circuit breaker 2 reported a tripped state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7580,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7580MainInputBreaker2AccessoryError,,,,,,The main input circuit breaker 2 reported an invalid state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7581,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7581MainInputBreaker2OpenFail,,,,,,The main input circuit breaker 2 failed to open as commanded.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7588,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7588LossofCommunication,,,,,,The system board has stopped communicating.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7589,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7589NoInitialCommunication,,,,,,The system board has not established initial communications.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7590,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7590Misconfiguration,,,,,,The system board is misconfigured.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7591,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7591FirmwareIncompatibility,,,,,,The system board firmware is incompatible with the other components.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7697,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7697OutputOvervoltage,,,,,,The output voltage crossed above the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7698,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7698OutputUndervoltage,,,,,,The output voltage crossed below the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7699,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7699PhaseOvercurrent,,,,,,The phase current crossed above the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7700,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7700NeutralOvercurrent,,,,,,The neutral current crossed above the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7701,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7701GroundOvercurrent,,,,,,The ground current crossed above the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7702,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7702OutputFrequencyDeviation,,,,,,The output frequency deviated beyond the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7703,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7703EnergyMeasurementRollover,,,,,,The total accumulated energy value reached its limit and was reset to zero.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7704,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7704Input1Overvoltage,,,,,,The voltage crossed above the threshold of input 1.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7705,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7705Input1Undervoltage,,,,,,The voltage crossed below the threshold of input 1 .
.1.3.6.1.4.1.476.1.42.3.2.7.1.7706,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7706Input1PhaseLoss,,,,,,The voltage of one or more phases dropped below the threshold of input 1.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7707,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7707Input1InvalidPhaseRotation,,,,,,The phases are not in the expected sequence for input 1.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7708,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7708Input1FrequencyDeviation,,,,,,The frequency deviated beyond the threshold of input 1.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7709,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7709Input1HighVoltageTHD,,,,,,The voltage total harmonic distortion crossed above the threshold of input 1.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7710,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7710Input2Overvoltage,,,,,,The voltage crossed above the threshold of input 2.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7711,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7711Input2Undervoltage,,,,,,The voltage crossed below the threshold of input 2.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7712,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7712Input2PhaseLoss,,,,,,The voltage of one or more phases dropped below the threshold of input 2.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7713,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7713Input2InvalidPhaseRotation,,,,,,The phases are not in the expected sequence for input 2.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7714,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7714Input2FrequencyDeviation,,,,,,The frequency deviated beyond the threshold of input 2.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7715,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7715Input2HighVoltageTHD,,,,,,The voltage total harmonic distortion crossed above the threshold of input 2.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7792,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7792PanelboardPhaseOvercurrent,,,,,,The phase current crossed above the threshold of the panelboard.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7793,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7793PanelboardNeutralOvercurrent,,,,,,The neutral current crossed above the threshold of the panelboard.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7794,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7794PanelboardGroundOvercurrent,,,,,,The ground current crossed above the threshold of the panelboard.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7795,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7795PanelboardMainBreakerTripped,,,,,,The main panelboard circuit breaker reported a tripped state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7796,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7796PanelboardMainBreakerAccessoryError,,,,,,The main panelboard circuit breaker reported an invalid state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7797,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7797PanelboardEnergyMeasurementRollover,,,,,,The total accumulated energy value of the panelboard reached its limit and was reset to zero.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7822,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7822BranchPhaseOvercurrent,,,,,,The phase current crossed above the threshold of the branch.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7823,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7823BranchPhaseUndercurrent,,,,,,The phase current crossed below the threshold of the branch.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7824,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7824BranchEnergyMeasurementRollover,,,,,,The total accumulated energy value of the branch reached its limit and was reset to zero.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7896,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7896PanelboardPhaseOvercurrent,,,,,,The phase current crossed above the threshold of the panelboard.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7897,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7897PanelboardNeutralOvercurrent,,,,,,The neutral current crossed above the threshold of the panelboard.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7898,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7898PanelboardGroundOvercurrent,,,,,,The ground current crossed above the threshold of the panelboard.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7899,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7899PanelboardMainBreakerTripped,,,,,,The main panelboard circuit breaker reported a tripped state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7900,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7900PanelboardMainBreakerAccessoryError,,,,,,The main panelboard circuit breaker reported an invalid state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7901,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7901PanelboardEnergyMeasurementRollover,,,,,,The total accumulated energy value of the panelboard reached its limit and was reset to zero.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7953,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7953SubfeedPhaseOvercurrent,,,,,,The phase current crossed above the threshold of the subfeed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7954,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7954SubfeedNeutralOvercurrent,,,,,,The neutral current crossed above the threshold of the subfeed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7955,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7955SubfeedGroundOvercurrent,,,,,,The ground current crossed above the threshold of the subfeed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7956,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7956SubfeedBreakerTripped,,,,,,The subfeed circuit breaker reported a tripped state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7957,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7957SubfeedBreakerAccessoryError,,,,,,The subfeed circuit breaker reported an invalid state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.7958,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId7958SubfeedEnergyMeasurementRollover,,,,,,The total accumulated energy value reached its limit and was reset to zero.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8029,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8029SubfeedPhaseOvercurrent,,,,,,The phase current crossed above the threshold of the subfeed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8030,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8030SubfeedNeutralOvercurrent,,,,,,The neutral current crossed above the threshold of the subfeed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8031,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8031SubfeedGroundOvercurrent,,,,,,The ground current crossed above the threshold of the subfeed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8032,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8032SubfeedBreakerTripped,,,,,,The subfeed circuit breaker reported a tripped state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8033,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8033SubfeedBreakerAccessoryError,,,,,,The subfeed circuit breaker reported an invalid state.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8034,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8034SubfeedEnergyMeasurementRollover,,,,,,The total accumulated energy value reached its limit and was reset to zero.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8045,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8045ExternalInputContactState,,,,,,The state of the external input contact.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8047,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8047InternalInputContactState,,,,,,The state of the internal input contact.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8051,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8051CompressorDriveFailureU00,,,,,,Compressor Drive Failure U00.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8052,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8052CompressorDriveFailureU01,,,,,,Compressor Drive Failure U01.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8053,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8053CompressorDriveFailureU02,,,,,,Compressor Drive Failure U02.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8054,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8054CompressorDriveFailureU03,,,,,,Compressor Drive Failure U03.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8055,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8055CompressorDriveFailureU04,,,,,,Compressor Drive Failure U04.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8056,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8056CompressorDriveFailureU05,,,,,,Compressor Drive Failure U05.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8057,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8057CompressorDriveFailureU06,,,,,,Compressor Drive Failure U06.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8058,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8058CompressorDriveFailureU07,,,,,,Compressor Drive Failure U07.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8059,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8059CompressorDriveFailureU08,,,,,,Compressor Drive Failure U08.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8060,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8060CompressorDriveFailureU09,,,,,,Compressor Drive Failure U09.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8061,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8061CompressorDriveFailureU10,,,,,,Compressor Drive Failure U10.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8062,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8062CompressorDriveFailureU11,,,,,,Compressor Drive Failure U11.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8063,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8063CompressorDriveFailureU12,,,,,,Compressor Drive Failure U12.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8064,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8064CompressorDriveFailureU13,,,,,,Compressor Drive Failure U13.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8065,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8065CompressorDriveFailureU14,,,,,,Compressor Drive Failure U14.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8066,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8066CompressorDriveFailureU15,,,,,,Compressor Drive Failure U15.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8067,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8067EEVDriverUnselectRefrigerant,,,,,,EEV Driver Unselect Refrigerant.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8068,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8068CompressorDriveHeatsinkHighTemperature,,,,,,Compressor Drive Heatsink High Temperature.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8069,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8069CompressorDriveOverCurrent,,,,,,Compressor Drive Over Current.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8070,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8070CompressorDrivePhaseLoss,,,,,,Compressor Drive Phase Loss.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8071,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8071CompressorDriveDCPowerAbnormal,,,,,,Compressor Drive DC Power Abnormal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8072,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId807210DISensorCommunicationFail,,,,,,10DI Sensor Communication Fail.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8073,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8073SystemLackOfRefrigerant,,,,,,System Lack Of Refrigerant.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8075,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8075ValveCommunicationsFailure,,,,,,A valve is configured to exist but communications cannot be established.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8076,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8076ValveIssue,,,,,,Valve is reporting abnormal operating condition.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8083,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8083CondensatePumpFailure,,,,,,Condensate Pump Failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8096,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8096BypasscontrollingtheSCRautonomously,,,,,,The bypass is controlling the SCR autonomously because not all inverters are online.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8098,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8098PowerModuleCommunicationstatus,,,,,,The control has detected a power module communication failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8100,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8100ECOmodeInhibited,,,,,,ECO mode is inhibited due to an external inhibit signal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8105,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8105SupplyFanCommunicationLost,,,,,,Communications with Supply Fan has been lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8119,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8119CommunicationBusError,,,,,,The system board is experiencing an abnormal number of communication errors.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8120,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8120ExternalBatteryCabinetRemoved,,,,,,One or more external battery cabinets have been removed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8125,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8125InternalBatteryBreakerOpen,,,,,,The internal battery breaker is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8126,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8126AllChargersShutdown,,,,,,All chargers in system are shut down to avoid incompatibility in external charger application, or to avoid over-charging in Lithium-ion battery application.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8127,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8127SpecificChargerShutdown,,,,,,The charger in this power module is shut down to detect battery connection status or to avoid Lithium-ion battery over-charging.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8166,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8166BIBBatteryBreakerPowerSupplyFailure,,,,,,Battery Interface Board power supply has failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8170,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8170XDPumpCommunicationLost,,,,,,Communications with XD Pump has been lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8178,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8178EmergencyCooling,,,,,,Emergency Cooling.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8179,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8179BatteryManagementSystemPowerSupplyFailure,,,,,,The battery management system has reported a power supply failure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8180,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8180SupplyFluidLowTemp,,,,,,[Supply Fluid Temperature] below Supply Fluid Low Temp Threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8181,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8181ReturnFluidLowTemp,,,,,,[Return Fluid Temperature] below Return Fluid Low Temp Threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8182,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8182FluidHighDifferentialPressure,,,,,,Fluid Loop High Differential Pressure (Supply - Return).
.1.3.6.1.4.1.476.1.42.3.2.7.1.8183,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8183FluidLowDifferentialPressure,,,,,,Fluid Loop Low Differential Pressure (Supply - Return).
.1.3.6.1.4.1.476.1.42.3.2.7.1.8184,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8184FluidFlowLowInletPressure,,,,,,Fluid Loop Flow Low Inlet Pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8185,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8185FluidFlowHighSupplyPressure,,,,,,Fluid Loop Flow High Supply Pressure.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8186,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8186FluidLowSystemFlow,,,,,,Fluid Loop Low System Flow (Low total flow for units in group).
.1.3.6.1.4.1.476.1.42.3.2.7.1.8187,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8187FluidFlowBlocked,,,,,,Fluid Loop Flow Blocked (Loss of Flow with High Supply Pressure).
.1.3.6.1.4.1.476.1.42.3.2.7.1.8188,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8188FluidDewpointMarginControl,,,,,,Fluid Loop Dewpoint Margin Control is active.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8189,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8189FluidSupplyPressureSensorIssue,,,,,,Fluid Loop Supply Pressure Sensor Issue.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8190,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8190FluidReturnPressureSensorIssue,,,,,,Fluid Loop Return Pressure Sensor Issue.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8191,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8191FluidInletPressureSensorIssue,,,,,,Fluid Loop Inlet Pressure Sensor Issue.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8192,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8192WaterLeakage,,,,,,Water Leakage - Typically indicates unit internal water leakage.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8194,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8194BatteryManagementSystemRackisOfflineWarning,,,,,,The Battery Management System has reported a rack-is-offline warning.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8195,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8195BatteryManagementSystemGeneralWarning,,,,,,The Battery Management System has reported a General Warning.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8196,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8196BatteryManagementSystemFault,,,,,,The Battery Management System has reported a Fault.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8197,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8197BatteryManagementSystemEndOfDischargeWarning,,,,,,The Battery Management System has reported an End-Of-Discharge Warning.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8199,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8199LoadonBypassUnion,,,,,,The output power is supplied by the bypass and maintenance bypass.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8200,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8200BypassControlModuleNotAvailable,,,,,,The bypass control module is not available.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8201,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8201BypassModuleNotAvailable,,,,,,The bypass module is not available.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8208,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8208BranchOverCurrent,,,,,,The PDU branch current is over limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8209,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8209BranchCurrentOverHL,,,,,,The current of pdu branch is over the high level.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8210,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8210BranchCurrentOverLL,,,,,,The current of pdu branch is over the low level.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8211,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8211BranchInrushOC,,,,,,The instantaneous current of pdu branch is large.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8212,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8212BranchBreakerFail,,,,,,A failure has been detected with the branch breaker.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8227,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8227SPMInternalCommFailure,,,,,,The communication with Server Power Management is lost.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8228,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8228SPMCRCCheckError,,,,,,Server Power Management CRC Check Error.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8229,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8229SPMBoardNotReady,,,,,,The Server Power Management sample board is not ready.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8231,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8231PHESupTemSnsrFail,,,,,,Plate Heat Exchanger Supply Temperature Sensor Fail.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8253,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8253PanelboardOvervoltage,,,,,,The panelboard voltage crossed above the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8254,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8254PanelboardUndervoltage,,,,,,The panelboard voltage crossed below the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8255,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8255PanelboardFrequencyDeviation,,,,,,The panelboard frequency deviated beyond the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8259,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8259BranchNeutralOvercurrent,,,,,,The neutral current crossed above the threshold of the branch.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8262,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8262PanelboardOvervoltage,,,,,,The Panelboard voltage crossed above the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8263,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8263PanelboardUndervoltage,,,,,,The panelboard voltage crossed below the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8264,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8264PanelboardFrequencyDeviation,,,,,,The panelboard frequency deviated beyond the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8267,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8267SubfeedOvervoltage,,,,,,The subfeed voltage crossed above the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8268,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8268SubfeedUndervoltage,,,,,,The subfeed voltage crossed below the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8269,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8269SubfeedFrequencyDeviation,,,,,,The subfeed frequency deviated beyond the threshold.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8273,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8273BatteryTempAbnormal,,,,,,Battery temperature is abnormal.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8274,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8274DischargerShutdown,,,,,,A condition is present that prevents the Battery Discharger from working.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8283,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8283BypassUnabletoTrace,,,,,,The voltage amplitude or frequency of bypass is out of the range of trace.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8284,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8284OutputBreakerOpen,,,,,,UPS internal or external output breaker is open.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8285,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8285PowerModuleInputCurrentHigh,,,,,,Input current of the power module is over limit.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8286,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8286ParameterConfigurationFailed,,,,,,Parameter configuration failed.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8287,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8287OutputDisabled,,,,,,Output Disabled.
.1.3.6.1.4.1.476.1.42.3.2.7.1.8288,LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB::lgpCondId8288BatteryTerminalAbnormal,,,,,,Battery Terminal Abnormal.
.1.3.6.1.4.1.476.1.42.3.3,LIEBERT-GP-REGISTRATION-MIB::lgpNotifications,,,,,,This branch is used to register Liebert notification object identifiers.
.1.3.6.1.4.1.476.1.42.3.3.0,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventNotifications,,,,,,Notifications for Liebert Global Products.
.1.3.6.1.4.1.476.1.42.3.3.0.1,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventConditionEntryAdded,,,,,,This notification is sent each time a condition is inserted into the conditions table.
.1.3.6.1.4.1.476.1.42.3.3.0.2,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventConditionEntryRemoved,,,,,,This notification is sent each time a condition is removed from the conditions table.
.1.3.6.1.4.1.476.1.42.3.3.0.3,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventLowBatteryWarning,,,,,,The battery's remaining charge is less than or equal to the agent's configured low threshold 'lgpPwrConfigLowBatteryWarningTime'.
.1.3.6.1.4.1.476.1.42.3.3.0.4,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventLoadTransferedToBypass,,,,,,The device has transferred the load to the bypass source.
.1.3.6.1.4.1.476.1.42.3.3.0.5,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventInternalFault,,,,,,The device has reported an internal fault.
.1.3.6.1.4.1.476.1.42.3.3.0.6,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventBatteryTestFailed,,,,,,The device has reported a battery self-test failure.
.1.3.6.1.4.1.476.1.42.3.3.0.7,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventOutputOverload,,,,,,The device has reported an output overload condition.
.1.3.6.1.4.1.476.1.42.3.3.0.8,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventEstablishedPowerRedundancy,,,,,,The device has transitioned to the user defined redundant state.
.1.3.6.1.4.1.476.1.42.3.3.0.9,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventLostPowerRedundancy,,,,,,The device as transitioned to a non-redundant power state as defined by the user configured threshold.
.1.3.6.1.4.1.476.1.42.3.3.0.10,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventPowerModuleFailure,,,,,,Device power module failure.
.1.3.6.1.4.1.476.1.42.3.3.0.11,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventBatteryModuleFailure,,,,,,Device battery module failure.
.1.3.6.1.4.1.476.1.42.3.3.0.12,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventControlModuleFailure,,,,,,Device control module failure.
.1.3.6.1.4.1.476.1.42.3.3.0.13,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventPowerModuleWarning,,,,,,Device power module warning.
.1.3.6.1.4.1.476.1.42.3.3.0.14,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventBatteryModuleWarning,,,,,,Device battery module warning.
.1.3.6.1.4.1.476.1.42.3.3.0.15,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventControlModuleWarning,,,,,,Device control module warning.
.1.3.6.1.4.1.476.1.42.3.3.0.16,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventAgentFirmwareUpdateSuccessful,,,,,,The firmware update to the agent card has completed successfully. This element has been relocated to lgpAgentFirmwareUpdateSuccessful in the LIEBERT-GP-AGENT-MIB document.
.1.3.6.1.4.1.476.1.42.3.3.0.17,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventAgentFirmwareCorrupt,,,,,,The firmware update to the agent card has failed and the firmware is now corrupt. This element has been relocated to lgpAgentFirmwareCorrupt in the LIEBERT-GP-AGENT-MIB document.
.1.3.6.1.4.1.476.1.42.3.3.0.18,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventConfigModified,,,,,,Configuration for the referenced PDU has been modified.
.1.3.6.1.4.1.476.1.42.3.3.0.19,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventModuleAdded,,,,,,A hot-swappable module has been added to the object specified by the  lgpEventParmTableRef and lgpEventParmTableRowRef.
.1.3.6.1.4.1.476.1.42.3.3.0.20,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventModuleRemoved,,,,,,A hot-swappable module has been removed from the object specified by  the lgpEventParmTableRef and lgpEventParmTableRowRef.
.1.3.6.1.4.1.476.1.42.3.3.0.21,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventRcpPowerStateChangeOn,,,,,,Receptacle's power state has been changed from OFF to ON.
.1.3.6.1.4.1.476.1.42.3.3.0.22,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventRcpPowerStateChangeOff,,,,,,Receptacle's power state has been changed from ON to OFF.
.1.3.6.1.4.1.476.1.42.3.3.0.23,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventRcpLoadAdded,,,,,,The receptacle's load started drawing power. This notification  is asserted when the receptacle power is ON and the associated load  was previously not drawing power but is now drawing power.  This event is not asserted as a result of turning the  receptacle power ON.
.1.3.6.1.4.1.476.1.42.3.3.0.24,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventRcpLoadRemoved,,,,,,The receptacle's load stopped drawing power. This notification  is asserted when the receptacle power is ON and the associated load  was previously drawing power but is now no longer drawing power.  This event is not asserted as a result of turning the  receptacle power OFF.
.1.3.6.1.4.1.476.1.42.3.3.10,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventParameters,,,,,,This sub tree describes various parameters/data that are carried in the payload of some notifications.
.1.3.6.1.4.1.476.1.42.3.3.10.5,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventParmTableRef,OBJECT,read-only,,current,,This object will be included as a varbind in some lgpEventNotifications. It is a reference to a table object in  the MIB. The value of this object will be the OID of a table  that the object that the notification applies to is defined. The notification containing this object will also contain  a varbind 'lgpEventParmTableRowRef' that will specify which  instance (row) in the table the object is defined in. Example: NOTIFICATION: lgpEventConditionEntryAdded varbind: lgpConditionId 6 varbind: lgpConditionDescr lgpConditionRcpBranchBreakerOpen varbind: lgpConditionTime 393884848 varbind: lgpEventParmTableRef lgpPduRbTable varbind: lgpEventParmTableRowRef lgpPduRbEntryId.1.4 In the above example the breaker opened for a Receptacle branch. The specific receptacle branch is specified by the additional varbind (lgpEventParmTableRowRef). In this case the notification is for the 4th receptacle branch on the 1st PDU in the PDU cluster. 
.1.3.6.1.4.1.476.1.42.3.3.10.6,LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventParmTableRowRef,OBJECT,read-only,,current,,This is a reference to the intersection of a row and column (cell) in the table specified by the companion varbind  (lgpEventParmTableRef) in this notification. The row in the table where this cell exists represents the object that this notification applies to. Example: NOTIFICATION: lgpEventRcpPowerStateChangeOff varbind: sysUpTime 393885975 varbind: lgpEventParmTableRef lgpPduRcpTable varbind: lgpEventParmTableRowRef lgpPduRcpEntryId.2.4.5 In the above example the power state changed for a Receptacle. The table containing the definition of the receptacle (lgpPduRcpTable) is given by the varbind (lgpEventParmTableRef) The specific receptacle is specified by the varbind (lgpEventParmTableRowRef). In this case the notification is for the 5th receptacle on the 4th receptacle branch on the  2nd PDU in the PDU cluster. If one wanted to retrieve the user assigned label for this  receptacle the OID would be: lgpPduRcpEntryUsrLabel.2.4.5 
.1.3.6.1.4.1.476.1.42.3.4,LIEBERT-GP-REGISTRATION-MIB::lgpEnvironmental,,,,,,This branch is used to register Liebert environmental object identifiers.
.1.3.6.1.4.1.476.1.42.3.4.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperature,,,,,,This sub-tree is used to register Liebert temperature object identifiers.
.1.3.6.1.4.1.476.1.42.3.4.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureWellKnown,,,,,,Liebert well known temperature objects are identified by OIDs that reside in this sub-tree.
.1.3.6.1.4.1.476.1.42.3.4.1.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvControlTemperature,,,,,,Temperature measurement used as control feedback.
.1.3.6.1.4.1.476.1.42.3.4.1.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvReturnAirTemperature,,,,,,Temperature measurement of return air.
.1.3.6.1.4.1.476.1.42.3.4.1.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSupplyAirTemperature,,,,,,Temperature measurement of supply air.
.1.3.6.1.4.1.476.1.42.3.4.1.1.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpAmbientTemperature,,,,,,Ambient temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.1.5,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpInverterTemperature,,,,,,Temperature measurement of the inverter.
.1.3.6.1.4.1.476.1.42.3.4.1.1.6,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpBatteryTempterature,,,,,,Temperature measurement of the battery.
.1.3.6.1.4.1.476.1.42.3.4.1.1.7,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpAcDcConverterTemperature,,,,,,Temperature measurement of the AC-to-DC Converter.
.1.3.6.1.4.1.476.1.42.3.4.1.1.8,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpPfcTemperature,,,,,,Temperature measurement of the power factor correction circuitry.
.1.3.6.1.4.1.476.1.42.3.4.1.1.9,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpTransformerTemperature,,,,,,Temperature measurement of the transformer.
.1.3.6.1.4.1.476.1.42.3.4.1.1.10,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpLocalTemperature,,,,,,Temperature measurement of local temperature sensor.
.1.3.6.1.4.1.476.1.42.3.4.1.1.10.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpLocal1Temperature,,,,,,Temperature and humidity measurements of Local Sensor 1.
.1.3.6.1.4.1.476.1.42.3.4.1.1.10.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpLocal2Temperature,,,,,,Temperature and humidity measurements of Local Sensor 2.
.1.3.6.1.4.1.476.1.42.3.4.1.1.10.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpLocal3Temperature,,,,,,Temperature and humidity measurements of Local Sensor 3.
.1.3.6.1.4.1.476.1.42.3.4.1.1.11,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpDigitalScrollCompressorTemperature,,,,,,Temperature and humidity measurements of a digital Scroll Compressor.
.1.3.6.1.4.1.476.1.42.3.4.1.1.11.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpDigitalScrollCompressor1Temperature,,,,,,Temperature and humidity measurements of a digital Scroll Compressor 1.
.1.3.6.1.4.1.476.1.42.3.4.1.1.11.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpDigitalScrollCompressor2Temperature,,,,,,Temperature and humidity measurements of a digital Scroll Compressor 2.
.1.3.6.1.4.1.476.1.42.3.4.1.1.12,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpChillWaterTemperature,,,,,,Temperature measurements of a chill water system.
.1.3.6.1.4.1.476.1.42.3.4.1.1.13,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpCoolantTemperature,,,,,,Temperature measurements of an environmental system's coolant.
.1.3.6.1.4.1.476.1.42.3.4.1.1.14,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvEnclosureTemperatureSensors,,,,,,Enclosure temperature sensors
.1.3.6.1.4.1.476.1.42.3.4.1.1.14.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvEnclosureTemperatureSensor1,,,,,,Enclosure temperature sensor 1
.1.3.6.1.4.1.476.1.42.3.4.1.1.14.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvEnclosureTemperatureSensor2,,,,,,Enclosure temperature sensor 2
.1.3.6.1.4.1.476.1.42.3.4.1.1.14.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvEnclosureTemperatureSensor3,,,,,,Enclosure temperature sensor 3
.1.3.6.1.4.1.476.1.42.3.4.1.1.14.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvEnclosureTemperatureSensor4,,,,,,Enclosure temperature sensor 4
.1.3.6.1.4.1.476.1.42.3.4.1.1.15,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvValueAmbientRoomTemperature,,,,,,Temperature outside enclosure.
.1.3.6.1.4.1.476.1.42.3.4.1.1.16,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvDewPointTemperature,,,,,,The calculated temperature outside of the enclosure at which condensation is likely to occur.
.1.3.6.1.4.1.476.1.42.3.4.1.1.17,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvEnclosureTemperature,,,,,,Temperature inside of enclosure.
.1.3.6.1.4.1.476.1.42.3.4.1.1.18,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvAdjustedTemperature,,,,,,The current temperature set-point which is computed by the system and may be temporarily different from the user set-point because of external factors.
.1.3.6.1.4.1.476.1.42.3.4.1.1.19,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvExternalSensors,,,,,,External sensors to monitor environmental variables such as  temperature and humidity
.1.3.6.1.4.1.476.1.42.3.4.1.1.19.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvExternalAirSensorA,,,,,,Temperature and humidity measurements from external air sensor A.
.1.3.6.1.4.1.476.1.42.3.4.1.1.19.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvExternalAirSensorADewPoint,,,,,,Dewpoint temperature for External Air Sensor A.
.1.3.6.1.4.1.476.1.42.3.4.1.1.19.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvExternalAirSensorB,,,,,,Temperature and humidity measurements from external air sensor B.
.1.3.6.1.4.1.476.1.42.3.4.1.1.19.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvExternalAirSensorBDewPoint,,,,,,Dewpoint temperature for External Air Sensor B.
.1.3.6.1.4.1.476.1.42.3.4.1.1.20,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSupplyFluidTemperature,,,,,,The current temperature of the fluid being supplied.
.1.3.6.1.4.1.476.1.42.3.4.1.1.21,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSupplyRefrigerantTemperature,,,,,,The current temperature of the refrigerant being supplied.
.1.3.6.1.4.1.476.1.42.3.4.1.1.22,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvMinDesiredRoomAirTemperature,,,,,,The minimum desired room air temperature. If the room air temperature falls below this set point, the unit will reduce the cooling.
.1.3.6.1.4.1.476.1.42.3.4.1.1.23,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvDewPointTemperatures,,,,,,This sub-tree identifies well-known dew point temperatures in the system.
.1.3.6.1.4.1.476.1.42.3.4.1.1.23.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvInletDewPointTemperature,,,,,,Dew point temperature measured at the inlet of the unit.
.1.3.6.1.4.1.476.1.42.3.4.1.1.24,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvReturnFluidTemperature,,,,,,The current temperature of the return fluid.
.1.3.6.1.4.1.476.1.42.3.4.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureFahrenheit,,,,,,This sub-tree contains OIDs that are used to control and monitor temperature using the Fahrenheit temperature scale.
.1.3.6.1.4.1.476.1.42.3.4.1.2.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureSettingDegF,Integer32,read-write,,current,,The temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegC' with the value converted to Celsius.
.1.3.6.1.4.1.476.1.42.3.4.1.2.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureToleranceDegF,Integer32,read-write,,current,,The acceptable variance from 'lgpEnvTemperatureSettingDegF', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegC' with the value converted to Celsius.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureTableDegF,,not-accessible,,current,,A list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegC' where Fahrenheit values are converted to Celsius.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureEntryDegF,,not-accessible,lgpEnvTemperatureIdDegF,current,,This entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegF'.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureIdDegF,Unsigned32,read-only,,current,,This OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegF'.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureDescrDegF,OBJECT,read-only,,current,,A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureMeasurementDegF,Integer32,read-only,,current,,The measured temperature value.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureHighThresholdDegF,Integer32,read-write,,current,,The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.5,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureLowThresholdDegF,Integer32,read-write,,current,,The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.6,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureSetPointDegF,Integer32,read-write,,current,,The temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.7,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureDailyHighDegF,Integer32,read-only,,current,,The daily high temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.8,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureDailyLowDegF,Integer32,read-only,,current,,The daily low temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.9,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempDailyHighTimeHourDegF,Integer32,read-only,,current,,The hours digit of the time corresponding to the daily high temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.10,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempDailyHighTimeMinuteDegF,Integer32,read-only,,current,,The minutes digit of the time corresponding to the daily high temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.11,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempDailyHighTimeSecondDegF,Integer32,read-only,,current,,The seconds digit of the time corresponding to the daily high temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.12,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempDailyLowTimeHourDegF,Integer32,read-only,,current,,The hours digit of the time corresponding to the daily low temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.13,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempDailyLowTimeMinuteDegF,Integer32,read-only,,current,,The minutes digit of the time corresponding to the daily low temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.14,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempDailyLowTimeSecondDegF,Integer32,read-only,,current,,The seconds digit of the time corresponding to the daily low temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.50,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureMeasurementTenthsDegF,Integer32,read-only,,current,,The measured temperature value.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.51,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureHighThresholdTenthsDegF,Integer32,read-write,,current,,The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.52,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureLowThresholdTenthsDegF,Integer32,read-write,,current,,The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.53,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureSetPointTenthsDegF,Integer32,read-write,,current,,The temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.60,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureDeadBandTenthsDegF,Integer32,read-write,,current,,The deadband region around the setpoint value  (lgpEnvTemperatureSetPointTenthsDegF) where no heating or cooling will occur.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.61,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempHeatingPropBandTenthsDegF,Integer32,read-write,,current,,The proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where heating will be proportionally controlled.
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.62,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempCoolingPropBandTenthsDegF,Integer32,read-write,,current,,The proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where cooling will be proportionally controlled.
.1.3.6.1.4.1.476.1.42.3.4.1.2.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureDeadbandRangeDegF,Integer32,read-write,,current,,The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled.
.1.3.6.1.4.1.476.1.42.3.4.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureCelsius,,,,,,This sub-tree contains OIDs that are used to control and monitor temperature using the Celsius temperature scale.
.1.3.6.1.4.1.476.1.42.3.4.1.3.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureSettingDegC,Integer32,read-write,,current,,The temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegF' with the value converted to Fahrenheit.
.1.3.6.1.4.1.476.1.42.3.4.1.3.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureToleranceDegC,Integer32,read-write,,current,,The acceptable variance from 'lgpEnvTemperatureSettingDegC', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegF' with the value converted to Fahrenheit.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureTableDegC,,not-accessible,,current,,A list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegF' where Celsius values are converted to Fahrenheit.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureEntryDegC,,not-accessible,lgpEnvTemperatureIdDegC,current,,This entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegC'.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureIdDegC,Unsigned32,read-only,,current,,This OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegC'.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureDescrDegC,OBJECT,read-only,,current,,A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureMeasurementDegC,Integer32,read-only,,current,,The measured temperature value.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureHighThresholdDegC,Integer32,read-write,,current,,The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.5,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureLowThresholdDegC,Integer32,read-write,,current,,The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.6,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureSetPointDegC,Integer32,read-write,,current,,The temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.7,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureDailyHighDegC,Integer32,read-only,,current,,The daily high temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.8,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureDailyLowDegC,Integer32,read-only,,current,,The daily low temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.9,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempDailyHighTimeHourDegC,Integer32,read-only,,current,,The hours digit of the time corresponding to the daily high temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.10,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempDailyHighTimeMinuteDegC,Integer32,read-only,,current,,The minutes digit of the time corresponding to the daily high temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.11,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempDailyHighTimeSecondDegC,Integer32,read-only,,current,,The seconds digit of the time corresponding to the daily high temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.12,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempDailyLowTimeHourDegC,Integer32,read-only,,current,,The hours digit of the time corresponding to the daily low temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.13,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempDailyLowTimeMinuteDegC,Integer32,read-only,,current,,The minutes digit of the time corresponding to the daily low temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.14,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempDailyLowTimeSecondDegC,Integer32,read-only,,current,,The seconds digit of the time corresponding to the daily low temperature measurement.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.50,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureMeasurementTenthsDegC,Integer32,read-only,,current,,The measured temperature value.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.51,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureHighThresholdTenthsDegC,Integer32,read-write,,current,,The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.52,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureLowThresholdTenthsDegC,Integer32,read-write,,current,,The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.53,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureSetPointTenthsDegC,Integer32,read-write,,current,,The temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.60,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureDeadBandTenthsDegC,Integer32,read-write,,current,,The deadband region around the setpoint value  (lgpEnvTemperatureSetPointTenthsDegC) where no heating or cooling will occur.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.61,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempHeatingPropBandTenthsDegC,Integer32,read-write,,current,,The proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where heating will be proportionally controlled.
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.62,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTempCoolingPropBandTenthsDegC,Integer32,read-write,,current,,The proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where cooling will be proportionally controlled.
.1.3.6.1.4.1.476.1.42.3.4.1.3.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureDeadbandRangeDegC,Integer32,read-write,,current,,The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled.
.1.3.6.1.4.1.476.1.42.3.4.1.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvTemperatureControlMode,OBJECT,read-only,,current,,A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature object that is used for control.
.1.3.6.1.4.1.476.1.42.3.4.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidity,,,,,,This sub-tree is used to register Liebert humidity object identifiers.
.1.3.6.1.4.1.476.1.42.3.4.2.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityWellKnown,,,,,,Liebert well known humidity objects are defined by OIDs that reside in this sub-tree.
.1.3.6.1.4.1.476.1.42.3.4.2.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvControlHumidity,,,,,,Humidity measurement used as control feedback.
.1.3.6.1.4.1.476.1.42.3.4.2.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvReturnAirHumidity,,,,,,Humidity measurement of return air.
.1.3.6.1.4.1.476.1.42.3.4.2.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSupplyAirHumidity,,,,,,Humidity measurement of supply air.
.1.3.6.1.4.1.476.1.42.3.4.2.1.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvValueAmbientHumidity,,,,,,Humidity outside enclosure.
.1.3.6.1.4.1.476.1.42.3.4.2.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityRelative,,,,,,This sub-tree contains OIDs that are used to control and monitor relative humidity.
.1.3.6.1.4.1.476.1.42.3.4.2.2.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumiditySettingRel,Integer32,read-write,,current,,The humidity setting used to control the well known humidity point.
.1.3.6.1.4.1.476.1.42.3.4.2.2.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityToleranceRel,Integer32,read-write,,current,,Acceptable variance from lgpEnvHumiditySettingRel, without initiating a control action.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityTableRel,,not-accessible,,current,,A list of humidity table entries. The table contains zero, one, or many rows, depending upon the number of humidity objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityEntryRel,,not-accessible,lgpEnvHumidityIdRel,current,,This entry defines the contents of the rows for the table 'lgpEnvHumidityTableRel'.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityIdRel,Unsigned32,read-only,,current,,This OID is used as an index to identify a row in the table 'lgpEnvHumidityTableRel'.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityDescrRel,OBJECT,read-only,,current,,A reference to a humidity description object. The object referenced should not be accessible, but rather be used to provide a unique description of the humidity.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityMeasurementRel,Integer32,read-only,,current,,The measured humidity value.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityHighThresholdRel,Integer32,read-write,,current,,The high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.5,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityLowThresholdRel,Integer32,read-write,,current,,The low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.6,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumiditySetPoint,Integer32,read-write,,current,,The humidity setting used to control the well known humidity object 'lgpEnvHumidityDescrRel'. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.7,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityDailyHigh,Integer32,read-only,,current,,The daily high relative humidity measurement.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.8,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityDailyLow,Integer32,read-only,,current,,The daily low relative humidity measurement.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.9,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityDailyHighTimeHour,Integer32,read-only,,current,,The hours digit of the time corresponding to the daily high humidity measurement.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.10,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityDailyHighTimeMinute,Integer32,read-only,,current,,The minutes digit of the time corresponding to the daily high humidity measurement.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.11,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityDailyHighTimeSecond,Integer32,read-only,,current,,The seconds digit of the time corresponding to the daily high humidity measurement.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.12,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityDailyLowTimeHour,Integer32,read-only,,current,,The hours digit of the time corresponding to the daily low humidity measurement.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.13,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityDailyLowTimeMinute,Integer32,read-only,,current,,The minutes digit of the time corresponding to the daily low humidity measurement.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.14,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityDailyLowTimeSecond,Integer32,read-only,,current,,The seconds digit of the time corresponding to the daily low humidity measurement.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.15,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityDeadBand,Integer32,read-write,,current,,The deadband region around the setpoint value  (lgpEnvHumiditySetPoint) where no humidifying or dehumidifying will occur.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.16,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidifyPropBand,Integer32,read-write,,current,,The proportional region below the setpoint value (lgpEnvHumiditySetPoint) where humidifying will be proportionally controlled.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.17,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvDehumidifyPropBand,Integer32,read-write,,current,,The proportional region above the setpoint value (lgpEnvHumiditySetPoint) where dehumidifying will be proportionally controlled.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.50,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityMeasurementRelTenths,Integer32,read-only,,current,,The measured humidity value.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.51,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityHighThresholdRelTenths,Integer32,read-write,,current,,The high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification.
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.52,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityLowThresholdRelTenths,Integer32,read-write,,current,,The low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification.
.1.3.6.1.4.1.476.1.42.3.4.2.2.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidityDeadbandRange,Integer32,read-write,,current,,The allowable deviation above and below the humidity set point used to create a no control region, a dead-band, where humidifying and dehumidifying control are disabled.
.1.3.6.1.4.1.476.1.42.3.4.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvState,,,,,,This sub-tree is used to register Liebert environmental state object identifiers.
.1.3.6.1.4.1.476.1.42.3.4.3.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateSystem,INTEGER,read-only,,current,on(1):off(2):standby(3),The present state of the system.
.1.3.6.1.4.1.476.1.42.3.4.3.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateCooling,INTEGER,read-only,,current,on(1):off(2),The present state of the cooling subsystem.
.1.3.6.1.4.1.476.1.42.3.4.3.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateHeating,INTEGER,read-only,,current,on(1):off(2),The present state of the heating subsystem.
.1.3.6.1.4.1.476.1.42.3.4.3.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateHumidifying,INTEGER,read-only,,current,on(1):off(2),The present state of the humidifier subsystem.
.1.3.6.1.4.1.476.1.42.3.4.3.5,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateDehumidifying,INTEGER,read-only,,current,on(1):off(2),The present state of the dehumidifier subsystem
.1.3.6.1.4.1.476.1.42.3.4.3.6,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateEconoCycle,INTEGER,read-only,,current,on(1):off(2),The present state of the Econ-o-cycle subsystem.
.1.3.6.1.4.1.476.1.42.3.4.3.7,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateFan,INTEGER,read-only,,current,on(1):off(2),The present state of the system fan.
.1.3.6.1.4.1.476.1.42.3.4.3.8,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateGeneralAlarmOutput,INTEGER,read-only,,current,on(1):off(2),The present state of the general alarm output. This indicates if an alarm is active in the system.
.1.3.6.1.4.1.476.1.42.3.4.3.9,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateCoolingCapacity,Unsigned32,read-only,,current,,The percentage of the cooling capacity presently in use.
.1.3.6.1.4.1.476.1.42.3.4.3.10,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateHeatingCapacity,Unsigned32,read-only,,current,,The percentage of the heating capacity presently in use.
.1.3.6.1.4.1.476.1.42.3.4.3.11,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateAudibleAlarm,INTEGER,read-only,,current,on(1):off(2),The present state of the audible alarm output.
.1.3.6.1.4.1.476.1.42.3.4.3.12,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateCoolingUnits,,,,,,This sub-tree contains OIDs that are used to indicate the status of cooling units.
.1.3.6.1.4.1.476.1.42.3.4.3.12.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateCoolingUnit1,INTEGER,read-only,,current,on(1):off(2),The present state of cooling unit 1.
.1.3.6.1.4.1.476.1.42.3.4.3.12.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateCoolingUnit2,INTEGER,read-only,,current,on(1):off(2),The present state of cooling unit 2.
.1.3.6.1.4.1.476.1.42.3.4.3.12.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateCoolingUnit3,INTEGER,read-only,,current,on(1):off(2),The present state of cooling unit 3.
.1.3.6.1.4.1.476.1.42.3.4.3.12.5,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateCoolingUnit4,INTEGER,read-only,,current,on(1):off(2),The present state of cooling unit 4.
.1.3.6.1.4.1.476.1.42.3.4.3.13,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateHeatingUnits,,,,,,This sub-tree contains OIDs that are used to indicate the status of heating units.
.1.3.6.1.4.1.476.1.42.3.4.3.13.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateHeatingUnit1,INTEGER,read-only,,current,on(1):off(2),The present state of heating unit 1.
.1.3.6.1.4.1.476.1.42.3.4.3.13.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateHeatingUnit2,INTEGER,read-only,,current,on(1):off(2),The present state of heating unit 2.
.1.3.6.1.4.1.476.1.42.3.4.3.13.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateHeatingUnit3,INTEGER,read-only,,current,on(1):off(2),The present state of heating unit 3.
.1.3.6.1.4.1.476.1.42.3.4.3.13.5,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateHeatingUnit4,INTEGER,read-only,,current,on(1):off(2),The present state of heating unit 4.
.1.3.6.1.4.1.476.1.42.3.4.3.14,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateOperatingReason,INTEGER,read-only,,current,none(1):localUser(2):alarm(3):schedule(4):remoteUser(5):externalDevice(6):localDisplay(7),The reason for the current operating state of the system.
.1.3.6.1.4.1.476.1.42.3.4.3.15,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateOperatingMode,INTEGER,read-only,,current,auto(1):manual(2),The present operating mode of the system.
.1.3.6.1.4.1.476.1.42.3.4.3.16,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateFanCapacity,Unsigned32,read-only,,current,,The percentage of the fan capacity presently in use.
.1.3.6.1.4.1.476.1.42.3.4.3.17,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateFreeCoolingCapacity,Unsigned32,read-only,,current,,The percentage of the free cooling capacity presently in use.
.1.3.6.1.4.1.476.1.42.3.4.3.18,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateDehumidifyingCapacity,Unsigned32,read-only,,current,,The percentage of the dehumidifying capacity presently in use.
.1.3.6.1.4.1.476.1.42.3.4.3.19,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateHumidifyingCapacity,Unsigned32,read-only,,current,,The percentage of the humidifying capacity presently in use.
.1.3.6.1.4.1.476.1.42.3.4.3.20,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateFreeCooling,INTEGER,read-only,,current,on(1):off(2):start(3):unavailable(4),The present state of the system free cooling process of heat exchange. When 'off', free cooling is not in use. When 'on' free cooling is in use. When 'start', free cooling is preparing to turn on. When 'unavailable', the state information is unavailable.
.1.3.6.1.4.1.476.1.42.3.4.3.21,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateElectricHeater,INTEGER,read-only,,current,on(1):off(2),The present state of the electric heaters.
.1.3.6.1.4.1.476.1.42.3.4.3.22,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateHotWater,INTEGER,read-only,,current,on(1):off(2),The present state of hot water system.
.1.3.6.1.4.1.476.1.42.3.4.3.23,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStateOperatingEfficiency,Unsigned32,read-only,,current,,The ratio of cooling energy provided to the amount of total energy being used.
.1.3.6.1.4.1.476.1.42.3.4.3.50,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvComponentStateTable,,not-accessible,,current,,This table contains a list of the units components that have a state associated with them. The table contains zero, one, or more rows, depending upon the number of components associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored.
.1.3.6.1.4.1.476.1.42.3.4.3.50.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvComponentStateEntry,,not-accessible,lgpEnvComponentStateIndex,current,,This entry defines the attributes to be populated in the various columns of the 'lgpEnvComponentStateTable'.
.1.3.6.1.4.1.476.1.42.3.4.3.50.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvComponentStateIndex,Unsigned32,not-accessible,,current,,This is the index indicating the nth element of the table.
.1.3.6.1.4.1.476.1.42.3.4.3.50.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvComponentStateDescr,OBJECT,read-only,,current,,A reference to a component description object. The object referenced should not be accessible, but rather be used to provide a unique description of the component being  described in the row of the table.
.1.3.6.1.4.1.476.1.42.3.4.3.50.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvComponentState,INTEGER,read-only,,current,not-specified(0):on(1):off(2),not-specified The state of the component is unknown. on The component is on. off The component is off.
.1.3.6.1.4.1.476.1.42.3.4.3.70,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvValveTable,,not-accessible,,current,,This table contains a list of the unit valves that have information associated with them. The table contains zero, one, or more rows, depending upon the number of valves associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored.
.1.3.6.1.4.1.476.1.42.3.4.3.70.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvValveEntry,,not-accessible,lgpEnvValveIndex,current,,This entry defines the attributes to be populated in the various columns of the 'lgpEnvValveTable'.
.1.3.6.1.4.1.476.1.42.3.4.3.70.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvValveIndex,Unsigned32,not-accessible,,current,,This is the index indicating the nth element of the table.
.1.3.6.1.4.1.476.1.42.3.4.3.70.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvValveDescr,OBJECT,read-only,,current,,A reference to a valve description object. The object referenced should not be accessible, but rather be used to provide a unique description of the valve being  described in the row of the table.
.1.3.6.1.4.1.476.1.42.3.4.3.70.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvValveState,INTEGER,read-only,,current,not-specified(0):open(1):closed(2),not-specified The state of the component is unknown. open The valve is open. off The valve is closed.
.1.3.6.1.4.1.476.1.42.3.4.3.70.1.20,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvValvePositionTenths,Unsigned32,read-only,,current,,This gives a value describing the position of the valve.
.1.3.6.1.4.1.476.1.42.3.4.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfig,,,,,,This sub-tree is used to register Liebert environmental configuration object identifiers.
.1.3.6.1.4.1.476.1.42.3.4.4.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigReheatLockout,INTEGER,read-write,,current,lockedOut(1):notLockedOut(2),If locked-out the reheats will not operate even if controller calls for its operation.
.1.3.6.1.4.1.476.1.42.3.4.4.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigHumLockout,INTEGER,read-write,,current,lockedOut(1):notLockedOut(2),If locked-out the humidifier will not operate even if controller calls for its operation.
.1.3.6.1.4.1.476.1.42.3.4.4.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigRestartDelay,Unsigned32,read-write,,current,,When utility power is disrupted, this is the delay interval to wait before restarting the system after the utility power is restored. A Restart Delay of zero denotes a manual restart, the unit will NOT automatically restart.
.1.3.6.1.4.1.476.1.42.3.4.4.7,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigRemoteShutdown,INTEGER,read-write,,current,disabled(1):enabled(2),When in the disabled state, the remote shutdown feature should be locked out. The enabled state is self-describing.
.1.3.6.1.4.1.476.1.42.3.4.4.8,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigCoolingServiceInterval,Unsigned32,read-write,,current,,The amount of time, in hours, between scheduled maintenance of the cooling system. When the cooling service timer reaches this value an lgpConditionServiceCooling will be activated. Once service has been completed the cooling service timer should be reset to 0.
.1.3.6.1.4.1.476.1.42.3.4.4.9,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigHumidifierServiceInterval,Unsigned32,read-write,,current,,The amount of time, in hours, between scheduled maintenance of the humidifier. When the humidifier service timer reaches this value an lgpConditionServiceHumidifier will be activated. Once service has been completed humidifier service timer should be reset to 0.
.1.3.6.1.4.1.476.1.42.3.4.4.10,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigFilterServiceInterval,Unsigned32,read-write,,current,,The amount of time, in hours, between scheduled maintenance of the system filter. When the filter service timer reaches this value an lgpConditionChangeFilter will be activated. Once service has been completed the filter service timer should be reset to 0.
.1.3.6.1.4.1.476.1.42.3.4.4.11,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigSleepModeDeadbandRangeDegC,Integer32,read-write,,current,,The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation.
.1.3.6.1.4.1.476.1.42.3.4.4.12,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigSleepModeDeadbandRangeDegF,Integer32,read-write,,current,,The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation.
.1.3.6.1.4.1.476.1.42.3.4.4.13,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigSupplyTempLowLimitDegF,Integer32,read-write,,current,,The minimum allowable supply temperature.
.1.3.6.1.4.1.476.1.42.3.4.4.14,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigSupplyTempLowLimitDegC,Integer32,read-write,,current,,The minimum allowable supply temperature.
.1.3.6.1.4.1.476.1.42.3.4.4.15,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigTemperatureIntegTime,Integer32,read-write,,current,,The value used as the integration factor in the proportional integral derivative (PID) temperature calculation.
.1.3.6.1.4.1.476.1.42.3.4.4.16,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigLocalTemperatureUnit,INTEGER,read-write,,current,degC(1):degF(2),The local temperature unit of the system.
.1.3.6.1.4.1.476.1.42.3.4.4.17,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigSleepMode,INTEGER,read-write,,current,enabled(1):disabled(2):auto(3),The configured mode of the device's sleep function. If 'enabled', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day. If 'disabled', the device will operate continually and not sleep at all. If 'auto', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day unless the environmental conditions fall outside the desired operation ranges.
.1.3.6.1.4.1.476.1.42.3.4.4.18,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigHumidityIntegTime,Integer32,read-write,,current,,The value used as the integration factor in the proportional integral derivative (PID) humidity calculation.
.1.3.6.1.4.1.476.1.42.3.4.4.19,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigFreecoolingDeltaDegF,Integer32,read-write,,current,,The minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling.
.1.3.6.1.4.1.476.1.42.3.4.4.20,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigFreecoolingDeltaDegC,Integer32,read-write,,current,,The minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling.
.1.3.6.1.4.1.476.1.42.3.4.4.21,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigSupplyTempLowLimit,INTEGER,read-write,,current,disabled(1):enabled(2),The system configuration parameter to enable or disable the supply air low temperature limit.
.1.3.6.1.4.1.476.1.42.3.4.4.22,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigSensorEventsStandard,INTEGER,read-write,,current,disabled(1):enabled(2),The system configuration parameter to enable or disable the standard sensor events.
.1.3.6.1.4.1.476.1.42.3.4.4.23,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigSensorEvents1,INTEGER,read-write,,current,disabled(1):enabled(2),The system configuration parameter to enable or disable sensor 1 events.
.1.3.6.1.4.1.476.1.42.3.4.4.24,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigSleepModeDeadbandRange,INTEGER,read-write,,current,disabled(1):enabled(2),The system configuration parameter to enable or disable the use of the sleep interval dead-band range in the sleep mode temperature calculations and control algorithm.
.1.3.6.1.4.1.476.1.42.3.4.4.25,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigAutoConfiguration,INTEGER,read-write,,current,disabled(1):enabled(2),The system configuration parameter to enable or disable the auto configuration feature. This feature configures temperature and humidity control parameters.
.1.3.6.1.4.1.476.1.42.3.4.4.26,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigDeltaGlycolType,INTEGER,read-write,,current,disabled(1):contact(2):value(3),The system configuration parameter that specifies how the system will determine if there is enough capacity to initiate free cooling. If 'disabled', the system will use the valve temperature to initiate free cooling. If 'contact', a input to the system will initiate free cooling. If 'valve', the system compares the room and glycol temperature differential with the valve temperature to initiate free cooling. If the temperature differential is greater than or equal to the valve temperature, free cooling will be initiated.
.1.3.6.1.4.1.476.1.42.3.4.4.27,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigChillWaterControl,INTEGER,read-write,,current,disabled(1):enabled(2),The system configuration parameter to enable or disable the minimum chill water temperature control.
.1.3.6.1.4.1.476.1.42.3.4.4.28,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigInfaredFlushRate,Unsigned32,read-write,,current,,The Infrared humidifier pan overfill rate. This parameter configures the amount of water that flows into the humidifier pan when the 'humidifier is in operation.
.1.3.6.1.4.1.476.1.42.3.4.4.29,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigHumidityControl,INTEGER,read-write,,current,relative(1):compensated(2):predictive(3),The present configured state of the automatic humidity compensation algorithm.
.1.3.6.1.4.1.476.1.42.3.4.4.30,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigCompressorLockout,INTEGER,read-write,,current,lockedOut(1):notLockedOut(2),The system as locked out the compressor(s). If locked-out, the compressor(s) will not operate even if the controller calls for their operation.
.1.3.6.1.4.1.476.1.42.3.4.4.31,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigReheatAndHumidifierLockout,INTEGER,read-write,,current,lockedOut(1):notLockedOut(2),The system as locked out the compressor(s). If locked-out, the electrical reheats and humidifier will not operate even if the controller calls for their operation.
.1.3.6.1.4.1.476.1.42.3.4.4.32,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvOperationalTimeTable,,not-accessible,,current,,A list of environmental operational time ranges for a given environmental unit. The entries in this table may be duplicated from values in the 'lgpEnvStatistics' group. This table contains zero, one, or many rows, depending upon the number of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available in the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
.1.3.6.1.4.1.476.1.42.3.4.4.32.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvOperationalTimeEntry,,not-accessible,lgpEnvOperationTimeIndex,current,,This entry defines the contents of the columns for the table 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.4.32.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvOperationTimeIndex,Unsigned32,not-accessible,,current,,This is the index indicating the nth element of the table.
.1.3.6.1.4.1.476.1.42.3.4.4.32.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvOperationTimePoint,OBJECT,read-only,,current,,An OID representing a well known operation point. These object identifiers can indicate a point, location, or mode of an operation for which a measurement is recorded. The OID's name usually implies a location of the measurement point such as 'fan', 'compressor', etc.
.1.3.6.1.4.1.476.1.42.3.4.4.32.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvOperationTimeSubID,Integer32,read-only,,current,,This is a sub identifier for the 'lgpEnvOperationPoint'. It indicates the instance number of the well known operation point. For example, a system could have two fans installed. This variable would identify fan 1 with a lgpEnvOperationSubID equal to 1 and fan 2 with a lgpEnvOperationSubID equal to 2.
.1.3.6.1.4.1.476.1.42.3.4.4.32.1.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvOperationTimeUnit,OBJECT,read-only,,current,,An OID representing a well known operation time unit type. These object identifiers indicate the units of the operation time. The OID's name usually implies a measurement type such as 'lgpEnvHours', etc.
.1.3.6.1.4.1.476.1.42.3.4.4.32.1.5,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvOperationTimeValue,Integer32,read-write,,current,,The actual operation time value of the 'lgpEnvOperationTimePoint'. If multiple operation times are available for a 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them.
.1.3.6.1.4.1.476.1.42.3.4.4.32.1.6,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvOperationTimeHighWarning,Integer32,read-write,,current,,The high warning time of the operation designated by the 'lgpEnvOperationTimePoint'. If operation times are available at a single 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them.
.1.3.6.1.4.1.476.1.42.3.4.4.33,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigTempControlAlgorithm,INTEGER,read-write,,current,pi(1):pid(2):intelligent(3):proportional(4),Selects the algorithm for controlling temperature.
.1.3.6.1.4.1.476.1.42.3.4.4.34,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigFanSpeedMode,INTEGER,read-write,,current,manual(1):auto(2),Changes the function of the fan speed output. If auto, then the fan speed is modulated. If manual, the fan speed output follows lgpEnvConfigFanSpeedCapacity.
.1.3.6.1.4.1.476.1.42.3.4.4.35,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigFanSpeedCapacity,Unsigned32,read-write,,current,,Sets the fan speed output if lgpEnvConfigFanSpeedMode is set to 'manual'. Typical values range from 0 to 100% (actual valid ranges may differ from unit to unit).
.1.3.6.1.4.1.476.1.42.3.4.4.36,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigBmsResetTimer,Unsigned32,read-write,,current,,The current count-down time for a BMS to continue controlling the fan speed. If this value reaches 0, then the condition lgpConditionBmsResetTimerExpired will be generated. If a BMS wants to continue controlling the fan speed, it must reset this timer. Typical values range from 0 to 120 minutes (actual valid ranges may differ from unit to unit).
.1.3.6.1.4.1.476.1.42.3.4.4.37,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigDisableSensorOffsetDegC,Integer32,read-write,,current,,If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used.
.1.3.6.1.4.1.476.1.42.3.4.4.38,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigDisableSensorOffsetDegF,Integer32,read-write,,current,,If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used.
.1.3.6.1.4.1.476.1.42.3.4.4.39,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigCabinetSensorAlarms,INTEGER,read-write,,current,disabled(0):enabled(1),Enable or Disable Cabinet Sensor Alarms.
.1.3.6.1.4.1.476.1.42.3.4.4.42,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigAirTemperatureControlSensor,INTEGER,read-write,,current,supply(1):remote(2):return(3),Sensor from which air temperature measurements will be used for cooling and heating control.
.1.3.6.1.4.1.476.1.42.3.4.4.43,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigFanSpeedControlSensor,INTEGER,read-write,,current,supply(1):remote(2):return(3),Sensor from which air temperature measurements will be used for fan speed control.
.1.3.6.1.4.1.476.1.42.3.4.4.44,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigMinFanSpeed,Unsigned32,read-write,,current,,Sets the minimum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'.
.1.3.6.1.4.1.476.1.42.3.4.4.45,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigMaxFanSpeed,Unsigned32,read-write,,current,,Sets the maximum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'.
.1.3.6.1.4.1.476.1.42.3.4.4.46,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigFanSpeedPropBandDegC,Integer32,read-write,,current,,Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled.
.1.3.6.1.4.1.476.1.42.3.4.4.47,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigFanSpeedPropBandDegF,Integer32,read-write,,current,,Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled.
.1.3.6.1.4.1.476.1.42.3.4.5,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvControl,,,,,,This sub-tree is used to register Liebert environmental control object identifiers.
.1.3.6.1.4.1.476.1.42.3.4.5.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvControlShutdownAfterDelay,Integer32,read-write,,current,,Setting this object will shutdown (i.e., turn off) the system after the indicated number of seconds. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. When read, lgpEnvControlShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any lgpEnvControlShutdownAfterDelay already in effect.
.1.3.6.1.4.1.476.1.42.3.4.5.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvControlStartupAfterDelay,Integer32,read-write,,current,,Setting this object will start the system after the indicated number of seconds. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the system is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any lgpEnvControlStartupAfterDelay countdown in progress. When read, lgpEnvControlStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.
.1.3.6.1.4.1.476.1.42.3.4.5.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepIntervalTimeTable,,not-accessible,,current,,A sleep time interval table containing a list of the start and stop times to be used to take a device online or offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
.1.3.6.1.4.1.476.1.42.3.4.5.3.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepIntervalTimeEntry,,not-accessible,lgpEnvSleepTimeIndex,current,,This entry defines the contents of the columns for the table 'lgpEnvSleepIntervalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.5.3.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepTimeIndex,Unsigned32,not-accessible,,current,,This is the index indicating the row of the table 'lgpEnvSleepIntervalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.5.3.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepTimeSubID,Integer32,read-only,,current,,This is a sub identifier for each 'lgpEnvSleepIntervalTimeEntry'. It indicates the instance number of the 'lgpEnvSleepIntervalTimeEntry'. For example, a system could have two sleep intervals and the first interval's sub ID would be 1 and the second interval's sub ID would be 2.
.1.3.6.1.4.1.476.1.42.3.4.5.3.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepTimeStartHour,Integer32,read-write,,current,,This is the hours digit of the time when the system will be put online.
.1.3.6.1.4.1.476.1.42.3.4.5.3.1.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepTimeStartMinute,Integer32,read-write,,current,,This is the minutes digit of the time when the system will be put online.
.1.3.6.1.4.1.476.1.42.3.4.5.3.1.5,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepTimeStopHour,Integer32,read-write,,current,,This is the hours digit containing the time when the system will be taken offline.
.1.3.6.1.4.1.476.1.42.3.4.5.3.1.6,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepTimeStopMinute,Integer32,read-write,,current,,This is the minutes digit containing the time when the system will be taken offline.
.1.3.6.1.4.1.476.1.42.3.4.5.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepDayTable,,not-accessible,,current,,A sleep table containing a list of the days of the week the system will be offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
.1.3.6.1.4.1.476.1.42.3.4.5.4.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepDayEntry,,not-accessible,lgpEnvSleepDayIndex,current,,This entry defines the contents of the columns for the table 'lgpEnvSleepDayTable'.
.1.3.6.1.4.1.476.1.42.3.4.5.4.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepDayIndex,Unsigned32,not-accessible,,current,,This is the index indicating the row of the table 'lgpEnvSleepDayTable'.
.1.3.6.1.4.1.476.1.42.3.4.5.4.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepDay,INTEGER,read-only,,current,sunday(1):monday(2):tuesday(3):wednesday(4):thursday(5):friday(6):saturday(7),This is a sub identifier for the day of the week within 'lgpEnvSleepDayTable'.
.1.3.6.1.4.1.476.1.42.3.4.5.4.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvSleepAllDayEnabled,INTEGER,read-write,,current,yes(1):no(2),The all day sleep functionality has been enabled for the corresponding 'lgpEnvSleepDay' in the 'lgpEnvSleepDayTable'.
.1.3.6.1.4.1.476.1.42.3.4.6,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatistics,,,,,,This sub-tree is used to register Liebert environmental statistic object identifiers.
.1.3.6.1.4.1.476.1.42.3.4.6.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsComp1RunHr,Unsigned32,read-only,,current,,Accumulated run hours of compressor 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsComp2RunHr,Unsigned32,read-only,,current,,Accumulated run hours of compressor 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsFanRunHr,Unsigned32,read-only,,current,, Accumulated run hours of the main fan. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsHumRunHr,Unsigned32,read-only,,current,, Accumulated run hours of the humidifier. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.7,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsReheat1RunHr,Unsigned32,read-only,,current,,Accumulated run hours of reheat element 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.8,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsReheat2RunHr,Unsigned32,read-only,,current,,Accumulated run hours of reheat element 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.9,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsReheat3RunHr,Unsigned32,read-only,,current,,Accumulated run hours of reheat element 3. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.10,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsCoolingModeHrs,Unsigned32,read-only,,current,,Accumulated run hours while lgpEnvStateCooling is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.11,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsHeatingModeHrs,Unsigned32,read-only,,current,,Accumulated run hours while lgpEnvStateHeating is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.12,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsHumidifyModeHrs,Unsigned32,read-only,,current,,Accumulated run hours of the humidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.13,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsDehumidifyModeHrs,Unsigned32,read-only,,current,,Accumulated run hours of the dehumidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.14,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsHotGasRunHr,Unsigned32,read-only,,current,,Accumulated run hours of the hot gas system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.15,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsHotWaterRunHr,Unsigned32,read-only,,current,,Accumulated run hours of the hot water system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.16,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsFreeCoolRunHr,Unsigned32,read-only,,current,,Accumulated run hours of the free cooling process. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
.1.3.6.1.4.1.476.1.42.3.4.6.17,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsComp3RunHr,Unsigned32,read-only,,current,, Accumulated run hours of compressor 3.
.1.3.6.1.4.1.476.1.42.3.4.6.18,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvStatisticsComp4RunHr,Unsigned32,read-only,,current,, Accumulated run hours of compressor 4.
.1.3.6.1.4.1.476.1.42.3.4.7,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvPoints,,,,,,This sub-tree is used to register Liebert environmental point object identifiers.
.1.3.6.1.4.1.476.1.42.3.4.7.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvWellKnownPoints,,,,,,This sub-tree registers well known Liebert Environmental Points. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied.
.1.3.6.1.4.1.476.1.42.3.4.7.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvFanPoint,,,,,,This identifier represents a well known fan measurement point.
.1.3.6.1.4.1.476.1.42.3.4.7.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvCompressorPoint,,,,,,This identifier represents a well known compressor measurement point.
.1.3.6.1.4.1.476.1.42.3.4.7.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvElectricHeaterPoint,,,,,,This identifier represents a well known electric heater measurement point.
.1.3.6.1.4.1.476.1.42.3.4.7.1.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvChilledWaterPoint,,,,,,This identifier represents a well known chilled water measurement point.
.1.3.6.1.4.1.476.1.42.3.4.7.1.5,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHumidifierPoint,,,,,,This identifier represents a well known humidifier measurement point.
.1.3.6.1.4.1.476.1.42.3.4.7.1.6,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvDehumidifierPoint,,,,,,This identifier represents a well known dehumidifier measurement point.
.1.3.6.1.4.1.476.1.42.3.4.7.1.7,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvFreeCoolingPoint,,,,,,This identifier represents a well known free-cooling measurement process.
.1.3.6.1.4.1.476.1.42.3.4.7.1.8,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHotWaterPoint,,,,,,This identifier represents a well known hot water measurement point.
.1.3.6.1.4.1.476.1.42.3.4.7.1.9,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHotGasPoint,,,,,,This identifier represents a well known hot gas measurement point.
.1.3.6.1.4.1.476.1.42.3.4.7.1.10,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvBatteryCabinetPoint,,,,,,This identifier represents a well known cabinet point. To determine the cabinet being described in a multi-cabinet system,  this point implements two additional indexes. The first index  describes the module being supplied with battery power. The second  index identifies the number of the battery cabinet, which is  typically a sequential number. Example: lgpPwrMeasBatteryCabinet.2.4 'lgpEnvBatteryCabinetPoint' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4
.1.3.6.1.4.1.476.1.42.3.4.7.1.11,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvPumpPoints,,,,,,This sub-tree identifies well-known pumps in the system.
.1.3.6.1.4.1.476.1.42.3.4.7.1.11.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvPump1Point,,,,,,This identifier represents pump 1.
.1.3.6.1.4.1.476.1.42.3.4.7.1.11.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvPump2Point,,,,,,This identifier represents pump 2.
.1.3.6.1.4.1.476.1.42.3.4.7.1.12,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvCompressorPoints,,,,,,This sub-tree identifies well-known compressors in the system.
.1.3.6.1.4.1.476.1.42.3.4.7.1.12.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvCompressor1Point,,,,,,This identifier represents compressor 1.
.1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvCompressor1APoint,,,,,,This identifier represents compressor 1A.
.1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvCompressor1BPoint,,,,,,This identifier represents compressor 1B.
.1.3.6.1.4.1.476.1.42.3.4.7.1.12.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvCompressor2Point,,,,,,This identifier represents compressor 2.
.1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvCompressor2APoint,,,,,,This identifier represents compressor 2A.
.1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvCompressor2BPoint,,,,,,This identifier represents compressor 2B.
.1.3.6.1.4.1.476.1.42.3.4.7.1.13,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvValvePoints,,,,,,This sub-tree identifies well-known valves in the system.
.1.3.6.1.4.1.476.1.42.3.4.7.1.13.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHotGasValve1Point,,,,,,This identifier represents hot gas valve 1.
.1.3.6.1.4.1.476.1.42.3.4.7.1.13.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHotGasValve2Point,,,,,,This identifier represents hot gas valve 2.
.1.3.6.1.4.1.476.1.42.3.4.7.1.14,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorStatisticPoints,,,,,,This sub-tree identifies well-known remote sensor statistics in the system.
.1.3.6.1.4.1.476.1.42.3.4.7.1.14.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorMinimumPoint,,,,,,This identifier represents the minimum value for remote sensor readings.
.1.3.6.1.4.1.476.1.42.3.4.7.1.14.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorMaximumPoint,,,,,,This identifier represents the maximum value for remote sensor readings.
.1.3.6.1.4.1.476.1.42.3.4.7.1.14.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorAveragePoint,,,,,,This identifier represents the average value for remote sensor readings.
.1.3.6.1.4.1.476.1.42.3.4.8,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvUnits,,,,,,This sub-tree is used to register Liebert environmental unit object identifiers.
.1.3.6.1.4.1.476.1.42.3.4.8.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvWellKnownUnits,,,,,,This sub-tree registers well known Liebert Environmental Units. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied.
.1.3.6.1.4.1.476.1.42.3.4.8.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvHours,,,,,,This identifier represents well known time unit of hours.
.1.3.6.1.4.1.476.1.42.3.4.9,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensors,,,,,,This sub-tree is used to register Liebert environmental remote sensor object identifiers.
.1.3.6.1.4.1.476.1.42.3.4.9.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorCalc,INTEGER,read-write,,current,average(1):maximum(2),Calculation method applied to temperature readings from the remote sensors to determine a single temperature measurement value for cooling and heating control.
.1.3.6.1.4.1.476.1.42.3.4.9.10,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorTable,,not-accessible,,current,,This table contains a list of remote sensors attached to the environmental unit. The table contains zero, one, or more rows, depending upon the number of sensors attached to the unit.
.1.3.6.1.4.1.476.1.42.3.4.9.10.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorEntry,,not-accessible,lgpEnvRemoteSensorIndex,current,,This entry defines the attributes to be populated in the various columns of the 'lgpEnvRemoteSensorTable'.
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.1,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorIndex,Unsigned32,not-accessible,,current,,This is the index indicating the nth element of the table.
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.2,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorId,Unsigned32,read-only,,current,,This is the sensor number identifying the sensor.
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.3,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorMode,INTEGER,read-write,,current,disable(0):reference(1):control(2),Function assigned to remote sensor. When set to control(2) the sensor will be used in calculation of remote sensor temperature which may be used for heating and cooling control. When set to disable(0) the remote sensor reading is not available. When set to reference(1) the remote sensor reading is available but not used for control.
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.4,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorUsrLabel,OCTET,read-write,,current,,User assigned remote sensor label.
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.5,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorTempMeasurementDegF,Integer32,read-only,,current,,Temperature measured at the temperature sensor reported in degrees Fahrenheit.
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.6,LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvRemoteSensorTempMeasurementDegC,Integer32,read-only,,current,,Temperature measured at the temperature sensor reported in degrees Celsius.
.1.3.6.1.4.1.476.1.42.3.5,LIEBERT-GP-REGISTRATION-MIB::lgpPower,,,,,,This branch is used to register Liebert power object identifiers.
.1.3.6.1.4.1.476.1.42.3.5.1,LIEBERT-GP-POWER-MIB::lgpPwrBattery,,,,,,This sub-tree is used to register Liebert Power Battery object identifiers.
.1.3.6.1.4.1.476.1.42.3.5.1.1,LIEBERT-GP-POWER-MIB::lgpPwrNumberInstalledBatteryModules,Integer32,read-only,,current,,The number of battery modules installed in the device.
.1.3.6.1.4.1.476.1.42.3.5.1.2,LIEBERT-GP-POWER-MIB::lgpPwrNumberFailedBatteryModules,Integer32,read-only,,current,,The number of battery modules in the device that have failed.
.1.3.6.1.4.1.476.1.42.3.5.1.3,LIEBERT-GP-POWER-MIB::lgpPwrNumberRedundantBatteryModules,Integer32,read-only,,current,,The number of redundant battery modules in the device.
.1.3.6.1.4.1.476.1.42.3.5.1.4,LIEBERT-GP-POWER-MIB::lgpPwrNumberActiveBatteryModules,Integer32,read-only,,current,,The number of active battery modules in the device.
.1.3.6.1.4.1.476.1.42.3.5.1.5,LIEBERT-GP-POWER-MIB::lgpPwrConfigLowBatteryWarningTime,Integer32,read-write,,current,,The value of the device's estimated minutes of remaining battery at which a lgpEventLowBatteryWarning notification will be sent.
.1.3.6.1.4.1.476.1.42.3.5.1.6,LIEBERT-GP-POWER-MIB::lgpPwrNumberBatteryModuleWarnings,Integer32,read-only,,current,,The number of battery modules in the device that have a warning.
.1.3.6.1.4.1.476.1.42.3.5.1.7,LIEBERT-GP-POWER-MIB::lgpPwrBatteryCount,Integer32,read-only,,current,,The number of batteries installed.
.1.3.6.1.4.1.476.1.42.3.5.1.8,LIEBERT-GP-POWER-MIB::lgpPwrBatteryTestResult,INTEGER,read-only,,current,unknown(1):passed(2):failed(3):inProgress(4):systemFailure(5):inhibited(6),The outcome of the previous battery test.
.1.3.6.1.4.1.476.1.42.3.5.1.9,LIEBERT-GP-POWER-MIB::lgpPwrNominalBatteryCapacity,Integer32,read-write,,current,,The nominal battery capacity of the system (in minutes) at full load.
.1.3.6.1.4.1.476.1.42.3.5.1.10,LIEBERT-GP-POWER-MIB::lgpPwrBatteryFloatVoltage,Integer32,read-write,,current,,The battery float voltage of the system.
.1.3.6.1.4.1.476.1.42.3.5.1.11,LIEBERT-GP-POWER-MIB::lgpPwrBatteryEndOfDischargeVoltage,Integer32,read-write,,current,,The battery voltage threshold at which the batteries are considered completely discharged.
.1.3.6.1.4.1.476.1.42.3.5.1.12,LIEBERT-GP-POWER-MIB::lgpPwrAutomaticBatteryTestInterval,Integer32,read-write,,current,,The automatic battery test interval.
.1.3.6.1.4.1.476.1.42.3.5.1.13,LIEBERT-GP-POWER-MIB::lgpPwrAutomaticBatteryTestCountdown,Integer32,read-write,,current,,The time remaining before the next battery test.
.1.3.6.1.4.1.476.1.42.3.5.1.14,LIEBERT-GP-POWER-MIB::lgpPwrBatteryChargeStatus,INTEGER,read-only,,current,fullycharged(1):notfullycharged(2):charging(3):discharging(4),The present state of the system's battery charge. A value of 'charging' indicates the batteries are currently charging. A value of 'discharging' indicates the batteries are currently discharging. A value of 'fullycharged' indicates the batteries are charged to their full capacity. A value of 'notfullycharged' indicates the battery charge is neither fully charged, charging or discharging.
.1.3.6.1.4.1.476.1.42.3.5.1.15,LIEBERT-GP-POWER-MIB::lgpPwrBatteryLifeEnhancer,INTEGER,read-only,,current,on(1):off(2),The state of the battery life enhancer. When 'on', it will preserve battery life.
.1.3.6.1.4.1.476.1.42.3.5.1.16,LIEBERT-GP-POWER-MIB::lgpPwrBatteryCharger,INTEGER,read-only,,current,on(1):off(2),The state of the battery charger.
.1.3.6.1.4.1.476.1.42.3.5.1.17,LIEBERT-GP-POWER-MIB::lgpPwrBatteryChargeMode,INTEGER,read-only,,current,float(1):equalize(2),The mode of the battery charger: 'float' charging or 'equalize' charging.
.1.3.6.1.4.1.476.1.42.3.5.1.18,LIEBERT-GP-POWER-MIB::lgpPwrBatteryTimeRemaining,Integer32,read-only,,current,,An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off. NOTE: A UPS is expected to provide a battery time remaining value  when not operating on battery. However, if the system is not capable of  providing this information, then this point will return 65535 to indicate that the value is unavailable.
.1.3.6.1.4.1.476.1.42.3.5.1.19,LIEBERT-GP-POWER-MIB::lgpPwrBatteryCapacity,Integer32,read-only,,current,,The present percentage of battery capacity.
.1.3.6.1.4.1.476.1.42.3.5.1.20,LIEBERT-GP-POWER-MIB::lgpPwrBatteryCabinet,,,,,,This sub-tree contains items related to battery cabinets.
.1.3.6.1.4.1.476.1.42.3.5.1.20.1,LIEBERT-GP-POWER-MIB::lgpPwrBatteryCabinetCount,Integer32,read-write,,current,,The number of battery cabinets installed with this device. Note some devices may not permit writing a value to this object.
.1.3.6.1.4.1.476.1.42.3.5.1.20.2,LIEBERT-GP-POWER-MIB::lgpPwrBatteryCabinetType,INTEGER,read-write,,current,notSpecified(1):internal(2):external(3):lrt(4),The type of battery cabinet(s) installed on this device. Enumeration definitions: notSpecified - The type has not been specified in the device's configuration. internal - Battery cabinets are internal to the device. external - Device has external battery cabinets installed. lrt - Long Run Time cabinets. Note some devices may not permit writing a value to this object.
.1.3.6.1.4.1.476.1.42.3.5.1.20.3,LIEBERT-GP-POWER-MIB::lgpPwrBatteryCabinetRatedCapacity,Integer32,read-write,,current,,Battery cabinet rated capacity (tenths of Amp-hours). This assumes that each cabinet is of the same type and capacity. This is not a sum of the rating for all attached cabinets. Note some devices may not permit writing a value to this object.
.1.3.6.1.4.1.476.1.42.3.5.1.20.4,LIEBERT-GP-POWER-MIB::lgpPwrBatteryLeadAcidCellCount,Integer32,read-write,,current,,Battery cell count - lead-acid. The number of cells that comprise  the lead acid battery string.
.1.3.6.1.4.1.476.1.42.3.5.1.20.5,LIEBERT-GP-POWER-MIB::lgpPwrBatteryNiCadCellCount,Integer32,read-write,,current,,Battery cell count - nickel-cadmium. The number of cells that  comprise the nickel-cadmium battery string.
.1.3.6.1.4.1.476.1.42.3.5.1.21,LIEBERT-GP-POWER-MIB::lgpPwrBatteryAmpHoursConsumed,Integer32,read-write,,current,,The cumulative battery Amp-hours withdrawn over the life of the battery. This value persists across reboots. Typically, this value is reset back to zero when the batteries are replaced.
.1.3.6.1.4.1.476.1.42.3.5.1.22,LIEBERT-GP-POWER-MIB::lgpPwrBatteryAmpHoursDischargeConsumed,Integer32,read-write,,current,,The battery Amp-hours withdrawn during the current/latest discharge. This value does not persist across reboots.
.1.3.6.1.4.1.476.1.42.3.5.1.23,LIEBERT-GP-POWER-MIB::lgpPwrBatteryLastDischargeTime,Unsigned32,read-write,,current,,The date and time of the last battery discharge. Typically this is the time when the discharge starts. This value persists across reboots.  The date and time are determined in seconds since the epoch on  January 1, 1970.
.1.3.6.1.4.1.476.1.42.3.5.1.24,LIEBERT-GP-POWER-MIB::lgpPwrBatteryLastCommissionTime,Unsigned32,read-write,,current,,The date and time when the battery system was put into service. This information persists across system reboot events. It is the responsibility of Service to reset this date/time when the batteries are replaced. The date and time are determined in seconds since the  epoch on January 1, 1970.
.1.3.6.1.4.1.476.1.42.3.5.1.25,LIEBERT-GP-POWER-MIB::lgpPwrBatteryPresentDischargeTime,Integer32,read-only,,current,,The total time spent on battery during the current or last discharge. NOTE: While not discharging, some systems may display zero instead of the last discharge.
.1.3.6.1.4.1.476.1.42.3.5.1.26,LIEBERT-GP-POWER-MIB::lgpPwrBatteryCapacityStatus,INTEGER,read-only,,current,unknown(1):batteryNormal(2):batteryLow(3):batteryDepleted(4),The indication of the capacity remaining in the UPS system's batteries. NOTE: In a single-module system, this point is intended to have the same  behavior as the RFC1628 point upsBatteryStatus.
.1.3.6.1.4.1.476.1.42.3.5.1.27,LIEBERT-GP-POWER-MIB::lgpPwrBatteryCircuitBreakerState,INTEGER,read-only,,current,unknown(0):open(1):closed(2),The state of the Battery Circuit Breaker.
.1.3.6.1.4.1.476.1.42.3.5.2,LIEBERT-GP-POWER-MIB::lgpPwrMeasurements,,,,,,This sub-tree registers Liebert Power Measurement object identifiers. The sub-tree contains tables and well known power measurement points.
.1.3.6.1.4.1.476.1.42.3.5.2.1,LIEBERT-GP-POWER-MIB::lgpPwrWellKnownMeasurementPoints,,,,,,This sub-tree registers well known Liebert Power Measurement Points. The object identifier names usually imply locations where the measurement is taken -- such as 'input', 'output' and 'bypass'.
.1.3.6.1.4.1.476.1.42.3.5.2.1.1,LIEBERT-GP-POWER-MIB::lgpPwrSource1Input,,,,,,This sub-tree is used to register a source 1 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power source 1. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSource1Input' etc. may depend on the physical wiring of the system when it was installed.
.1.3.6.1.4.1.476.1.42.3.5.2.1.2,LIEBERT-GP-POWER-MIB::lgpPwrSource2Input,,,,,,This sub-tree is used to register a source 2 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power source 2. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSource2Input' etc. may depend on the physical wiring of the system when it was installed.
.1.3.6.1.4.1.476.1.42.3.5.2.1.3,LIEBERT-GP-POWER-MIB::lgpPwrSourcePdu1Input,,,,,,This sub-tree is used to register a source PDU 1 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power distribution unit 1. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSourcePdu1Input' etc. may depend on the physical wiring of the system when it was installed.
.1.3.6.1.4.1.476.1.42.3.5.2.1.4,LIEBERT-GP-POWER-MIB::lgpPwrSourcePdu2Input,,,,,,This sub-tree is used to register a source PDU 2 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power distribution unit 1. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSourcePdu2Input' etc. may depend on the physical wiring of the system when it was installed.
.1.3.6.1.4.1.476.1.42.3.5.2.1.5,LIEBERT-GP-POWER-MIB::lgpPwrOutputToLoad,,,,,,This sub-tree is used to register the output to the critical load as a well known measurement point. It is intended that no sub-trees be created below this node.
.1.3.6.1.4.1.476.1.42.3.5.2.1.6,LIEBERT-GP-POWER-MIB::lgpPwrMeasBattery,,,,,,This sub-tree is used to register a battery as a well known measurement point. It is intended that no sub-trees be created below this node.
.1.3.6.1.4.1.476.1.42.3.5.2.1.7,LIEBERT-GP-POWER-MIB::lgpPwrMeasBypass,,,,,,This sub-tree is used to register a bypass as a well known measurement point. It is intended that no sub-trees be created below this node.
.1.3.6.1.4.1.476.1.42.3.5.2.1.8,LIEBERT-GP-POWER-MIB::lgpPwrMeasDcBus,,,,,,This sub-tree is used to register a DC bus as a well known measurement point. It is intended that no sub-trees be created below this node.
.1.3.6.1.4.1.476.1.42.3.5.2.1.9,LIEBERT-GP-POWER-MIB::lgpPwrMeasSystemOutput,,,,,,This sub-tree is used to register the output of a multi-module system as a well known measurement point. It is intended that no sub-trees be created below this node. This identifier represents the power related data of the system.
.1.3.6.1.4.1.476.1.42.3.5.2.1.10,LIEBERT-GP-POWER-MIB::lgpPwrMeasBatteryCabinet,,,,,,This sub-tree is used to register the voltage between the  most negative and the most postive terminals of a battery cabinet. To determine the cabinet being described in a multi-cabinet system, this point implements an additional two indexes. The first index describes the module the cabinet is located in. The second index describes the cabinet number. In an SMS(Single-Module System) the first index is always 1. Example: lgpPwrMeasBatteryCabinet.2.4 'lgpPwrMeasBatteryCabinet' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4
.1.3.6.1.4.1.476.1.42.3.5.2.2,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointTable,,not-accessible,,current,,This table contains a list of AC power measurement point entries. The table contains zero, one, or many rows, depending upon the number of power related measurement points available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. Each row in the table represents a series of measurements on a given point or location within the system. Measurement points/locations are identified by the object identifier 'lgpPwrMeasurementPointId' in the 'LgpPwrMeasurementPointEntry' object. The actual measurement being taken at that identified point is identified by the other corresponding columns in the LgpPwrMeasurementPointEntry for the particular row of the table.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointEntry,,not-accessible,lgpPwrMeasurementPointIndex,current,,This entry defines the measurements to be populated in the various columns of the 'lgpPwrMeasurementPointTable'.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.1,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointIndex,Unsigned32,not-accessible,,current,,This is the index that indicates the row of the 'lgpPwrMeasurementPointTable' for a power measurement point.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.2,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointId,OBJECT,read-only,,current,,An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's name usually implies a location of the measurement point such as 'input', 'output', 'bypass' etc.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.3,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNumLines,Integer32,read-only,,current,,The number of lines on the indicated power measurement point. (i.e. the number of phases on the power source being measured.)
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.4,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomVolts,Integer32,read-only,,current,,The magnitude of the nominal voltage on the power source being measured.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.5,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomFrequency,Integer32,read-only,,current,,The nominal or configured/expected frequency for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.6,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointFrequency,Integer32,read-only,,current,,The present (actual) frequency for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.7,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointApparentPower,Integer32,read-only,,current,,The present apparent AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.8,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointTruePower,Integer32,read-only,,current,,The present AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.9,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointPowerFactor,Integer32,read-only,,current,,The present Power Factor for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.10,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointWattHours,Integer32,read-only,,current,,The present number of Watt Hours for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.11,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointVAPercent,Integer32,read-only,,current,,The percentage of the rated apparent AC power of the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.12,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNeutralCurrent,Integer32,read-only,,current,,The present neutral current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.13,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointGroundCurrent,Integer32,read-only,,current,,The present ground current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.14,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomCurrent,Integer32,read-only,,current,,The nominal or configured/expected current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.15,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomPowerFactor,Integer32,read-only,,current,,The nominal or configured/expected power factor of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.16,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomVA,Integer32,read-write,,current,,The nominal or configured/expected apparent AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.17,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomW,Integer32,read-write,,current,,The nominal or configured/expected true AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.19,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointPowerFactorTag,INTEGER,read-only,,current,leading(1):lagging(2),The present description of the Power Factor for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable. If Leading, the load is said to be capacitive and the phase of the current leads the voltage. If Lagging, the load is said to be inductive and the phase of the current lags the voltage.
.1.3.6.1.4.1.476.1.42.3.5.2.3,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementTable,,not-accessible,,current,,A list of power measurements for each phase/line for a given power measurement point/location in the 'lgpPwrMeasurementPointTable'. The lgpPwrMeasurementPointIndex in this table corresponds to the index in the lgpPwrMeasurementPointTable. This table contains zero, one, or many rows, depending upon the number of power line source objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementEntry,,not-accessible,lgpPwrMeasurementPtIndex:lgpPwrLineMeasurementIndex,current,,This entry defines the contents of the columns for the table 'lgpPwrLineMeasurementTable'.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.1,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPtIndex,Unsigned32,not-accessible,,current,,This is the index indicating the row of the table 'lgpPwrMeasurementPointTable' for a power measurement point.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.2,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementIndex,Unsigned32,not-accessible,,current,,This is the index indicating the row of the table 'lgpPwrLineMeasurementTable' for a power measurement point.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.3,LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPoint,OBJECT,read-only,,current,,An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID name usually implies a location of the measurement point such as 'input', 'output', 'bypass', etc.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.4,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLL,Integer32,read-only,,current,,The present Line-to-Line voltage measurement for the indicated source. The line being measured is given by the lgpPwrLineMeasurementIndex [1 = AB, 2 = BC, 3 = CA].
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.5,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLN,Integer32,read-only,,current,,The present Line-to-neutral voltage measurement for the indicated source. The line being measured is given by the lgpPwrLineMeasurementIndex where [1 = A, 2 = B, 3 = C].
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.6,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementCurrent,Integer32,read-only,,current,,The present current measurement for the indicated source. The line being measured is given by the 'lgpPwrLineMeasurementIndex' where [1 = A, 2 = B, 3 = C].
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.7,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementCapacity,Integer32,read-only,,current,,The percentage of the power capacity presently being used on this line.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.8,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVA,Integer32,read-only,,current,,The present apparent AC line power.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.9,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementTruePower,Integer32,read-only,,current,,The present AC line power measured in watts.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.10,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltageTHD,Integer32,read-only,,current,,The present total harmonic distortion on the AC line voltage.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.11,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementCurrentTHD,Integer32,read-only,,current,,The present total harmonic distortion on the AC line current.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.12,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementKFactorCurrent,Integer32,read-only,,current,,The present line K Factor.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.13,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementCrestFactorCurrent,Integer32,read-only,,current,,The present crest factor of the line current.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.14,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementPowerFactor,Integer32,read-only,,current,,The present Power Factor for the line.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.15,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementPowerFactorTag,INTEGER,read-only,,current,leading(1):lagging(2),The present description of the Power Factor for the line. If Leading, the load is said to be capacitive and the phase of the current leads the voltage. If Lagging, the load is said to be inductive and the phase of the current lags the voltage.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.16,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementMaxVolts,Integer32,read-only,,current,,The maximum voltage measurement recorded for the indicated source since the command 'lgpPwrStatisticsReset' was executed.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.17,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementMinVolts,Integer32,read-only,,current,,The minimum voltage measurement recorded for the indicated source since the command 'lgpPwrStatisticsReset' was executed.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.18,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVAR,Integer32,read-only,,current,,The present reactive AC line power of the power source indicated by 'lgpPwrMeasurementPoint'.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.19,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementPercentLoad,Integer32,read-only,,current,,The present percent load of the AC line power.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.20,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVolts,Integer32,read-only,,current,,The present voltage measurement for the indicated source.
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.21,LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVACapacity,Integer32,read-only,,current,,The percentage of the apparent power capacity presently being used on this line.
.1.3.6.1.4.1.476.1.42.3.5.2.4,LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointTable,,not-accessible,,current,,This table contains a list of DC power measurement point entries. The table contains zero, one, or many rows, depending upon the number of power related measurement points available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. Each row in the table represents a series of measurements on a given point or location within the system. Measurement points/locations are identified by the object identifier 'lgpPwrDcMeasurementPointId' in the 'LgpPwrDcMeasurementPointEntry' object. The actual measurement being taken at that identified point is identified by the other corresponding columns in the LgpPwrDcMeasurementPointEntry for the particular row of the table.
.1.3.6.1.4.1.476.1.42.3.5.2.4.1,LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointEntry,,not-accessible,lgpPwrDcMeasurementPointIndex,current,,This entry defines the measurements to be populated in the various columns of the 'lgpPwrDcMeasurementPointTable'.
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.1,LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointIndex,Unsigned32,not-accessible,,current,,This is the index that indicates the row of the 'lgpPwrMeasurementPointTable' for a power measurement point.
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.2,LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointId,OBJECT,read-only,,current,,An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's name usually implies a location of the measurement point such as 'input', 'output', 'bypass' etc.
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.3,LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointSubID,Integer32,read-only,,current,,The identifier used to differentiate between identical thresholds for a given point index and point ID in the DC measurements table.
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.4,LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointVolts,Integer32,read-only,,current,,The present DC voltage for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.5,LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointCurrent,Integer32,read-only,,current,,The present DC current for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.6,LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointNomVolts,Integer32,read-only,,current,,The nominal(configured/expected) DC voltage for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.7,LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointTruePower,Integer32,read-only,,current,,The present DC power for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
.1.3.6.1.4.1.476.1.42.3.5.2.5,LIEBERT-GP-POWER-MIB::lgpPwrWellKnownMeasurementTypes,,,,,,This sub-tree registers well known Liebert Power Measurement Types. The object identifier names usually encompass units of measure, lines of reference, and device location. The OID's name usually implies a measurement type such as 'voltsAC', 'current', 'voltsDc', 'VoltsLL', etc.
.1.3.6.1.4.1.476.1.42.3.5.2.5.1,LIEBERT-GP-POWER-MIB::lgpPwrVoltsAc,,,,,,This identifier represents an AC voltage.
.1.3.6.1.4.1.476.1.42.3.5.2.5.2,LIEBERT-GP-POWER-MIB::lgpPwrVoltsDc,,,,,,This identifier represents a DC voltage.
.1.3.6.1.4.1.476.1.42.3.5.2.5.3,LIEBERT-GP-POWER-MIB::lgpPwrAmpsNeutral,,,,,,This identifier represents a current measurement in Amps on the neutral line.
.1.3.6.1.4.1.476.1.42.3.5.3,LIEBERT-GP-POWER-MIB::lgpPwrStatus,,,,,,This sub-tree registers Liebert Power Status object identifiers. This is the location of power related status information that does not fit into a more specific category such as the lgpPwrConversion sub-tree.
.1.3.6.1.4.1.476.1.42.3.5.3.1,LIEBERT-GP-POWER-MIB::lgpPwrTransferCount,Integer32,read-only,,current,,Number of times that the output load has been transferred between the available input sources.
.1.3.6.1.4.1.476.1.42.3.5.3.2,LIEBERT-GP-POWER-MIB::lgpPwrAutoTransferTimer,Integer32,read-only,,current,,The required wait time between output load auto transfer attempts between available input sources.
.1.3.6.1.4.1.476.1.42.3.5.3.3,LIEBERT-GP-POWER-MIB::lgpPwrAutoReTransferEnabled,INTEGER,read-only,,current,no(0):yes(1),The ability to retransfer the output load automatically to the well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is the preferred input source of the system
.1.3.6.1.4.1.476.1.42.3.5.3.4,LIEBERT-GP-POWER-MIB::lgpPwrSyncPhaseAngle,Integer32,read-only,,current,,The phase angle difference of source 1 in relation to source 2.
.1.3.6.1.4.1.476.1.42.3.5.3.5,LIEBERT-GP-POWER-MIB::lgpPwrParallelSystemOutputToLoadSource,INTEGER,read-only,,current,unknown(0):utility(1):battery(2):bypass(3):none(4),The source supporting the parallel system's load.
.1.3.6.1.4.1.476.1.42.3.5.3.6,LIEBERT-GP-POWER-MIB::lgpPwrDcToDcConverter,INTEGER,read-only,,current,on(1):off(2),The state of the DC to DC converter.
.1.3.6.1.4.1.476.1.42.3.5.3.7,LIEBERT-GP-POWER-MIB::lgpPwrOutputToLoadOnInverter,INTEGER,read-only,,current,yes(1):no(2),The present source of output power is the Inverter.
.1.3.6.1.4.1.476.1.42.3.5.3.8,LIEBERT-GP-POWER-MIB::lgpPwrBatteryChargeCompensating,INTEGER,read-only,,current,yes(1):no(2),The system is adjusting the battery charging algorithm to accommodate for the battery temperature.
.1.3.6.1.4.1.476.1.42.3.5.3.9,LIEBERT-GP-POWER-MIB::lgpPwrInverterReady,INTEGER,read-only,,current,yes(1):no(2),The ability of the inverter to support the output load of the system.
.1.3.6.1.4.1.476.1.42.3.5.3.10,LIEBERT-GP-POWER-MIB::lgpPwrOutputToLoadOnBypass,INTEGER,read-only,,current,yes(1):no(2),The present source of output power is the Bypass.
.1.3.6.1.4.1.476.1.42.3.5.3.11,LIEBERT-GP-POWER-MIB::lgpPwrBoost,INTEGER,read-only,,current,on(1):off(2),The present state of the boost circuitry
.1.3.6.1.4.1.476.1.42.3.5.3.12,LIEBERT-GP-POWER-MIB::lgpPwrBuck,INTEGER,read-only,,current,on(1):off(2),The present state of the buck circuitry
.1.3.6.1.4.1.476.1.42.3.5.3.13,LIEBERT-GP-POWER-MIB::lgpPwrShutdownOverTemperature,INTEGER,read-only,,current,yes(1):no(2),The system has previously shutdown due to an over temperature condition.
.1.3.6.1.4.1.476.1.42.3.5.3.14,LIEBERT-GP-POWER-MIB::lgpPwrShutdownOverload,INTEGER,read-only,,current,yes(1):no(2),The system has previously shutdown due to an over load condition.
.1.3.6.1.4.1.476.1.42.3.5.3.15,LIEBERT-GP-POWER-MIB::lgpPwrShutdownDcBusOverload,INTEGER,read-only,,current,yes(1):no(2),The system has previously shutdown due to a DC bus over load condition.
.1.3.6.1.4.1.476.1.42.3.5.3.16,LIEBERT-GP-POWER-MIB::lgpPwrShutdownOutputShort,INTEGER,read-only,,current,yes(1):no(2),The system has previously shutdown due to an output short condition.
.1.3.6.1.4.1.476.1.42.3.5.3.17,LIEBERT-GP-POWER-MIB::lgpPwrShutdownLineSwap,INTEGER,read-only,,current,yes(1):no(2),The system has previously shutdown due to a condition where the line and neutral were reversed.
.1.3.6.1.4.1.476.1.42.3.5.3.18,LIEBERT-GP-POWER-MIB::lgpPwrShutdownLowBattery,INTEGER,read-only,,current,yes(1):no(2),The system has previously shutdown due to a low battery condition.
.1.3.6.1.4.1.476.1.42.3.5.3.19,LIEBERT-GP-POWER-MIB::lgpPwrShutdownRemote,INTEGER,read-only,,current,yes(1):no(2),The system has previously shutdown due to a remote shutdown command.
.1.3.6.1.4.1.476.1.42.3.5.3.20,LIEBERT-GP-POWER-MIB::lgpPwrShutdownInputUnderVoltage,INTEGER,read-only,,current,yes(1):no(2),The system has previously shutdown due to an under voltage condition during startup.
.1.3.6.1.4.1.476.1.42.3.5.3.21,LIEBERT-GP-POWER-MIB::lgpPwrShutdownPowerFactorCorrectionFailure,INTEGER,read-only,,current,yes(1):no(2),The system has previously shutdown due to a power factor correction startup failure.
.1.3.6.1.4.1.476.1.42.3.5.3.22,LIEBERT-GP-POWER-MIB::lgpPwrShutdownHardware,INTEGER,read-only,,current,yes(1):no(2),The system has previously shutdown due external shutdown signal.
.1.3.6.1.4.1.476.1.42.3.5.3.23,LIEBERT-GP-POWER-MIB::lgpPwrRedundantSubModule,INTEGER,read-only,,current,yes(1):no(2),The system has a redundant battery module installed.
.1.3.6.1.4.1.476.1.42.3.5.3.24,LIEBERT-GP-POWER-MIB::lgpPwrBypassReady,INTEGER,read-only,,current,yes(1):no(2),The ability of the bypass to support the output load of the system. If Yes, the bypass is available to transfer to.
.1.3.6.1.4.1.476.1.42.3.5.3.25,LIEBERT-GP-POWER-MIB::lgpPwrGeneratorStatus,INTEGER,read-only,,current,connected(1):disconnected(2),The state of the system generator.
.1.3.6.1.4.1.476.1.42.3.5.3.26,LIEBERT-GP-POWER-MIB::lgpPwrRotaryBreakerStatus,INTEGER,read-only,,current,unknown(1):closed(2):test(3):normal(4):bypass(5):maintenance(6),The state of the system rotary breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.27,LIEBERT-GP-POWER-MIB::lgpPwrPowerFactorCorrection,INTEGER,read-only,,current,on(1):off(2),The state of the power factor correction circuitry of the system.
.1.3.6.1.4.1.476.1.42.3.5.3.28,LIEBERT-GP-POWER-MIB::lgpPwrBypassSyncDiff,Integer32,read-only,,current,,The phase angle difference between the inverter output and bypass source. A positive value means the inverter leads the bypass source. A negative value means the inverter lags the bypass source.
.1.3.6.1.4.1.476.1.42.3.5.3.29,LIEBERT-GP-POWER-MIB::lgpPwrBypassOverloadShutdownTime,Integer32,read-only,,current,,The calculated time remaining before bypass static switch shutdown due to the present overload condition. If the bypass is not in an overload condition, this object returns -1.
.1.3.6.1.4.1.476.1.42.3.5.3.30,LIEBERT-GP-POWER-MIB::lgpPwrInverterOverloadShutdownTime,Integer32,read-only,,current,,The calculated time remaining before inverter shutdown. The calculated time of inverter operation remaining for the present overload event. Note: If the inverter is not experiencing an overload event this point will return 65535 indicating this value is unavailable.
.1.3.6.1.4.1.476.1.42.3.5.3.31,LIEBERT-GP-POWER-MIB::lgpPwrStateOutputSource,INTEGER,read-only,,current,none(1):inverter(2):bypass(3):maintenanceBypass(4),The UPS's output power source (inverter, bypass, or none). NOTE: It is possible that the load still has power from the  Maintenance Bypass.
.1.3.6.1.4.1.476.1.42.3.5.3.32,LIEBERT-GP-POWER-MIB::lgpPwrStateInputSource,INTEGER,read-only,,current,none(1):utility(2):generator(3),The system input power source (none, utility, generator).
.1.3.6.1.4.1.476.1.42.3.5.3.33,LIEBERT-GP-POWER-MIB::lgpPwrStateInputQualification,INTEGER,read-only,,current,fail(1):marginalLow(2):normal(3):marginalHigh(4),The current state of the system input. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states.
.1.3.6.1.4.1.476.1.42.3.5.3.34,LIEBERT-GP-POWER-MIB::lgpPwrStateBypassStaticSwitchState,INTEGER,read-only,,current,on(1):off(2),The current state of the bypass static switch.
.1.3.6.1.4.1.476.1.42.3.5.3.35,LIEBERT-GP-POWER-MIB::lgpPwrStateBypassQualification,INTEGER,read-only,,current,fail(1):marginalLow(2):normal(3):marginalHigh(4),The current operational state of the bypass static switch. The unit may  or may not operate normally under 'marginalLow' and 'marginalHigh' states.
.1.3.6.1.4.1.476.1.42.3.5.3.36,LIEBERT-GP-POWER-MIB::lgpPwrStateDCBusQualification,INTEGER,read-only,,current,fail(1):marginalLow(2):normal(3):marginalHigh(4),The current operational state of the DC bus. The unit may or may not  operate normally under 'marginalLow' and 'marginalHigh' states.
.1.3.6.1.4.1.476.1.42.3.5.3.37,LIEBERT-GP-POWER-MIB::lgpPwrStateOutQualification,INTEGER,read-only,,current,fail(1):marginalLow(2):normal(3):marginalHigh(4),The current operational state of the output. The unit may or may not  operate normally under 'marginalLow' and 'marginalHigh' states.
.1.3.6.1.4.1.476.1.42.3.5.3.38,LIEBERT-GP-POWER-MIB::lgpPwrStateInverterQualification,INTEGER,read-only,,current,fail(1):marginalLow(2):normal(3):marginalHigh(4),The current operational state of the inverter. The unit may or may not  operate normally under 'marginalLow' and 'marginalHigh' states.
.1.3.6.1.4.1.476.1.42.3.5.3.39,LIEBERT-GP-POWER-MIB::lgpPwrStateInverterState,INTEGER,read-only,,current,on(1):off(2),The current state of the inverter.
.1.3.6.1.4.1.476.1.42.3.5.3.40,LIEBERT-GP-POWER-MIB::lgpPwrStateRectifierState,INTEGER,read-only,,current,on(1):off(2),The current state of the rectifier.
.1.3.6.1.4.1.476.1.42.3.5.3.41,LIEBERT-GP-POWER-MIB::lgpPwrStateModuleGroup,,,,,,This group contains UPS module information.
.1.3.6.1.4.1.476.1.42.3.5.3.41.1,LIEBERT-GP-POWER-MIB::lgpPwrStateUpsModuleCount,Integer32,read-write,,current,,Number of UPS modules in the system. In a single module system, this value is one.
.1.3.6.1.4.1.476.1.42.3.5.3.41.2,LIEBERT-GP-POWER-MIB::lgpPwrStateUpsModuleRedundantCount,Integer32,read-only,,current,,Number of redundant UPS modules in the system. In a single module system, the value is zero. This value is dependent upon the present load and the number of modules (i.e. the value may change during normal operation based upon a load change). This value represents the number of extra modules above the minimum needed to support the load.
.1.3.6.1.4.1.476.1.42.3.5.3.42,LIEBERT-GP-POWER-MIB::lgpPwrStateBackfeedBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The state of the Static Bypass Switch Line Disconnect Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.43,LIEBERT-GP-POWER-MIB::lgpPwrStateLoadDisconnectState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The state of the Static Bypass Switch Load Disconnect Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.44,LIEBERT-GP-POWER-MIB::lgpPwrStateInputBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The state of the Input Disconnect Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.45,LIEBERT-GP-POWER-MIB::lgpPwrStateTrapFilterBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The state of the Trap Filter Disconnect Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.46,LIEBERT-GP-POWER-MIB::lgpPwrStateInvOutputBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The state of the Inverter Output Disconnect Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.47,LIEBERT-GP-POWER-MIB::lgpPwrStateIntBypassBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The state of the Internal Bypass Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.48,LIEBERT-GP-POWER-MIB::lgpPwrStateBypassIsolBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The state of the Bypass Isolation Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.49,LIEBERT-GP-POWER-MIB::lgpPwrStateRectifierIsolBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The state of the Rectifier Isolation Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.50,LIEBERT-GP-POWER-MIB::lgpPwrStateMaintBypassBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The state of the Maintenance Bypass Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.51,LIEBERT-GP-POWER-MIB::lgpPwrStateMaintIsolBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The state of the Maintenance Isolation Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.52,LIEBERT-GP-POWER-MIB::lgpPwrStateOutStaticSwState,INTEGER,read-only,,current,off(1):on(2):notInstalled(3),The state of the Output Series Static Switch.
.1.3.6.1.4.1.476.1.42.3.5.3.53,LIEBERT-GP-POWER-MIB::lgpPwrStateModuleOutBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The state of the Module Output Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.54,LIEBERT-GP-POWER-MIB::lgpPwrBypassReXfrRemainTime,Integer32,read-only,,current,,The time remaining before an inverter overload or inverter fault can  be cleared and auto retransfer from the bypass to the inverter can take  place.  Note: If an inverter overload or fault is not taking place, this point will return 65535.
.1.3.6.1.4.1.476.1.42.3.5.3.55,LIEBERT-GP-POWER-MIB::lgpPwrStateUpsOutputSource,INTEGER,read-only,,current,other(1):none(2):normal(3):bypass(4):battery(5):booster(6):reducer(7),The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. NOTE: In a single-module system, this point is intended to have the same  behavior as the RFC1628 point upsOutputSource.
.1.3.6.1.4.1.476.1.42.3.5.3.56,LIEBERT-GP-POWER-MIB::lgpPwrStateLoadBusSynchronization,INTEGER,read-only,,current,unknown(0):active(1):abnormal(2),The state of the Load Bus Synchronizer (LBS).
.1.3.6.1.4.1.476.1.42.3.5.3.57,LIEBERT-GP-POWER-MIB::lgpPwrStateCircuitBrkrStateGroup,,,,,,This group contains Static Switch circuit breaker state information.
.1.3.6.1.4.1.476.1.42.3.5.3.57.1,LIEBERT-GP-POWER-MIB::lgpPwrStateSource1InputBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The states of Source 1 Input Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.57.2,LIEBERT-GP-POWER-MIB::lgpPwrStateSource2InputBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The states of Source 2 Input Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.57.3,LIEBERT-GP-POWER-MIB::lgpPwrStateSource1BypassBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The states of Source 1 Bypass Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.57.4,LIEBERT-GP-POWER-MIB::lgpPwrStateSource2BypassBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The states of Source 2 Bypass Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.57.5,LIEBERT-GP-POWER-MIB::lgpPwrStateOutputBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The states of Output Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.57.6,LIEBERT-GP-POWER-MIB::lgpPwrStateAuxOutputBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The states of Auxiliary Output Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.57.7,LIEBERT-GP-POWER-MIB::lgpPwrStateSource1PduInputBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The states of Source 1 PDU Input Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.57.8,LIEBERT-GP-POWER-MIB::lgpPwrStateSource2PduInputBrkrState,INTEGER,read-only,,current,open(1):closed(2):notInstalled(3),The states of Source 2 PDU Input Breaker.
.1.3.6.1.4.1.476.1.42.3.5.3.58,LIEBERT-GP-POWER-MIB::lgpPwrEconomicOperation,INTEGER,read-only,,current,off(0):on(1),The present state of ECO mode operation, on(1) if system is on bypass due to ECO mode operation, off(0) any other time.
.1.3.6.1.4.1.476.1.42.3.5.4,LIEBERT-GP-POWER-MIB::lgpPwrSettings,,,,,,This sub-tree registers Liebert Power Static Switch object identifiers.
.1.3.6.1.4.1.476.1.42.3.5.4.1,LIEBERT-GP-POWER-MIB::lgpPwrPreferredSource,OBJECT,read-only,,current,,The well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is the preferred input source of the system.
.1.3.6.1.4.1.476.1.42.3.5.4.2,LIEBERT-GP-POWER-MIB::lgpPwrLoadOnSource,OBJECT,read-only,,current,,The well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is currently powering the output (load).
.1.3.6.1.4.1.476.1.42.3.5.4.3,LIEBERT-GP-POWER-MIB::lgpPwrNominalVoltageDeviation,Integer32,read-only,,current,,The nominal voltage deviation between the well known measurement source lgpPwrSource1Input and lgpPwrSource2Input.
.1.3.6.1.4.1.476.1.42.3.5.4.4,LIEBERT-GP-POWER-MIB::lgpPwrNominalVoltageDeviationPercent,Integer32,read-only,,current,,The percentage of the nominal voltage deviation between the well known measurement source lgpPwrSource1Input and lgpPwrSource2Input.
.1.3.6.1.4.1.476.1.42.3.5.4.5,LIEBERT-GP-POWER-MIB::lgpPwrPhaseDifferenceLimit,Integer32,read-only,,current,,The maximum phase difference (between the well known input sources ) in which a transfer to an available input source is permitted.
.1.3.6.1.4.1.476.1.42.3.5.4.6,LIEBERT-GP-POWER-MIB::lgpPwrFrequencyDeviationLimit,Integer32,read-only,,current,,The maximum frequency deviation (between the well known input sources ) in which a transfer to an available input source is permitted.
.1.3.6.1.4.1.476.1.42.3.5.4.7,LIEBERT-GP-POWER-MIB::lgpPwrThresholdTable,,not-accessible,,current,,A list of power thresholds for a given power measurement at a point/location in the system. The lgpPwrThresholdType in this table corresponds to the type of measurement the high and low thresholds applies to. This table contains zero, one, or many rows, depending upon the number of 'lgpPwrThresholdPoint' and 'lgpPwrThresholdSubID' available in the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
.1.3.6.1.4.1.476.1.42.3.5.4.7.1,LIEBERT-GP-POWER-MIB::lgpPwrThresholdEntry,,not-accessible,lgpPwrThresholdIndex,current,,This entry defines the contents of the columns for the table 'lgpPwrThresholdTable'.
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.1,LIEBERT-GP-POWER-MIB::lgpPwrThresholdIndex,Unsigned32,not-accessible,,current,,This is the index indicating the row of the table 'lgpPwrLineMeasurementTable' for a power measurement point.
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.2,LIEBERT-GP-POWER-MIB::lgpPwrThresholdPoint,OBJECT,read-only,,current,,An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's name usually implies a location of the measurement point such as 'input', 'output', 'bypass' etc.
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.3,LIEBERT-GP-POWER-MIB::lgpPwrThresholdSubID,Unsigned32,read-only,,current,,This is a sub identifier for the 'lgpPwrThresholdPoint'. It indicates the instance number of the well known threshold point.
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.4,LIEBERT-GP-POWER-MIB::lgpPwrThresholdType,OBJECT,read-only,,current,,An OID representing a well known measurement type. These object identifiers indicate the type of measurement referenced by the row of the table. These object identifiers can encompass units of measure, lines of reference, and device location. The OID's name usually implies a measurement type such as 'voltsAc', 'current', 'voltsDc', 'VoltsLL', etc.
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.5,LIEBERT-GP-POWER-MIB::lgpPwrThresholdHighWarning,Integer32,read-write,,current,,The high warning threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification.
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.6,LIEBERT-GP-POWER-MIB::lgpPwrThresholdHighFailure,Integer32,read-write,,current,,The high failure threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification.
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.7,LIEBERT-GP-POWER-MIB::lgpPwrThresholdLowWarning,Integer32,read-write,,current,,The low warning threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification.
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.8,LIEBERT-GP-POWER-MIB::lgpPwrThresholdLowFailure,Integer32,read-write,,current,,The low failure threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification.
.1.3.6.1.4.1.476.1.42.3.5.4.8,LIEBERT-GP-POWER-MIB::lgpPwrUpsAutoRestart,INTEGER,read-write,,current,on(1):off(2),The device will automatically restart when utility power is restored following a battery discharge.
.1.3.6.1.4.1.476.1.42.3.5.4.9,LIEBERT-GP-POWER-MIB::lgpPwrUpsAutoRestartDelay,Integer32,read-write,,current,,The device will automatically delay a certain number of seconds and then restart after utility power is restored following a battery discharge. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals.
.1.3.6.1.4.1.476.1.42.3.5.4.10,LIEBERT-GP-POWER-MIB::lgpPwrAutoRestartBatteryChargeThreshold,Integer32,read-write,,current,,The battery charge percentage required before the device can automatically restart.
.1.3.6.1.4.1.476.1.42.3.5.4.11,LIEBERT-GP-POWER-MIB::lgpPwrParallelModuleCount,Integer32,read-write,,current,,The number of modules in the parallel system.
.1.3.6.1.4.1.476.1.42.3.5.4.12,LIEBERT-GP-POWER-MIB::lgpPwrParallelRedundancyCount,Integer32,read-write,,current,,The number of redundant modules in the parallel system.
.1.3.6.1.4.1.476.1.42.3.5.4.13,LIEBERT-GP-POWER-MIB::lgpPwrLoadBusSyncMode,INTEGER,read-write,,current,master(1):slave(2):none(3),The configuration of Load Bus Synchronization (LBS) between independent systems.
.1.3.6.1.4.1.476.1.42.3.5.4.14,LIEBERT-GP-POWER-MIB::lgpPwrEconomicOperationMode,INTEGER,read-write,,current,on(1):off(2),The configuration of the economic operation mode of the system.
.1.3.6.1.4.1.476.1.42.3.5.4.15,LIEBERT-GP-POWER-MIB::lgpPwrAutomaticBatteryTest,INTEGER,read-write,,current,on(1):off(2),Automatic battery test option. If enabled, the battery will be tested on a fixed interval. If disabled, the battery test must be initiated by a battery test command. The interval at which a battery test is performed is defined by 'lgpPwrAutomaticBatteryTestInterval'.
.1.3.6.1.4.1.476.1.42.3.5.4.16,LIEBERT-GP-POWER-MIB::lgpPwrMinimumRedundantPowerModule,Integer32,read-write,,current,,The minimum number of redundant power modules that must be present before sending a loss of power redundancy alarm. If 0, there is no redundant power functionality.
.1.3.6.1.4.1.476.1.42.3.5.4.17,LIEBERT-GP-POWER-MIB::lgpPwrMinimumRedundantBatteryModule,Integer32,read-write,,current,,The minimum number of redundant battery modules that must be present before sending an alarm. If 0, the redundant battery module alarm is  disabled.
.1.3.6.1.4.1.476.1.42.3.5.4.18,LIEBERT-GP-POWER-MIB::lgpPwrOutputToLoadUserOverloadLimit,Integer32,read-write,,current,,This is the user specified maximum load the device can support without sending an alarm.
.1.3.6.1.4.1.476.1.42.3.5.4.19,LIEBERT-GP-POWER-MIB::lgpPwrNoLoadWarningLimit,Integer32,read-write,,current,,The minimum current draw on the output in which the device considers there to be a load present on the output. The condition lgpConditionWarningNoLoadDetected will be triggered if the output current falls below this value. If this value is '-1' then the lgpConditionNoLoadDetectedWarning condition is 'disabled'.
.1.3.6.1.4.1.476.1.42.3.5.4.20,LIEBERT-GP-POWER-MIB::lgpPwrNoLoadWarningDelay,Integer32,read-write,,current,,The amount of time to delay before annunciation of the condition lgpConditionNoLoadDetectedWarning after the output current load falls below the threshold lgpPwrOutputNoLoadWarningLimit.
.1.3.6.1.4.1.476.1.42.3.5.4.21,LIEBERT-GP-POWER-MIB::lgpPwrEconomicOperationModeControl,INTEGER,read-write,,current,disabled(0):mode1(1):mode2(2),The configuration of the economic operation mode of the system. Note that this supersedes lgpPwrEconomicOperationMode in newer devices.
.1.3.6.1.4.1.476.1.42.3.5.5,LIEBERT-GP-POWER-MIB::lgpPwrConversion,,,,,,This sub-tree is used to register Liebert Power Conversion object identifiers.
.1.3.6.1.4.1.476.1.42.3.5.5.1,LIEBERT-GP-POWER-MIB::lgpPwrNumberInstalledPowerModules,Integer32,read-only,,current,,The number of power modules installed in the device.
.1.3.6.1.4.1.476.1.42.3.5.5.2,LIEBERT-GP-POWER-MIB::lgpPwrNumberFailedPowerModules,Integer32,read-only,,current,,The number of power modules in the device that have failed.
.1.3.6.1.4.1.476.1.42.3.5.5.3,LIEBERT-GP-POWER-MIB::lgpPwrNumberRedundantPowerModules,Integer32,read-only,,current,,The number of redundant power modules installed in the device.
.1.3.6.1.4.1.476.1.42.3.5.5.4,LIEBERT-GP-POWER-MIB::lgpPwrNumberActivePowerModules,Integer32,read-only,,current,,The number of active power modules in the device.
.1.3.6.1.4.1.476.1.42.3.5.5.6,LIEBERT-GP-POWER-MIB::lgpPwrNumberPowerModuleWarnings,Integer32,read-only,,current,,The number of power modules in the device that have a warning.
.1.3.6.1.4.1.476.1.42.3.5.5.7,LIEBERT-GP-POWER-MIB::lgpPwrUpsInverterStandby,INTEGER,read-write,,current,on(1):off(2),The output to the load is supported by the bypass and the inverter is on standby.
.1.3.6.1.4.1.476.1.42.3.5.6,LIEBERT-GP-POWER-MIB::lgpPwrControl,,,,,,This sub-tree is used to register Liebert Power Control object identifiers.
.1.3.6.1.4.1.476.1.42.3.5.6.1,LIEBERT-GP-POWER-MIB::lgpPwrWellKnownControlPoints,,,,,,This sub-tree registers well known Liebert Power Control Points. The object identifier names usually imply locations where control of a device is available -- such 'output' or 'load circuits'.
.1.3.6.1.4.1.476.1.42.3.5.6.1.1,LIEBERT-GP-POWER-MIB::lgpPwrLoadCircuit,,,,,,The managed device's controllable load circuit. Many power systems contain more than one load circuit. This identifier represents one load circuit for the system but does not necessarily represent the 'first' one. The load circuits' numbering with respect to 'lgpPwrLoadCircuit1' etc. may depend on the physical wiring of the system when it was installed.
.1.3.6.1.4.1.476.1.42.3.5.6.2,LIEBERT-GP-POWER-MIB::lgpPwrLoadCircuitTable,,not-accessible,,current,,A list of load circuits that can be controlled(opened or closed). The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
.1.3.6.1.4.1.476.1.42.3.5.6.2.1,LIEBERT-GP-POWER-MIB::lgpPwrLoadCircuitEntry,,not-accessible,lgpPwrLoadCircuitIndex,current,,This entry defines the contents of the columns for the table 'lgpPwrLoadCircuitTable'.
.1.3.6.1.4.1.476.1.42.3.5.6.2.1.1,LIEBERT-GP-POWER-MIB::lgpPwrLoadCircuitIndex,Unsigned32,not-accessible,,current,,This is the index indicating the row of the table 'lgpPwrLoadCircuitTable'.
.1.3.6.1.4.1.476.1.42.3.5.6.2.1.2,LIEBERT-GP-POWER-MIB::lgpPwrLoadCircuitId,OBJECT,read-only,,current,,An OID representing a well known load circuit identifier. These load circuit identifiers indicate the name or type of load circuit reference in the table.
.1.3.6.1.4.1.476.1.42.3.5.6.2.1.3,LIEBERT-GP-POWER-MIB::lgpPwrLoadCircuitSubID,Unsigned32,read-only,,current,,This is a sub identifier for the 'lgpPwrLoadCircuitId'. It indicates the hardware identifier of the load control circuit.
.1.3.6.1.4.1.476.1.42.3.5.6.2.1.4,LIEBERT-GP-POWER-MIB::lgpPwrLoadCircuitState,INTEGER,read-write,,current,on(1):off(2):default(3),This identifier indicates the state of the load circuit. When read, only a closed or open response will be returned. When written to, the state of the circuit will transition to desired state.
.1.3.6.1.4.1.476.1.42.3.5.6.2.1.5,LIEBERT-GP-POWER-MIB::lgpPwrLoadCircuitStateAndControl,INTEGER,read-write,,current,off(0):on(1):reboot(2),This identifier indicates the state of the load circuit. When read, only a closed or open response will be returned. When written to, the state of the circuit will transition to desired state.
.1.3.6.1.4.1.476.1.42.3.5.6.3,LIEBERT-GP-POWER-MIB::lgpPwrAlarmSilence,Integer32,read-write,,current,,Audible Alarm Silence Command. This command turns off the device's audible alarm. It will not affect the status of the alarm(s) that caused the audible alarm. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
.1.3.6.1.4.1.476.1.42.3.5.6.4,LIEBERT-GP-POWER-MIB::lgpPwrBatteryTest,INTEGER,read-write,,current,start(1):abort(2),Battery Test Command. This command will initiate a battery test if one is not already in progress, or abort the current test if it is in progress.
.1.3.6.1.4.1.476.1.42.3.5.6.5,LIEBERT-GP-POWER-MIB::lgpPwrUpsAbortCommand,Integer32,read-write,,current,,UPS Abort command. This command will abort the pending command on the device. There is no guarantee a client using the abort command will cancel a command sent moments before from the same client. Another client could initiate a command and change what command is actually pending on the device. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
.1.3.6.1.4.1.476.1.42.3.5.6.6,LIEBERT-GP-POWER-MIB::lgpPwrTransferToBypass,Integer32,read-write,,current,,Transfer to Bypass Command. This command will initiate a transfer of the load to the bypass of the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
.1.3.6.1.4.1.476.1.42.3.5.6.7,LIEBERT-GP-POWER-MIB::lgpPwrTransferToInverter,Integer32,read-write,,current,,Transfer to Inverter Command. This command will initiate a transfer of the load to the inverter of the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
.1.3.6.1.4.1.476.1.42.3.5.6.8,LIEBERT-GP-POWER-MIB::lgpPwrOutputOnDelay,Integer32,read-write,,current,,Output On Delay Command. This command will turn on the output of the device after a user specified delay. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals.
.1.3.6.1.4.1.476.1.42.3.5.6.9,LIEBERT-GP-POWER-MIB::lgpPwrOutputOffDelayWithRestart,Integer32,read-write,,current,,Output Off Delay with Restart Command. This command will turn off the output of the device after a user specified delay. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals. The device will then turn the output on again after a specified amount of time. 
.1.3.6.1.4.1.476.1.42.3.5.6.10,LIEBERT-GP-POWER-MIB::lgpPwrOutputOffDelayWithoutRestart,Integer32,read-write,,current,,Output Off Delay without Restart Command. This command will turn off the output of the device after a specified delay. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals. The device will NOT automatically turn the output on following this command.
.1.3.6.1.4.1.476.1.42.3.5.7,LIEBERT-GP-POWER-MIB::lgpPwrTopology,,,,,,This sub-tree is used to register Liebert Power Topology object identifiers.
.1.3.6.1.4.1.476.1.42.3.5.7.1,LIEBERT-GP-POWER-MIB::lgpPwrUpsTopOffline,INTEGER,read-only,,current,yes(1):no(2),The UPS has an offline topology. Under normal operating conditions, AC power from the utility passes straight through the UPS to the critical load. The inverter is used to convert the DC power from the battery to create AC power to support the load when the utility fails. Normally the inverter is operating in the stand-by mode, keeping the batteries charged. Should the utility power go out of specification, the inverter will power the load by drawing energy from the battery.
.1.3.6.1.4.1.476.1.42.3.5.7.2,LIEBERT-GP-POWER-MIB::lgpPwrUpsTopLineInteractive,INTEGER,read-only,,current,yes(1):no(2),The UPS has a line-interactive topology. This topology resembles the offline product, but inserts a transformer or inductor in series between the utility power source and the load. This inline inductor enables the UPS inverter to interact with incoming power and provide a measure of power conditioning to the load. This buck-and-boost circuitry helps with high and low input voltage conditions.
.1.3.6.1.4.1.476.1.42.3.5.7.3,LIEBERT-GP-POWER-MIB::lgpPwrUPSTopDualInput,INTEGER,read-only,,current,yes(1):no(2),The system has separate input sources for the bypass and inverter.
.1.3.6.1.4.1.476.1.42.3.5.7.4,LIEBERT-GP-POWER-MIB::lgpPwrTopFrequencyConverter,INTEGER,read-only,,current,yes(1):no(2),The system has a frequency converter.
.1.3.6.1.4.1.476.1.42.3.5.7.5,LIEBERT-GP-POWER-MIB::lgpPwrTopVoltageConverter,INTEGER,read-only,,current,yes(1):no(2),The system has a voltage converter.
.1.3.6.1.4.1.476.1.42.3.5.7.6,LIEBERT-GP-POWER-MIB::lgpPwrTopMaximumFrameCapacity,Integer32,read-write,,current,,The maximum device system capacity.
.1.3.6.1.4.1.476.1.42.3.5.7.7,LIEBERT-GP-POWER-MIB::lgpPwrTopRedundantControlModules,INTEGER,read-only,,current,yes(1):no(2),The device has a redundant control module installed.
.1.3.6.1.4.1.476.1.42.3.5.7.8,LIEBERT-GP-POWER-MIB::lgpPwrInputIsolationTransformerInstalled,INTEGER,read-only,,current,notInstalled(1):installed(2),Indicates whether the input isolation transformer is installed.
.1.3.6.1.4.1.476.1.42.3.5.7.9,LIEBERT-GP-POWER-MIB::lgpPwrStateStaticSwitchType,INTEGER,read-only,,current,notApplicable(1):continuousDuty(2):momentaryDuty(3),Static switch type (N/A, continous duty, or momentary duty).
.1.3.6.1.4.1.476.1.42.3.5.7.10,LIEBERT-GP-POWER-MIB::lgpPwrStateModuleType,INTEGER,read-only,,current,singleModuleSystem(1):module1plus1(2):module1plusN(3):moduleNplus1(4):systemControlCabinet(5):mainStaticSwitch(6),UPS module type.  SMS -- Single Module System 1 + 1 -- Redundant system for capacity  1 + N -- Distributed multi-module system  N + 1 -- A multi-module system with one bypass for the system SCC -- System Control Cabinet used in an N+1 system to provide a single bypass for the system.  MSS -- Main Static Switch
.1.3.6.1.4.1.476.1.42.3.5.7.11,LIEBERT-GP-POWER-MIB::lgpPwrStateBypassInputConfig,INTEGER,read-only,,current,singlePhase2WireL1WithReturn(1):twoPhase2WireL1L2(2):twoPhase3WireL1L2WithNeutral(3):threePhase3WireL1L2L3(4):threePhase4WireL1L2L3WithNeutral(5),Bypass input wire physical wiring configuration. singlePhase2WireL1WithReturn Single phase input with 2 wires (Line 1, and Return). twoPhase2WireL1L2 Two phase input with 2 wires (Line 1, and Line 2). twoPhase3WireL1L2WithNeutral Two phase input with 3 wires (Line 1, Line 2, and Neutral) threePhase3WireL1L2L3 Three phase input with 3 wires (Line 1, Line 2, and Line 3) threePhase4WireL1L2L3WithNeutral Three phase input with 4 wires (Line 1, Line 2, Line 3, and  Neutral).
.1.3.6.1.4.1.476.1.42.3.5.7.12,LIEBERT-GP-POWER-MIB::lgpPwrStateOutputConfig,INTEGER,read-only,,current,singlePhase2WireL1WithReturn(1):twoPhase2WireL1L2(2):twoPhase3WireL1L2WithNeutral(3):threePhase3WireL1L2L3(4):threePhase4WireL1L2L3WithNeutral(5),Output wire physical wiring configuration. singlePhase2WireL1WithReturn Single phase output with 2 wires (Line 1, and Return). twoPhase2WireL1L2 Two phase output with 2 wires (Line 1, and Line 2). twoPhase3WireL1L2WithNeutral Two phase output with 3 wires (Line 1, Line 2, and Neutral) threePhase3WireL1L2L3 Three phase output with 3 wires (Line 1, Line 2, and Line 3) threePhase4WireL1L2L3WithNeutral Three phase output with 4 wires (Line 1, Line 2, Line 3, and  Neutral).
.1.3.6.1.4.1.476.1.42.3.5.7.13,LIEBERT-GP-POWER-MIB::lgpPwrRectifierPassiveFilterInstalled,INTEGER,read-only,,current,notInstalled(1):installed(2),Indicates whether the rectifier passive filter is installed.
.1.3.6.1.4.1.476.1.42.3.5.7.14,LIEBERT-GP-POWER-MIB::lgpPwrRectifierTrapInstalled,INTEGER,read-only,,current,notInstalled(1):installed(2),Indicates whether the rectifier input passive filter is installed.
.1.3.6.1.4.1.476.1.42.3.5.7.15,LIEBERT-GP-POWER-MIB::lgpPwrRectifierActiveFilterInstalled,INTEGER,read-only,,current,notInstalled(1):installed(2),Indicates whether the rectifier active filter is installed.
.1.3.6.1.4.1.476.1.42.3.5.8,LIEBERT-GP-POWER-MIB::lgpPwrStatistic,,,,,,This sub-tree is used to register Liebert Power Statistic object identifiers.
.1.3.6.1.4.1.476.1.42.3.5.8.1,LIEBERT-GP-POWER-MIB::lgpPwrBrownOutCount,Integer32,read-only,,current,,The number of occurrences where the input line voltage has fallen below a pre-determined threshold for a specified amount of time. This number resets when the command 'lgpPwrStatisticsReset' is executed.
.1.3.6.1.4.1.476.1.42.3.5.8.2,LIEBERT-GP-POWER-MIB::lgpPwrBlackOutCount,Integer32,read-only,,current,,The number of occurrences where there is a total loss of electric power. This number resets when the command 'lgpPwrStatisticsReset' is executed.
.1.3.6.1.4.1.476.1.42.3.5.8.3,LIEBERT-GP-POWER-MIB::lgpPwrTransientCount,Integer32,read-only,,current,,The number of occurrences where the input line voltage spikes above a pre-determined threshold for a specified amount of time. This number resets when the command 'lgpPwrStatisticsReset' is executed.
.1.3.6.1.4.1.476.1.42.3.5.8.4,LIEBERT-GP-POWER-MIB::lgpPwrBatteryDischargeCount,Integer32,read-only,,current,,The number of battery discharges since the last reset.
.1.3.6.1.4.1.476.1.42.3.5.8.5,LIEBERT-GP-POWER-MIB::lgpPwrBatteryDischargeTime,Integer32,read-only,,current,,The total accumulated time spent on battery since the last reset.
.1.3.6.1.4.1.476.1.42.3.5.8.6,LIEBERT-GP-POWER-MIB::lgpPwrBatteryAmpHours,Integer32,read-only,,current,,The total accumulated Amp-hours removed from the battery since last reset.
.1.3.6.1.4.1.476.1.42.3.5.8.7,LIEBERT-GP-POWER-MIB::lgpPwrBatteryWattHours,Integer32,read-only,,current,,The total accumulated Watt-Hours removed from the battery since last reset. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
.1.3.6.1.4.1.476.1.42.3.5.8.8,LIEBERT-GP-POWER-MIB::lgpPwrBatteryStatisticsReset,Integer32,read-write,,current,,Battery statistics clear command. The command to reset all battery statistics stored by the device. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
.1.3.6.1.4.1.476.1.42.3.5.8.9,LIEBERT-GP-POWER-MIB::lgpPwrStatisticsReset,Integer32,read-write,,current,,Reset Power Statistics Command. This command will reset the power statistics stored in the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
.1.3.6.1.4.1.476.1.42.3.5.9,LIEBERT-GP-POWER-MIB::lgpPwrConfig,,,,,,This sub-tree is used to register Liebert Power Configuration Object identifiers.
.1.3.6.1.4.1.476.1.42.3.5.9.1,LIEBERT-GP-POWER-MIB::lgpPwrSysCapacity,Integer32,read-write,,current,,The current device system capacity.
.1.3.6.1.4.1.476.1.42.3.5.9.2,LIEBERT-GP-POWER-MIB::lgpPwrUPSModuleMode,INTEGER,read-write,,current,single(1):parallel(2):hotmaster(3):hotslave(4),The module mode of the UPS.
.1.3.6.1.4.1.476.1.42.3.5.9.3,LIEBERT-GP-POWER-MIB::lgpPwrMaxRatedCurrent,Integer32,read-only,,current,,System output maximum amperage rating. The maximum rated amperage for  the system. This value is based upon the model type and is typically  limited by the wiring, breakers, power devices, etc.
.1.3.6.1.4.1.476.1.42.3.5.9.4,LIEBERT-GP-POWER-MIB::lgpPwrRectifierPulseCount,INTEGER,read-only,,current,sixPulse(1):twelvePulse(2):eighteenPulse(3):twentyFourPulse(4),Rectifier pulse count per waveform cycle (6-, 12-, 18-, or 24-pulse).
.1.3.6.1.4.1.476.1.42.3.6,LIEBERT-GP-REGISTRATION-MIB::lgpController,,,,,,This branch is used to register Liebert controller object identifiers.
.1.3.6.1.4.1.476.1.42.3.6.1,LIEBERT-GP-CONTROLLER-MIB::lgpCtrlNumberInstalledControlModules,Integer32,read-only,,current,,The number of control modules installed in the device.
.1.3.6.1.4.1.476.1.42.3.6.2,LIEBERT-GP-CONTROLLER-MIB::lgpCtrlNumberFailedControlModules,Integer32,read-only,,current,,The number of control modules in the device that have failed.
.1.3.6.1.4.1.476.1.42.3.6.3,LIEBERT-GP-CONTROLLER-MIB::lgpCtrlNumberRedundantControlModules,Integer32,read-only,,current,,The number of redundant control modules installed in the device.
.1.3.6.1.4.1.476.1.42.3.6.5,LIEBERT-GP-CONTROLLER-MIB::lgpCtrlNumberControlModuleWarnings,Integer32,read-only,,current,,The number of control modules in the device that have a warning.
.1.3.6.1.4.1.476.1.42.3.6.6,LIEBERT-GP-CONTROLLER-MIB::lgpCtrlBoardBatteryVoltage,Unsigned32,read-only,,current,,The control board battery voltage. Typically this battery is used to provide backup power to memory and other vital circuits.
.1.3.6.1.4.1.476.1.42.3.7,LIEBERT-GP-REGISTRATION-MIB::lgpSystem,,,,,,This branch is used to register Liebert system object identifiers.
.1.3.6.1.4.1.476.1.42.3.7.1,LIEBERT-GP-SYSTEM-MIB::lgpSysStatistics,,,,,,This sub-tree is used to register Liebert System Statistics object identifiers.
.1.3.6.1.4.1.476.1.42.3.7.1.1,LIEBERT-GP-SYSTEM-MIB::lgpSysStatisticsRunHrs,Unsigned32,read-only,,current,,Accumulated run hours of the system.
.1.3.6.1.4.1.476.1.42.3.7.2,LIEBERT-GP-SYSTEM-MIB::lgpSysStatus,,,,,,This sub-tree is used to register Liebert System Status object identifiers.
.1.3.6.1.4.1.476.1.42.3.7.2.1,LIEBERT-GP-SYSTEM-MIB::lgpSysSelfTestResult,INTEGER,read-only,,current,unknown(1):passed(2):failed(3):inProgress(4):sysFailure(5):inhibited(6),The outcome of the previous self-test.
.1.3.6.1.4.1.476.1.42.3.7.2.2,LIEBERT-GP-SYSTEM-MIB::lgpSysState,INTEGER,read-only,,current,normalOperation(1):startUp(2):normalWithWarning(3):normalWithAlarm(4):abnormalOperation(5),The operating status for the system. The intent of this data is to provide a high level status of the system. The possible states are: normalOperation(1) The system is operating normally with no active warnings or  alarms. startUp(2) The system is in a startup state (initializing). Monitoring  operations and information may not be fully supported at this  time. This state will clear automatically when the system is  fully initialized and ready to accept monitoring commands. normalWithWarning(3) The system is operating normally with one or more active  warnings. Appropriate personnel should investigate the  warning(s) as soon as possible and take appropriate action.  normalWithAlarm(4) The system is operating normally with one or more active  alarms. Appropriate personnel should investigate the alarm(s) as soon as possible and take appropriate action.  abnormalOperation(5) They system is operating abnormally. There is a  failure within the system that is unexpected under normal  operating conditions. Appropriate personnel should investigate the cause as soon as possible. The normal functioning of the system is likely inhibited.
.1.3.6.1.4.1.476.1.42.3.7.3,LIEBERT-GP-SYSTEM-MIB::lgpSysSettings,,,,,,This sub-tree is used to register Liebert System Settings object identifiers.
.1.3.6.1.4.1.476.1.42.3.7.3.1,LIEBERT-GP-SYSTEM-MIB::lgpSysAudibleAlarm,INTEGER,read-write,,current,on(1):off(2),The state of the audible alarm of the device.
.1.3.6.1.4.1.476.1.42.3.7.4,LIEBERT-GP-SYSTEM-MIB::lgpSysControl,,,,,,This sub-tree is used to register Liebert System Control object identifiers.
.1.3.6.1.4.1.476.1.42.3.7.4.1,LIEBERT-GP-SYSTEM-MIB::lgpSysSelfTest,Integer32,read-write,,current,,Self-Test Command. This command will initiate a system self-test of the system. If already initiated, this command will abort the self-test. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
.1.3.6.1.4.1.476.1.42.3.7.4.2,LIEBERT-GP-SYSTEM-MIB::lgpSysControlOperationOnOff,INTEGER,read-write,,current,on(1):off(2),This object allows control of the system functionality. This will not affect the communications or control of the system, so that once turned off, the system operation can be restored by setting this value to  'on'.
.1.3.6.1.4.1.476.1.42.3.7.5,LIEBERT-GP-SYSTEM-MIB::lgpSysTime,,,,,,This sub-tree is used to register Liebert System Time object identifiers.
.1.3.6.1.4.1.476.1.42.3.7.5.1,LIEBERT-GP-SYSTEM-MIB::lgpSysTimeEpoch,Unsigned32,read-write,,current,,The present time of the system. This time is represented as the number of seconds since the epoch of 1970-01-01 00:00:00 GMT.
.1.3.6.1.4.1.476.1.42.3.7.6,LIEBERT-GP-SYSTEM-MIB::lgpSysMaintenance,,,,,,This sub-tree is used to register Liebert System Maintenance object identifiers.
.1.3.6.1.4.1.476.1.42.3.7.6.1,LIEBERT-GP-SYSTEM-MIB::lgpSysMaintenanceCapacity,Unsigned32,read-only,,current,,The relative percentage of time that has elapsed since the last scheduled maintenance was performed. When this value reaches 100%, the device is due for another scheduled maintenance procedure.
.1.3.6.1.4.1.476.1.42.3.7.6.2,LIEBERT-GP-SYSTEM-MIB::lgpSysMaintenanceYear,Unsigned32,read-only,,current,,The year in which the next scheduled service is due
.1.3.6.1.4.1.476.1.42.3.7.6.3,LIEBERT-GP-SYSTEM-MIB::lgpSysMaintenanceMonth,Unsigned32,read-only,,current,,The month in which the next scheduled service is due
.1.3.6.1.4.1.476.1.42.3.7.7,LIEBERT-GP-SYSTEM-MIB::lgpSysEventDescription,OCTET,read-only,,current,,An ASCII textual description for the event. This object is primarily used in the varbind of some notifications to provide a simple human-readable description.
.1.3.6.1.4.1.476.1.42.3.7.8,LIEBERT-GP-SYSTEM-MIB::lgpSysEventNotifications,,,,,,This sub-tree is used to register Liebert System Notification object identifiers.
.1.3.6.1.4.1.476.1.42.3.7.8.1,LIEBERT-GP-SYSTEM-MIB::lgpSysNotification,,,,,,This notification is a generic notification intended for direct user visibility. The user event description identifies the system condition that has occurred. This text will be prefixed with either 'Active:', 'Cleared:', or 'Message:' depending on the state of the event. Note: That a prefix of 'Message:' identifies a stateless event and as such there will be no corresponding 'Cleared:' trap sent.
.1.3.6.1.4.1.476.1.42.3.7.8.2,LIEBERT-GP-SYSTEM-MIB::lgpSysNormal,,,,,,The system has returned to a normal operating state. This implies prior to the generation of this event the system was operating in a state where one or more alarm or warning conditions were present. All of those alarms or conditions have now cleared. NOTE: This notification may be generated after a short delay during a cold boot of the system -- if no alarms or conditions are present in the monitored device(s) at that time.
.1.3.6.1.4.1.476.1.42.3.7.9,LIEBERT-GP-SYSTEM-MIB::lgpSysDeviceComponentGroup,,,,,,This sub-tree registers well known device components.
.1.3.6.1.4.1.476.1.42.3.7.9.1,LIEBERT-GP-SYSTEM-MIB::lgpSysDeviceComponentTable,,not-accessible,,current,,A list of components of devices identified by their serial number and  or model number. This table contains zero, one, or many rows. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
.1.3.6.1.4.1.476.1.42.3.7.9.1.1,LIEBERT-GP-SYSTEM-MIB::lgpSysDeviceComponentEntry,,not-accessible,lgpAgentDeviceIndex:lgpSysDeviceComponentIndex,current,,This entry defines the contents of the columns for the table 'lgpSysDeviceComponentTable'.
.1.3.6.1.4.1.476.1.42.3.7.9.1.1.1,LIEBERT-GP-SYSTEM-MIB::lgpSysDeviceComponentIndex,Unsigned32,not-accessible,,current,,This is the index indicating the row in the table 'lgpSysDeviceComponentTable' for a component entry.
.1.3.6.1.4.1.476.1.42.3.7.9.1.1.2,LIEBERT-GP-SYSTEM-MIB::lgpSysDeviceComponentDescr,OBJECT,read-only,,current,,An OID representing a component of the device indicated by the index lgpAgentDeviceIndex.
.1.3.6.1.4.1.476.1.42.3.7.9.1.1.3,LIEBERT-GP-SYSTEM-MIB::lgpSysDeviceComponentSerialNum,OCTET,read-only,,current,,This is the serial number of the component described by the OID  'lgpSysDeviceComponentDescr'. This data is intended for  display / human consumption. Do not use this field for determining programmatic behavior.
.1.3.6.1.4.1.476.1.42.3.7.9.1.1.4,LIEBERT-GP-SYSTEM-MIB::lgpSysDeviceComponentModelNum,OCTET,read-only,,current,,This is the model identifier of the component described by the OID  'lgpSysDeviceComponentDescr'. This data is intended for  display / human consumption. Do not use this field for determining programmatic behavior.
.1.3.6.1.4.1.476.1.42.3.7.9.5,LIEBERT-GP-SYSTEM-MIB::lgpSysDeviceComponentWellknown,,,,,,This sub-tree registers well known Liebert System Components.
.1.3.6.1.4.1.476.1.42.3.7.9.5.5,LIEBERT-GP-SYSTEM-MIB::lgpSysDeviceBatCabinet,,,,,,This sub-tree is used to register a battery cabinet component. To determine the cabinet being described in a multi-cabinet system, this point implements an additional two indexes. The first index describes the module the cabinet is located in. The second index describes the cabinet number. In an SMS (Single-Module System) the first index is always 1. Example: lgpSysDeviceComponentCabinet.2.4 'lgpSysDeviceCabinet' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4 in second module
.1.3.6.1.4.1.476.1.42.3.7.9.5.6,LIEBERT-GP-SYSTEM-MIB::lgpSysDeviceParallelCabinet,,,,,,This sub-tree is used to register a parallel cabinet.
.1.3.6.1.4.1.476.1.42.3.7.9.5.7,LIEBERT-GP-SYSTEM-MIB::lgpSysDeviceMaintBypass,,,,,,This sub-tree is used to register the maintenance bypass.
.1.3.6.1.4.1.476.1.42.3.8,LIEBERT-GP-REGISTRATION-MIB::lgpPdu,,,,,,This branch is used to register Liebert system object identifiers.
.1.3.6.1.4.1.476.1.42.3.8.5,LIEBERT-GP-PDU-MIB::lgpPduGlobalData,,,,,,This sub-tree contains data and control associated with PDU's controlled by this agent. Data in this sub-tree will affect the behavior of all PDU's controlled by this agent.
.1.3.6.1.4.1.476.1.42.3.8.5.5,LIEBERT-GP-PDU-MIB::lgpPduEntrySWOverTemperatureProtectionConfig,INTEGER,read-write,,current,local(0):array(1),This configures the scope of behavior for the PDU Software Over  Temperature Protection feature.  See lgpPduRcpEntrySwOverTemperatureProtection to enable this feature and get further information about what actions will be performed. local (0) Only receptacles on the PDU with the alarming temperature sensor  will be affected. array (1) All receptacles in the PDU array will be affected, regardless of  which PDU the alarming temperature sensor is connected to. 
.1.3.6.1.4.1.476.1.42.3.8.5.10,LIEBERT-GP-PDU-MIB::lgpPduEntrySWOverTemperatureProtectionDelay,Unsigned32,read-write,,current,,This sets the delay for the PDU Software Over Temperature Protection  feature. This value determines the amount of time to delay, after the high temperature alarm becomes active, before taking action on the  enabled receptacles. If the high temperature alarm becomes inactive before the expiration of the delay time, no action will be taken on  the enabled receptacles.  See lgpPduRcpEntrySwOverTemperatureProtection to enable this feature and get further information about what actions will be performed. 
.1.3.6.1.4.1.476.1.42.3.8.10,LIEBERT-GP-PDU-MIB::lgpPduCluster,,,,,,This sub-tree contains information about PDU clusters. Clusters are groups of PDU's under a single monitoring or control domain.
.1.3.6.1.4.1.476.1.42.3.8.10.5,LIEBERT-GP-PDU-MIB::lgpPduGrpSysStatus,Unsigned32,read-only,,current,,This value represents a bit-field of the various operational states of the PDUs that are part of the cluster of PDUs being monitored by this agent. This value is the bit-wise logical OR of all of the 'lgpPduEntrySysStatus' columns in the 'lgpPduTable' which represents the combined statuses of all PDUs for this agent. Note the bit-position is given parenthetically next to the operational state in the description below. The bit position is big-endian (least significant digit is the right-most digit). The state is present in the PDU when the bit is on (value = 1). The value is a logical OR of all of the following potential states of each PDU in the cluster. normalOperation(1) One or more PDUs in the cluster are operating normally with no active warnings or alarms. startUp(2) One or more PDUs are in the startup state (initializing). Control and monitoring operations may be inhibited or unavailable while the PDU is in this state. This state will clear automatically when the PDU(s) are fully initialized and ready to accept control and monitoring commands. unknownNoSupport(4) The state of one or more PDUs are not known at this time or there is no support for this piece of information from 1 or more PDUs in the cluster/group. normalWithWarning(8) One or more PDUs are operating normally with one or more active warnings. Appropriate personnel should investigate the warning(s) as soon as possible and take appropriate action. normalWithAlarm(16) One or more PDUs are operating normally with one or more active alarms. Appropriate personnel should investigate the alarm(s) as soon as possible and take appropriate action. abnormalOperation(32) One ore more PDUs are operating abnormally. There is a failure within the system that is unexpected under normal operating conditions. Appropriate personnel should investigate the cause as soon as possible. The normal functioning of the system is likely inhibited. unknownCommFailure(64) The state of one or more PDUs are not known due to a communications failure between the PDU hardware and the communications module. This state is usually indicative of a hardware problem. 
.1.3.6.1.4.1.476.1.42.3.8.19,LIEBERT-GP-PDU-MIB::lgpPduTableCount,Unsigned32,read-only,,current,,Number of PDUs being monitored by this agent. This is the number of entries in the lgpPduTable.
.1.3.6.1.4.1.476.1.42.3.8.20,LIEBERT-GP-PDU-MIB::lgpPduTable,,not-accessible,,current,,This table contains a list of PDU entries. The table contains zero, one, or many rows, depending upon the number of PDUs being monitored. The Network Management System (NMS) cannot create or delete rows in the table. The rows are created by the agent based upon the number of PDUs being managed. Each row in the table represents a PDU in the system.
.1.3.6.1.4.1.476.1.42.3.8.20.1,LIEBERT-GP-PDU-MIB::lgpPduEntry,,not-accessible,lgpPduEntryIndex,current,,This entry defines the columns to be populated in the 'lgpPduTable'. Each column represents an attribute of a PDU. This table is indexed by the PDU identifier that is unique within the agent. 
.1.3.6.1.4.1.476.1.42.3.8.20.1.1,LIEBERT-GP-PDU-MIB::lgpPduEntryIndex,Unsigned32,not-accessible,,current,,This is the index that indicates the row of the 'lgpPduTable'.
.1.3.6.1.4.1.476.1.42.3.8.20.1.5,LIEBERT-GP-PDU-MIB::lgpPduEntryId,Unsigned32,read-only,,current,,This is an internal index representing a unique identifier for each PDU represented by this agent. The value is assigned by the agent.
.1.3.6.1.4.1.476.1.42.3.8.20.1.10,LIEBERT-GP-PDU-MIB::lgpPduEntryUsrLabel,OCTET,read-write,,current,,This is a user assigned label representing the PDU.
.1.3.6.1.4.1.476.1.42.3.8.20.1.15,LIEBERT-GP-PDU-MIB::lgpPduEntrySysAssignLabel,OCTET,read-only,,current,,System assigned identifier representing the PDU. The value is independent of any user assigned label or tag. The exact format of this label is system dependent and is subject to change, therefore, it should not be referenced for programmatic use.
.1.3.6.1.4.1.476.1.42.3.8.20.1.20,LIEBERT-GP-PDU-MIB::lgpPduEntryPositionRelative,Unsigned32,read-only,,current,,This is a one-based value that indicates the PDU's relative position within a rack or other enclosing entity.
.1.3.6.1.4.1.476.1.42.3.8.20.1.25,LIEBERT-GP-PDU-MIB::lgpPduEntrySysStatus,Unsigned32,read-only,,current,,This value represents a bit-field of the various operational states of the PDU. The value is a logical OR of all of the following potential states of the PDU. Note the bit-position is given parenthetically next to the operational state in the description below. The bit position is assumed to be a big-endian format (least significant digit is the right-most digit). The state is present in the PDU when the bit is on (value = 1). normalOperation(1) The PDU is operating normally with no active warnings or alarms. startUp(2) The PDU is in the startup state (initializing). Control and monitoring operations maybe inhibited or unavailable while the PDU is in this state. This state will clear automatically when the PDU(s) are fully initialized and ready to accept control and monitoring commands. normalWithWarning(8) The PDU is operating normally with one or more active warnings. Appropriate personnel should investigate the warning(s) as soon as possible and take appropriate action. normalWithAlarm(16) The PDU is operating normally with one or more active alarms. Appropriate personnel should investigate the alarm(s) as soon as possible and take appropriate action. abnormalOperation(32) The PDU is operating abnormally. That is there is some failure within the system that is unexpected under normal operating conditions. Appropriate personnel should investigate the cause as soon as possible. The normal functioning of the system is likely inhibited. 
.1.3.6.1.4.1.476.1.42.3.8.20.1.35,LIEBERT-GP-PDU-MIB::lgpPduEntryUsrTag1,OCTET,read-write,,current,,This is a user assigned Tag for the PDU. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be unique for this unit or across other units.
.1.3.6.1.4.1.476.1.42.3.8.20.1.40,LIEBERT-GP-PDU-MIB::lgpPduEntryUsrTag2,OCTET,read-write,,current,,This is a user assigned Tag for the PDU. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be unique for this unit or across other units.
.1.3.6.1.4.1.476.1.42.3.8.20.1.45,LIEBERT-GP-PDU-MIB::lgpPduEntrySerialNumber,OCTET,read-only,,current,,System assigned serial number for this PDU. This number is assigned at time of manufacture, is globally unique with respect to all PDU units.
.1.3.6.1.4.1.476.1.42.3.8.20.1.50,LIEBERT-GP-PDU-MIB::lgpPduEntryRbCount,Unsigned32,read-only,,current,,Number of receptacle branches (Rb) within this PDU.
.1.3.6.1.4.1.476.1.42.3.8.20.1.55,LIEBERT-GP-PDU-MIB::lgpPduEntrySWOverCurrentProtection,INTEGER,read-write,,current,disabled(0):enable(1),This is the PDU Software Over Current Protection feature which will prevent unused receptacles from turning on when the 'PDU Over Current Warning' or 'PDU Over Current Alarm' threshold is violated. Such receptacles shall get locked to prevent any user from switching them ON. Only device-admin shall have the authorization to unlock such receptacles. If the feature is enabled, in case of PDU Over Current Warning or Alarm condition, following action will be taken on the receptacles: a. Locked & OFF  No change b. Locked & ON - No change c. UnLocked & OFF  Receptacle shall be locked d. Unlocked & ON  If the receptacle is being used (current>0), no change. If that outlet is being unused(current=0), turn it off and lock it in that position. No action will be taken if the feature is disabled. Note: Only applicable to PDU models where receptacle measurement and control is supported. Not applicable for PDU models that support only branch monitoring. disabled This function is disabled. enable This function is enabled.
.1.3.6.1.4.1.476.1.42.3.8.30,LIEBERT-GP-PDU-MIB::lgpPduPowerSource,,,,,,This sub-tree contains information about PDU power sources.
.1.3.6.1.4.1.476.1.42.3.8.30.19,LIEBERT-GP-PDU-MIB::lgpPduPsTableCount,Unsigned32,read-only,,current,,Number of power sources in the lgpPduPsTable.
.1.3.6.1.4.1.476.1.42.3.8.30.20,LIEBERT-GP-PDU-MIB::lgpPduPsTable,,not-accessible,,current,,This table contains a list of the PDU's power source(s). The table contains zero, one, or more rows, depending upon the number of PDUs being monitored and the number of power sources installed for each PDU. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDUs being monitored. Each row in the table represents a PDU's Power Source.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1,LIEBERT-GP-PDU-MIB::lgpPduPsEntry,,not-accessible,lgpPduEntryIndex:lgpPduPsEntryIndex,current,,This entry defines the attributes to be populated in the various columns of the 'lgpPduPsTable' (Power Source Table). This table is indexed by both the 'lgpPduEntryIndex' which is the sole index into the 'lgpPduTable' and the 'lgpPduPsEntryIndex' which is a unique identifier for the Power Source within a given PDU. Taken together these two indexes uniquely identify a Power Source within this agent. 
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.5,LIEBERT-GP-PDU-MIB::lgpPduPsEntryIndex,Unsigned32,not-accessible,,current,,This is a unique identifier for the Power Source within a given PDU. This is one of two indexes used to indicate the row of the 'lgpPduTable'.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.10,LIEBERT-GP-PDU-MIB::lgpPduPsEntryId,Unsigned32,read-only,,current,,This is a unique entry id representing a given PDU power source for the PDU.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.15,LIEBERT-GP-PDU-MIB::lgpPduPsEntrySysAssignLabel,OCTET,read-only,,current,,System assigned identifier for this power source. The value is independent of any user assigned label or tag. The exact format of this label is system dependent and is subject to change, therefore, it should not be referenced for programmatic use.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.20,LIEBERT-GP-PDU-MIB::lgpPduPsEntryModel,OCTET,read-only,,current,,This is the model name (identifier) of the power supply.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.25,LIEBERT-GP-PDU-MIB::lgpPduPsEntryWiringType,INTEGER,read-write,,current,not-specified(0):single-phase-3-wire-L1-N-PE(1):two-phase-3-wire-L1-L2-PE(2):three-phase-4-wire-L1-L2-L3-PE(3):three-phase-5-wire-L1-L2-L3-N-PE(4):two-phase-4-wire-L1-L2-N-PE(5),The PDU's power supply physical wiring type. not-specified The type has not been specified/configured. The end_user must configure this object to specify the physical wiring type. single-phase-3-wire-L1-N-PE Single Phase input with 3 wires (Line 1, Neutral and Protective Earth). two-phase-3-wire-L1-L2-PE Two Phase input with 3 wires (Line 1, Line 2, and Protective Earth). three-phase-4-wire-L1-L2-L3-PE Three Phase input with 4 wires (Line 1, Line 2, Line 3, and Protective Earth). three-phase-5-wire-L1-L2-L3-N-PE Three Phase input with 5 wires (Line 1, Line 2, Line 3, Neutral and Protective Earth). two-phase-4-wire-L1-L2-N-PE Two Phase input with 4 wires (Line 1, Line 2, Neutral, and Protective Earth).
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.30,LIEBERT-GP-PDU-MIB::lgpPduPsEntryEpInputRated,Unsigned32,read-only,,current,,Rated Input Line Voltage for the power source (i.e. this is the nominal line input voltage; it is NOT a measured voltage). The value is defined to be the rated line voltage (either line-to-neutral or line-to-line depending upon the power source's type).
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.35,LIEBERT-GP-PDU-MIB::lgpPduPsEntryEcInputRated,Unsigned32,read-only,,current,,This is the rated input line current for the module (it is NOT the measured current).
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.40,LIEBERT-GP-PDU-MIB::lgpPduPsEntryFreqRated,Unsigned32,read-only,,current,,Rated input line frequency for this power source (i.e. This is the expected line frequency; it is NOT a measured frequency; it is typically 50 Hz or 60 Hz).
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.50,LIEBERT-GP-PDU-MIB::lgpPduPsEntryEnergyAccum,Unsigned32,read-write,,current,,Total accumulated energy, measured at the power source input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be reset. Writing a non-zero value is invalid and shall result in a write error and the total energy value remains unchanged. If the energy has not been reset and has not wrapped, then this is the total energy since installation. This value persists across boot events.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.55,LIEBERT-GP-PDU-MIB::lgpPduPsEntrySerialNum,OCTET,read-only,,current,,This is a unique serial number of the power supply. This number is assigned to the power supply at the time of manufacture.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.60,LIEBERT-GP-PDU-MIB::lgpPduPsEntryFirmwareVersion,OCTET,read-only,,current,,This is the version of the firmware installed on the PDU's power supply.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.65,LIEBERT-GP-PDU-MIB::lgpPduPsEntryPwrTotal,Unsigned32,read-only,,current,,Total input power for this power supply. This is the sum of the power for all phases
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.70,LIEBERT-GP-PDU-MIB::lgpPduPsEntryEcNeutral,Unsigned32,read-only,,current,,The neutral current measured at the PDU's power source.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.75,LIEBERT-GP-PDU-MIB::lgpPduPsEntryEcNeutralThrshldOvrWarn,Unsigned32,read-write,,current,,The threshold at which an over current warning is activated. If the measured neutral current (lgpPduPsEntryEcNeutral) is above this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over neutral current warning (lgpConditionSource1NeutralOverCurrent) is activated.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.80,LIEBERT-GP-PDU-MIB::lgpPduPsEntryEcNeutralThrshldOvrAlarm,Unsigned32,read-write,,current,,The threshold at which an over current alarm is activated. If the measured neutral current (lgpPduPsEntryEcNeutral) is above this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over neutral current alarm (lgpConditionSource1NeutralOverCurrent) is activated.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.85,LIEBERT-GP-PDU-MIB::lgpPduPsEntryUnbalancedLoadThrshldAlarm,Unsigned32,read-write,,current,,The parameter is for setting the maximum acceptable percentage of 'Unbalanced Load' between any two phases. This setting shall trigger an alarm when the % load between any two phases varies by a percentage higher than this configurable value. If this value is 0% then the alarm would be deactivated.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.90,LIEBERT-GP-PDU-MIB::lgpPduPsEntryApTotal,Unsigned32,read-only,,current,,Total Apparent power for this power supply. This is the sum of the apparent power for all phases
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.95,LIEBERT-GP-PDU-MIB::lgpPduPsEntryPfTotal,Integer32,read-only,,current,,Total power factor, which is real power/apparent power for all phases combined. This is the sum of the real power for all phases divided by the sum of the apparent power for all phases.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.100,LIEBERT-GP-PDU-MIB::lgpPduPsEntryEcResidual,Unsigned32,read-only,,current,,The measured residual current.
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.105,LIEBERT-GP-PDU-MIB::lgpPduPsEntryEcResidualThrshldOvrAlarm,Unsigned32,read-write,,current,,The threshold at which an over current alarm is activated. If the measured residual current (lgpPduPsEntryEcResidual) is above this value, an over current alarm is activated. Setting this to 0mA disables the alarm.
.1.3.6.1.4.1.476.1.42.3.8.30.40,LIEBERT-GP-PDU-MIB::lgpPduPsLineTable,,not-accessible,,current,,This table contains a list of PDU's power source line/phase measurements. The table contains zero, one, or many rows, depending upon the number of PDU's Power Sources being monitored. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the managed PDU's power supply(s). Each row in the table represents a particular phase/line measurement of a power supply for a given PDU.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntry,,not-accessible,lgpPduEntryIndex:lgpPduPsEntryIndex:lgpPduPsLineEntryIndex,current,,This entry defines the attributes to be populated in the various columns of the 'lgpPduPsLineTable'. The table is index by three indexes which taken together uniquely identify line/phase information for a given power source within a PDU. The 'lgpPduEntryIndex' is an index into the 'lgpPduTable'. This identifies the PDU that the power source is on. The 'lgpPduPsEntryIndex' is an index that together with the 'lgpPduEntryIndex' uniquely identifies the power source within the PDU that the row in this table represents. The final index 'lgpPduPsLineEntryIndex' identifies the particular line/phase that the measurement applies to within the identified power source.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.5,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryIndex,Unsigned32,not-accessible,,current,,This is the index that indicates the line/phase of the measurements in the given row of the 'lgpPduPsLineTable'.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.10,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryId,Unsigned32,read-only,,current,,Unique identifier (within a PDU) for the PDU's power source. The object may not be available in non-modular systems.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.15,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryLine,INTEGER,read-only,,current,phase1(1):phase2(2):phase3(3),The line number (phase) that the measurement represents for all measurements in a given row of the table. Note that this always matches the lgpPduPsLineEntryIndex of the same row in the table. The line/phases are as follows: Line# Description ----- --------------------------------------------------- 1 Line 1-N (A) for Line-to-Neutral measurements 2 Line 2-N (B) for Line-to-Neutral measurements 3 Line 3-N (C) for Line-to-Neutral measurements 1 Line 1-2 (A-B) for Line-to-Line measurements 2 Line 2-3 (B-C) for Line-to-Line measurements 3 Line 3-1 (C-A) for Line-to-Line measurements 
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.19,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEpLNTenths,Unsigned32,read-only,,current,,Alternating Current RMS Line to Neutral Electrical Potential measurement. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.20,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEpLN,Unsigned32,read-only,,current,,Alternating Current RMS Line to Neutral Electrical Potential measurement. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.21,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEc,Unsigned32,read-only,,current,,Total input line-to-neutral electrical current. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.22,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcHundredths,Unsigned32,read-only,,current,,Total input line-to-neutral electrical current. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.35,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldUndrAlarm,Unsigned32,read-write,,current,,The threshold at which an under current alarm is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or below this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an under current alarm is activated.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.36,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldOvrWarn,Unsigned32,read-write,,current,,The threshold at which an over current warning is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over current warning is activated.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.37,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldOvrAlarm,Unsigned32,read-write,,current,,The threshold at which an over current alarm is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over current alarm is activated.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.38,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcAvailBeforeAlarm,Unsigned32,read-only,,current,,The amount that the current/amperage may increase from its present value before an over current alarm occurs.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.39,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcUsedBeforeAlarm,Unsigned32,read-only,,current,,The percent of current utilization relative to the over current alarm threshold.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.60,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEpLL,Unsigned32,read-only,,current,,Line to Line Electrical Potential. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.61,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEpLLTenths,Unsigned32,read-only,,current,,Line to Line Electrical Potential. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.62,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcAvailBeforeAlarmHundredths,Unsigned32,read-only,,current,,The amount that the current/amperage may increase from its present value before an over current alarm occurs.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.63,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryPwrLN,Unsigned32,read-only,,current,,The line-to-neutral measurement of the Real Power (Watts). The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.64,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryPwrLL,Unsigned32,read-only,,current,,The line-to-line measurement of the Real Power (Watts). The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.65,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryApLN,Unsigned32,read-only,,current,,The line-to-neutral measurement of the Apparent Power (VA). The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.66,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryApLL,Unsigned32,read-only,,current,,The line-to-line measurement of the Apparent Power (VA). The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.67,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryPfLN,Integer32,read-only,,current,,The line-to-neutral measurement of the Power Factor of the power source. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.68,LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryPfLL,Integer32,read-only,,current,,The line-to-line measurement of the Power Factor of the power source. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
.1.3.6.1.4.1.476.1.42.3.8.40,LIEBERT-GP-PDU-MIB::lgpPduReceptacleBranch,,,,,,This sub-tree contains information about PDU receptacle branches.
.1.3.6.1.4.1.476.1.42.3.8.40.19,LIEBERT-GP-PDU-MIB::lgpPduRbTableCount,Unsigned32,read-only,,current,,Number of receptacle branches in the lgpPduRbTable.
.1.3.6.1.4.1.476.1.42.3.8.40.20,LIEBERT-GP-PDU-MIB::lgpPduRbTable,,not-accessible,,current,,This table contains a list of PDU Receptacle branches. The table contains zero, one, or many rows, depending upon the number of PDUs being managed and how many receptacle branches each PDU has installed. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDUs being managed. Each row in the table represents a receptacle branch for a given PDU. The PDU that a branch is installed on is indicated by the column lgpPduEntryIndex. The branch within the lgpPduEntryIndex PDU is indicated by the column lgpPduRbEntryIndex.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1,LIEBERT-GP-PDU-MIB::lgpPduRbEntry,,not-accessible,lgpPduEntryIndex:lgpPduRbEntryIndex,current,,This entry defines the attributes to be populated in the various columns of the 'lgpPduRbTable'. The table is indexed by both the 'lgpPduEntryIndex' and 'lgpPduRbEntryIndex'. The lgpPduEntryIndex specifies the PDU, defined in the lgpPduTable that the branch is on. The lgpPduRbEntryIndex uniquely identifies the branch within that PDU. Taken together the two indexes uniquely identify a branch being monitored by this agent. 
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.1,LIEBERT-GP-PDU-MIB::lgpPduRbEntryIndex,Unsigned32,not-accessible,,current,,This is the index that indicates the row of the 'lgpPduRbTable'
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.5,LIEBERT-GP-PDU-MIB::lgpPduRbEntryId,Unsigned32,read-only,,current,,A unique id representing the receptacle branch within the collection of branches being monitored by this agent. The uniqueness of this id is within the PDUs being managed by a single agent.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.8,LIEBERT-GP-PDU-MIB::lgpPduRbEntryUsrLabel,OCTET,read-write,,current,,A user assigned label representing the receptacle branch.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.20,LIEBERT-GP-PDU-MIB::lgpPduRbEntrySysAssignLabel,OCTET,read-only,,current,,System assigned identifier for this receptacle branch. The value is independent of any user assigned label or tag. The exact format of this label is system dependent and is subject to change, therefore, it should not be referenced for programmatic use.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.25,LIEBERT-GP-PDU-MIB::lgpPduRbEntryPositionRelative,Unsigned32,read-only,,current,,This is a one-based value that indicates the relative position of the branch within the PDU.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.30,LIEBERT-GP-PDU-MIB::lgpPduRbEntrySerialNum,OCTET,read-only,,current,,A globally unique serial number for this branch. This number is assigned to the branch at the time of manufacture and can not be modified. NOTE: Generally only PDUs with replaceable receptacle branches will have serial numbers.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.35,LIEBERT-GP-PDU-MIB::lgpPduRbEntryModel,OCTET,read-only,,current,,This is the model designation for this receptacle branch.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.40,LIEBERT-GP-PDU-MIB::lgpPduRbEntryFirmwareVersion,OCTET,read-only,,current,,This is the firmware version number of the control software running on the receptacle branch. Only PDUs with replaceable receptacle branches will typically support this object.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.41,LIEBERT-GP-PDU-MIB::lgpPduRbEntryUsrTag1,OCTET,read-write,,current,,This is a user assigned Tag for the receptacle branch. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be unique for this unit or across other units.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.42,LIEBERT-GP-PDU-MIB::lgpPduRbEntryUsrTag2,OCTET,read-write,,current,,This is a user assigned Tag for the receptacle branch. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be unique for this unit or across other units.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.45,LIEBERT-GP-PDU-MIB::lgpPduRbEntryReceptacleType,INTEGER,read-only,,current,not-specified(0):nema-5-20R-20-Amp(1):iec-C13-sheet-F-10-Amp(2):iec-C19-sheet-J-16-Amp(3):iec-C13-sheet-F-10-Amp-and-iec-C19-sheet-J-16-Amp(4):nema-5-20R-20-Amp-and-iec-C13-sheet-F-10-Amp(5):nema-5-20R-20-Amp-and-iec-C19-sheet-J-16-Amp(6):cee-7-type-E-schuko(7):nema-L6-30R-30-Amp(8),This enumeration represents the type of receptacles installed on this receptacle branch. All receptacles on this branch are of this type/style. not-specified If this value is returned, either the receptacle type has not been specified/configured or the agent monitoring this PDU does not have a SNMP enumeration defined to the type. 
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.50,LIEBERT-GP-PDU-MIB::lgpPduRbEntryCapabilities,INTEGER,read-only,,current,not-specified(0):no-optional-capabilities(1):measurement-only(2):measurement-and-control(3):control-only(4):current-measurement-only(5):current-measurement-and-control(6),Receptacle branch capabilities describes what an individual branch is capable of. no-optional-capabilities The branch is unable to report measurements and lacks control capabilities. measurement-only The branch is capable of reporting multiple measurements. measurement-and-control The branch is capable of reporting multiple measurements and controlling the state. control-only The branch is capable of controlling the state. current-measurement-only The branch is capable of reporting the current/amperage only. current-measurement-and-control The branch is capable of reporting the current/amperage and has the ability to control the state.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.55,LIEBERT-GP-PDU-MIB::lgpPduRbEntryLineSource,INTEGER,read-only,,current,not-specified(0):line-1-neutral(1):line-2-neutral(2):line-3-neutral(3):line-1-line-2(4):line-2-line-3(5):line-3-line-1(6):line-1-line-2-and-line-1-neutral(7):line-2-line-3-and-line-2-neutral(8):line-3-line-1-and-line-3-neutral(9):unknown-line-neutral(10):unknown-line-line(11),This represents the line source that is supplying power to this receptacle branch. not-specified The line source supplying power to the load for this receptacle branch has not been specified/configured. line-1-N The load for this receptacle branch is supplied by a line-to-neutral configuration. (line 1 to neutral). line-2-N The load for this receptacle branch is supplied by a line-to-neutral configuration. (line 2 to neutral). line-3-N The load for this receptacle branch is supplied by a line-to-neutral configuration. (line 3 to neutral). line-1-line-2 The load for this receptacle branch is supplied by a line-to-line configuration (line 1 to line 2). line-2-line-3 The load for this receptacle branch is supplied by a line-to-line configuration (line 2 to line 3). line-3-line-1 The load for this receptacle branch is supplied by a line-to-line configuration (line 3 to line 1). line-1-line-2-and-line-1-neutral The load for this mixed receptacle branch is supplied by a line-to-line and line-to-neutral configuration (line 1 to line 2 and line 1 to neutral). line-2-line-3-and-line-2-neutral The load for this mixed receptacle branch is supplied by a line-to-line and line-to-neutral configuration (line 2 to line 3 and line 2 to neutral). line-3-line-1-and-line-3-neutral The load for this mixed receptacle branch is supplied by a line-to-line and line-to-neutral configuration (line 3 to line 1 and line 3 to neutral). unknown-line-neutral The load for this branch is supplied by a line-to-neutral configuration. The system is unable to determine which lines are supporting the load. unknown-line-line The load for this branch is supplied by a line-to-line configuration. The system is unable to determine which lines are supporting the load. 
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.60,LIEBERT-GP-PDU-MIB::lgpPduRbEntryRcpCount,Unsigned32,read-only,,current,,The number of receptacles on this receptacle branch.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.70,LIEBERT-GP-PDU-MIB::lgpPduRbEntryEpRated,Unsigned32,read-only,,current,,Rated Line Voltage for the receptacle branch and its associated receptacles (i.e. This is the nominal line voltage that is available to the connected load; it is NOT a measured voltage.)
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.75,LIEBERT-GP-PDU-MIB::lgpPduRbEntryEcRated,Unsigned32,read-only,,current,,This is the rated input line current for the module (it is NOT the measured current).
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.80,LIEBERT-GP-PDU-MIB::lgpPduRbEntryFreqRated,Unsigned32,read-only,,current,,This is the rated electrical frequency for the receptacle branch and its associated receptacles
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.85,LIEBERT-GP-PDU-MIB::lgpPduRbEntryEnergyAccum,Unsigned32,read-write,,current,,Total accumulated energy, measured at the receptacle branch input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be reset. Writing a non-zero value is invalid and shall result in a write error and the total energy value remains unchanged. If the energy has not been reset and has not wrapped, then this is the total energy since installation. This value persists across boot events. NOTE: Resetting this value does not reset the values for the individual receptacles.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.100,LIEBERT-GP-PDU-MIB::lgpPduRbEntryEpLNTenths,Unsigned32,read-only,,current,,The line-to-neutral measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared).
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.115,LIEBERT-GP-PDU-MIB::lgpPduRbEntryPwr,Unsigned32,read-only,,current,,The line-to-neutral measurement of the Real Power (Wattage)
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.120,LIEBERT-GP-PDU-MIB::lgpPduRbEntryAp,Unsigned32,read-only,,current,,The line-to-neutral measurement of the Apparent Power (VA)
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.125,LIEBERT-GP-PDU-MIB::lgpPduRbEntryPf,Integer32,read-only,,current,,The line-to-neutral measurement of the Power Factor of the receptacle branches' input.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.130,LIEBERT-GP-PDU-MIB::lgpPduRbEntryEcHundredths,Unsigned32,read-only,,current,,The line-to-neutral measurement of the Electrical Current measured in Amperes RMS (Root Mean Squared).
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.135,LIEBERT-GP-PDU-MIB::lgpPduRbEntryEcThrshldUndrAlm,Unsigned32,read-write,,current,,The threshold at which an under current alarm is activated. If the measured current (lgpPduRbEntryEc) is equal to or below this percentage of the full scale rated value (lgpPduRbEntryEcRated), an under current alarm is activated
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.140,LIEBERT-GP-PDU-MIB::lgpPduRbEntryEcThrshldOvrWarn,Unsigned32,read-write,,current,,The threshold at which an over current warning is activated. If the measured current (lgpPduRbEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current warning is activated
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.145,LIEBERT-GP-PDU-MIB::lgpPduRbEntryEcThrshldOvrAlm,Unsigned32,read-write,,current,,The threshold at which an over current alarm is activated. If the measured current (lgpPduRbEntryEcLN) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current alarm is activated
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.150,LIEBERT-GP-PDU-MIB::lgpPduRbEntryEcAvailBeforeAlarmHundredths,Unsigned32,read-only,,current,,The amount that the current/amperage may increase from its present value before an over current alarm occurs.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.160,LIEBERT-GP-PDU-MIB::lgpPduRbEntryEcUsedBeforeAlarm,Unsigned32,read-only,,current,,The percent of current utilization relative to the over current alarm threshold.
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.170,LIEBERT-GP-PDU-MIB::lgpPduRbEntryEpLLTenths,Unsigned32,read-only,,current,,The line-to-line measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared).
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.175,LIEBERT-GP-PDU-MIB::lgpPduRbEntrySwOverCurrentProtection,INTEGER,read-write,,current,disable(0):enable(1),The configuration parameter to enable or disable the Branch SW Over Current Protection feature.If the feature is enabled, in case of Over Current Warning or Alarm condition, following action will be taken on the receptacles: Locked & On - No Change Locked & Off - No Change Unlocked & Off - Turn it Off and Lock it Unlocked & On - If load present, No Change. If no load, turn it Off and Lock it. No action will be taken if the feature is disabled. Note: Only applicable to PDU models where receptacle measurement and control is possible. Not applicable to branch monoitoring models disabled This function is disabled. enable This function is enabled.
.1.3.6.1.4.1.476.1.42.3.8.40.40,LIEBERT-GP-PDU-MIB::lgpPduRbLineTable,,not-accessible,,deprecated,,This table contains a list of PDU receptacle branch line/phase measurements. The table contains zero, one, or many rows, depending upon the number of PDUs and the number of receptacle branches on each PDU that are being monitored. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDU(s) being monitored. Each row in the table represents a particular phase/line measurement of a PDU Receptacle Branch. Rows in the table are uniquely identified by three indexes representing respectively the PDU (lgpPduEntryIndex), the receptacle branch (lgpPduRbEntryIndex) and the line/phase being measured (lgpPduRbLineEntryIndex). 
.1.3.6.1.4.1.476.1.42.3.8.40.40.1,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntry,,not-accessible,lgpPduEntryIndex:lgpPduRbEntryIndex:lgpPduRbLineEntryIndex,deprecated,,This entry defines the attributes to be populated in the various columns of the 'lgpPduRbLineTable'. The table is indexed by three indexes. The 'lgpPduEntryIndex' references a PDU in the 'lgpPduTable' to which this receptacle branch line/phase measurement belongs. The 'lgpPduRbEntryIndex' together with the 'lgpPduEntryIndex' references the receptacle branch in the 'lgpPduRbTable'. The 'lgpPduRbLineEntryIndex' represents the line/phase of the measurements in the row of this table. Together these three indexes uniquely identify a phase/line measurement on a receptacle branch within a PDU being monitored by this agent. 
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.1,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryIndex,Unsigned32,not-accessible,,deprecated,,This is the index that indicates the row of the 'lgpPduRbLineTable'
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.5,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryId,Unsigned32,read-only,,deprecated,,Runtime assigned branch identifier.
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.10,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryLine,INTEGER,read-only,,deprecated,phase1(1):phase2(2):phase3(3),The line number or phase that the measurement for this receptacle branch represents for each measurement in this row of the table. The phases are as follows: Line# Description ----- --------------------------------------------------- 1 Line 1-N (A) for Line-to-Neutral measurements 2 Line 2-N (B) for Line-to-Neutral measurements 3 Line 3-N (C) for Line-to-Neutral measurements 1 Line 1-2 (A-B) for Line-to-Line measurements 2 Line 2-3 (B-C) for Line-to-Line measurements 3 Line 3-1 (C-A) for Line-to-Line measurements 
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.19,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryEpLNTenths,Unsigned32,read-only,,deprecated,,The line-to-neutral measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared).
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.20,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryEpLN,Unsigned32,read-only,,deprecated,,The line-to-neutral measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared).
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.21,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryEc,Unsigned32,read-only,,deprecated,,The line-to-neutral measurement of the Electrical Current measured in Amperes RMS (Root Mean Squared).
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.22,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryPwr,Unsigned32,read-only,,deprecated,,The line-to-neutral measurement of the Real Power (Wattage)
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.23,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryAp,Unsigned32,read-only,,deprecated,,The line-to-neutral measurement of the Apparent Power (VA)
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.24,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryPf,Integer32,read-only,,deprecated,,The line-to-neutral measurement of the Power Factor of the receptacle branches' input.
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.25,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryEcHundredths,Unsigned32,read-only,,deprecated,,The line-to-neutral measurement of the Electrical Current measured in Amperes RMS (Root Mean Squared).
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.35,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryEcThrshldUndrAlm,Unsigned32,read-write,,deprecated,,The threshold at which an under current alarm is activated. If the measured current (lgpPduRbLineEntryEc) is equal to or below this percentage of the full scale rated value (lgpPduRbEntryEcRated), an under current alarm is activated
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.36,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryEcThrshldOvrWarn,Unsigned32,read-write,,deprecated,,The threshold at which an over current warning is activated. If the measured current (lgpPduRbLineEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current warning is activated
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.37,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryEcThrshldOvrAlm,Unsigned32,read-write,,deprecated,,The threshold at which an over current alarm is activated. If the measured current (lgpPduRbLineEntryEcLN) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current alarm is activated
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.39,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryEcAvailBeforeAlarmHundredths,Unsigned32,read-only,,deprecated,,The amount that the current/amperage may increase from its present value before an over current alarm occurs.
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.40,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryEcAvailBeforeAlarm,Unsigned32,read-only,,deprecated,,The amount that the current/amperage may increase from its present value before an over current alarm occurs.
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.41,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryEcUsedBeforeAlarm,Unsigned32,read-only,,deprecated,,The percent of current utilization relative to the over current alarm threshold.
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.60,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryEpLL,Unsigned32,read-only,,deprecated,,The line-to-line measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared).
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.61,LIEBERT-GP-PDU-MIB::lgpPduRbLineEntryEpLLTenths,Unsigned32,read-only,,deprecated,,The line-to-line measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared).
.1.3.6.1.4.1.476.1.42.3.8.50,LIEBERT-GP-PDU-MIB::lgpPduReceptacle,,,,,,This sub-tree contains information about PDU receptacles.
.1.3.6.1.4.1.476.1.42.3.8.50.19,LIEBERT-GP-PDU-MIB::lgpPduRcpTableCount,Unsigned32,read-only,,current,,Number of receptacles in the lgpPduRcpTable.
.1.3.6.1.4.1.476.1.42.3.8.50.20,LIEBERT-GP-PDU-MIB::lgpPduRcpTable,,not-accessible,,current,,This table contains a list of PDU receptacle entries. The table contains numerous rows representing an individual receptacle, depending upon the number and configuration of the PDU(s) being monitored by the agent. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the managed PDU(s). Each row in the table represents a receptacle in the system. 
.1.3.6.1.4.1.476.1.42.3.8.50.20.1,LIEBERT-GP-PDU-MIB::lgpPduRcpEntry,,not-accessible,lgpPduEntryIndex:lgpPduRbEntryIndex:lgpPduRcpEntryIndex,current,,This entry defines the attributes to be populated in the various columns of the 'lgpPduRcpTable'. This table is indexed by three indexes. The 'lgpPduEntryIndex' references a PDU in the 'lgpPduTable' that a given row in this table represents. The 'lgpPduRbEntryIndex' together with the 'lgpPduEntryIndex' specifies a row in the 'lgpPduRbTable' that the receptacle belongs. The 'lgpPduRcpEntryIndex' identifies the particular receptacle within the branch. 
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.1,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryIndex,Unsigned32,not-accessible,,current,,This is the index that indicates the receptacle position on the receptacle branch. This along with the other two indexes on the lgpPduRcpTable uniquely identify the receptacle in this table.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.5,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryId,Unsigned32,read-only,,current,,A runtime assigned receptacle identification number.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.10,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryUsrLabel,OCTET,read-write,,current,,User assigned label for this receptacle.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.15,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryUsrTag1,OCTET,read-write,,current,,User assigned Tag to assist in identifying or grouping this receptacle within the end-users domain.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.20,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryUsrTag2,OCTET,read-write,,current,,User assigned Tag to assist in identifying or grouping this receptacle within the end-users domain.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.25,LIEBERT-GP-PDU-MIB::lgpPduRcpEntrySysAssignLabel,OCTET,read-only,,current,,System assigned identifier representing the receptacle. The value is independent of any user assigned label or tag. The exact format of this label is system dependent and is subject to change, therefore, it should not be referenced for programmatic use.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.30,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryPosition,Unsigned32,read-only,,current,,A number representing the position of the receptacle within the receptacle branch.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.40,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryType,INTEGER,read-only,,current,not-specified(0):nema-5-20R-20-Amp(1):iec-C13-sheet-F-10-Amp(2):iec-C19-sheet-J-16-Amp(3):cee-7-type-E-schuko(7):nema-L6-30R-30-Amp(8),The type or form of receptacle. The enumerations are specified in well-known industry standard terms and abbreviations.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.45,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryLineSource,INTEGER,read-only,,current,not-specified(0):line-1-N(1):line-2-N(2):line-3-N(3):line-1-line-2(4):line-2-line-3(5):line-3-line-1(6):unknown-line-neutral(7):unknown-line-line(8),This represents the line source that is supplying power to this receptacle. not-specified The line source supplying power to the load for this receptacle has not been specified/configured. line-1-N The load for this receptacle is supplied by a line-to-neutral configuration. (line 1 to neutral). line-2-N The load for this receptacle is supplied by a line-to-neutral configuration. (line 2 to neutral). line-3-N The load for this receptacle is supplied by a line-to-neutral configuration. (line 3 to neutral). line-1-line-2 The load for this receptacle is supplied by a line-to-line configuration (line 1 to line 2). line-2-line-3 The load for this receptacle is supplied by a line-to-line configuration (line 2 to line 3). line-3-line-1 The load for this receptacle is supplied by a line-to-line configuration (line 3 to line 1). unknown-line-neutral The load for this receptacle is supplied by a line-to-neutral configuration. The system is unable to determine which lines are supporting the load. unknown-line-line The load for this receptacle is supplied by a line-to-line configuration. The system is unable to determine which lines are supporting the load. 
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.50,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryCapabilities,INTEGER,read-only,,current,not-specified(0):no-optional-capabilities(1):measurement-only(2):measurement-and-control(3):control-only(4):current-measurement-only(5):current-measurement-and-control(6),Receptacle capabilities describes what an individual receptacle is capable of. no-optional-capabilities The receptacle is unable to report measurements and lacks control capabilities. measurement-only The receptacle is capable of reporting multiple measurements. measurement-and-control The receptacle is capable of reporting multiple measurements and controlling the state. control-only The receptacle is capable of controlling the state. current-measurement-only The receptacle is capable of reporting the current/amperage only. current-measurement-and-control The receptacle is capable of reporting the current/amperage and has the ability to control the state.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.55,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEp,Unsigned32,read-only,,current,,Voltage being delivered to the load attached to the receptacle. Alternating Current RMS Electrical Potential measurement.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.56,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEpTenths,Unsigned32,read-only,,current,,Voltage being delivered to the load attached to the receptacle. Alternating Current RMS Electrical Potential measurement.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.60,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEc,Unsigned32,read-only,,current,,Current (amperage) being delivered to the load attached to the receptacle. Electrical Current is measured in Amperes RMS (Root Mean Squared).
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.61,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEcHundredths,Unsigned32,read-only,,current,,Current (amperage) being delivered to the load attached to the receptacle. Electrical Current is measured in Amperes RMS (Root Mean Squared).
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.65,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryPwrOut,Unsigned32,read-only,,current,,Real Power (watts) being delivered to the load attached to the receptacle.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.70,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryApOut,Unsigned32,read-only,,current,,Apparent Power (volt-amps) being delivered to the load attached to the receptacle.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.75,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryPf,Unsigned32,read-only,,current,,Receptacle Power Factor, which is the ratio of real power to apparent power (i.e. ratio of watts to volts-amps).
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.80,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryFreq,Unsigned32,read-only,,current,,The measured line frequency being delivered to the load attached to the receptacle.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.85,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEnergyAccum,Unsigned32,read-write,,current,,Total accumulated energy, measured at the module input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be reset. Writing a non-zero value is invalid and shall result in a write error and the total energy value remains unchanged. If the energy has not been reset and has not wrapped, then this is the total energy since installation. This value persists across boot events.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.90,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryPwrOnDelay,Unsigned32,read-write,,current,,The amount of time to wait before power is applied to the receptacle after a power strip is turned on or rebooted. This can be used to stagger the powering of multiple receptacles in order to prevent a large initial current draw.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.95,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryPwrState,INTEGER,read-only,,current,unknown(0):off(1):on(2):off-pending-on-delay(3),unknown The current power state is unknown. off The current power state of the receptacle is OFF. on The current power state of the receptacle is ON. off-pending-on-delay The current power state of the receptacle is OFF. The power will be ON at the expiration of the ON delay of this receptacle.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.96,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryPwrUpState,INTEGER,read-write,,current,on(1):off(2):last-state(3),The 'Power Up State' defines the state to which the receptacle shall return  timer (lgpPduRcpEntryPwrOnDelay). last-state
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.100,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryControl,INTEGER,read-write,,current,off(0):on(1):cycle-power(2),This object represents the current and persistent (configured) power state of the receptacle. The receptacle can also be controlled by writing to this object. off The current and persisted (configured) power state of the receptacle is 'off'. When writing 'off' to this object the receptacle, if ON, will be turned OFF and its persistent (configured) power state will be set to 'off'. on The current and persisted (configured) power state of the receptacle is 'on'. When writing 'on' to this object the receptacle, if 'off', will be turned 'on' and its persistent (configured) power state will be set to 'on'. cycle-power The receptacle is currently in a power-cycle state. The power to the receptacle is being turned off momentarily and will then revert to being 'on'. When writing 'cycle-power' to this OBJECT if the receptacle is 'on' it will be momentarily turned 'off' and then revert to the 'on' state. The receptacle's persistent (configured) power state will be left unchanged ('on'). If the receptacle is OFF writing cycle-power has no affect on the receptacle. 
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.105,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryControlLock,INTEGER,read-write,,current,unknown(0):unlocked(1):locked(2),This object represents the locked state of the receptacle. unknown The lock state of the receptacle is not known at this time. locked If the receptacle is 'locked' then its current persisted (configured) state can not be changed. unlocked If the receptacle is 'unlocked', then a user with proper permissions may change the receptacles state.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.150,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEcThrshldUnderAlarm,Unsigned32,read-write,,current,,The threshold at which an under current alarm is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or below this percentage of the full scale rated value (lgpPduRbEntryEcRated), an under current alarm is activated
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.151,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEcThrshldOverWarn,Unsigned32,read-write,,current,,The threshold at which an over current warning is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current warning is activated
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.152,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEcThrshldOverAlarm,Unsigned32,read-write,,current,,The threshold at which an over current alarm is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current alarm is activated
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.159,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEcAvailBeforeAlarmHundredths,Unsigned32,read-only,,current,,The amount that the current/amperage may increase from its present value before an over current alarm occurs.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.160,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEcAvailBeforeAlarm,Unsigned32,read-only,,current,,The amount that the current/amperage may increase from its present value before an over current alarm occurs.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.161,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEcUsedBeforeAlarm,Unsigned32,read-only,,current,,The percent of current utilization relative to the over current alarm threshold.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.162,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEcCrestFactor,Unsigned32,read-only,,current,,Receptacle current crest factor, which is the peak amplitude of the current waveform divided by the RMS value of the waveform.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.200,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryBlinkLED,INTEGER,read-write,,current,noAction(1):blinkLED(2),Blink the receptacle LED. Writing blinkLED(2) will cause the LED to blink for a predefined duration of time. Reading this object will always return noAction(1).
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.205,LIEBERT-GP-PDU-MIB::lgpPduRcpEntrySwOverTemperatureProtection,INTEGER,read-write,,current,disable(0):enable(1),The configuration parameter to enable or disable the Receptacle SW Over Temperature Protection feature If the feature is enabled, in case of Over Temperature Alarm condition, following action will be taken on the receptacles: Locked & Off - No Change Unlocked & Off - No Change Unlocked & On - Turn it Off. Locked & On - Turn it Off and keep it Locked. No action will be taken if the feature is disabled.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.210,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryOperationCondition,INTEGER,read-only,,current,normalOperation(1):normalWithWarning(2):normalWithAlarm(3):abnormal(4),Receptacle Operating Condition - indicates the condition of the receptacle. The operating condition has the following: Normal Normal operation without any alarm or warning. Alarm An Alarm condition due to over/under current. Warning A Warning condition due to over/under current Abnormal A condition in which the outlet is in 'Power Off State' but still drawing current.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.215,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryCriticality,INTEGER,read-write,,current,critical(0):notCritical(1),The configuration parameter can be used by the user to mark a receptacle as critical or non-critical.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.220,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryPostOnDelay,Unsigned32,read-write,,current,,The 'Post On Delay' is the time interval (in seconds) that the PDU waits after a command is issued to switch ON a receptacle before applying power to the receptacle A value of zero implies that there is no delay (i.e. the receptacle is turned on immediately on command issue).
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.225,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryPostOffDelay,Unsigned32,read-write,,current,,The 'Post Off Delay' is the time interval (in seconds) that the PDU waits after a command is issued to switch OFF a receptacle before removing power from the receptacle A value of zero implies that there is no delay (i.e. the receptacle is turned off immediately on command issue).
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.230,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryAddReceptacleToGroup,OBJECT,read-write,,current,,This receptacle can be added to a group by writing a corresponding OID to this column. The OID must be a pointer to the  lgpPduRcpGroupUsrLabel from the lgpPduRcpGroupTable. For example, to add this receptacle to group 1, the oid  .1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1 would be written to  this column.
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.235,LIEBERT-GP-PDU-MIB::lgpPduRcpEntryRemoveReceptacleFromGroup,OBJECT,read-write,,current,,This receptacle can be removed from a group by writing a corresponding OID to this column. The OID must be a pointer to the  lgpPduRcpGroupUsrLabel from the lgpPduRcpGroupTable. For example, to remove this receptacle from group 1, the oid  .1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1 would be written to  this column.
.1.3.6.1.4.1.476.1.42.3.8.50.30,LIEBERT-GP-PDU-MIB::lgpPduRcpGroup,,,,,,This sub-tree contains information about receptacle groups. Receptacle groups are supported by some PDU's and allow control of  multiple receptacles at a time by issuing commands to an associated  receptacle group.
.1.3.6.1.4.1.476.1.42.3.8.50.30.9,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupTableCount,Unsigned32,read-only,,current,,Number of receptacle groups (rows) in the lgpPduRcpGroupTable.
.1.3.6.1.4.1.476.1.42.3.8.50.30.10,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupTable,,not-accessible,,current,,This table contains a list of the possible receptacle groups that can be created. The table contains a fixed number of rows, which is the maximum number of receptacle groups that can be used.
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupEntry,,not-accessible,lgpPduRcpGroupIndex,current,,This entry defines the attributes to be populated in the various columns of the 'lgpPduRcpGroupTable'. This table is indexed by lgpPduRcpGroupIndex. 
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupIndex,Unsigned32,not-accessible,,current,,This is an index into the table. There will always be 64 rows, each representing a separate receptacle group. 
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.10,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupUsrLabel,OCTET,read-write,,current,,User assigned identifier for this receptacle group.
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.20,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupDeleteGroup,INTEGER,read-write,,current,no-action(0):delete-receptacle-group(1),This column will delete the receptacles from the group when written to.
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.30,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupControlPower,INTEGER,read-write,,current,no-action(0):off(1):on(2):cycle-power(3),This column controls the power to the group of receptacles. The corresponding operation will be performed on all receptacles that have been added to the group.  
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.40,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupControlLock,INTEGER,read-write,,current,no-action(0):unlock(1):lock(2),This column controls the locking of the group of receptacles. The corresponding operation will be performed on all receptacles that have been added to the group.  
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.50,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupBlinkLED,INTEGER,read-write,,current,no-action(0):blinkLED(1),This column will blink the LED's associated with all receptacles that are part of the group.  
.1.3.6.1.4.1.476.1.42.3.8.50.30.19,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupDisplayTableCount,Unsigned32,read-only,,current,,Number of rows currently in the lgpPduRcpGroupDisplayTable.
.1.3.6.1.4.1.476.1.42.3.8.50.30.20,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupDisplayTable,,not-accessible,,current,,This table is used to display which receptacle groups are currently defined and which receptacles are associated with each group. The table will have 0 rows when no receptacles have been added to any receptacle groups. If a single receptacle has been added to 2 different groups,  there will be 2 rows in the table. 
.1.3.6.1.4.1.476.1.42.3.8.50.30.20.1,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupDisplayEntry,,not-accessible,lgpPduRcpGroupIndex:lgpPduEntryIndex,current,,This entry defines the attributes to be populated in the various columns of the 'lgpPduRcpGroupDisplayTable'. This table is indexed by two indexes.  The 'lgpPduRcpGroupIndex' references a receptacle group in the 'lgpPduRcpGroupTable' that a given row in this table represents. The 'lgpPduEntryIndex' references a PDU in the 'lgpPduTable'  that identifies the particular PDU receptacle list  within the receptacle group. 
.1.3.6.1.4.1.476.1.42.3.8.50.30.20.1.10,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupDisplayIndex,Unsigned32,not-accessible,,current,,This is an index into the table. There can be zero or more rows in this table.
.1.3.6.1.4.1.476.1.42.3.8.50.30.20.1.20,LIEBERT-GP-PDU-MIB::lgpPduRcpGroupDisplayGroup,OCTET,read-only,,current,,This column displays the PDU receptacle list of the specified  receptacle group. The value in this column is a comma delimted string that decribes For example, if receptacles 1 and 3 of branch A and receptacles 2 and 4  of branch B are members of the receptacle group, this column  would show: A-1,A-3,B-2,B-4
.1.3.6.1.4.1.476.1.42.3.8.60,LIEBERT-GP-PDU-MIB::lgpPduAuxiliarySensors,,,,,,This sub-tree contains information about PDU Auxiliary Sensors.
.1.3.6.1.4.1.476.1.42.3.8.60.5,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorCount,Unsigned32,read-only,,current,,Number of auxiliary sensors in the lgpPduAuxSensorTable.
.1.3.6.1.4.1.476.1.42.3.8.60.10,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTable,,not-accessible,,deprecated,,This table contains a list of the PDU's Auxiliary Sensors. The table contains zero, one, or more rows, depending upon the number of PDUs being monitored and the number of auxiliary sensors installed for each PDU. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDUs being monitored. Each row in the table represents an auxiliary sensor in a PDU.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorEntry,,not-accessible,lgpPduEntryIndex:lgpPduAuxSensorIndex,deprecated,,This entry defines the attributes to be populated in the various columns of the 'lgpPduAuxSensorTable'. This table is indexed by both the 'lgpPduEntryIndex' which is the sole index into the 'lgpPduTable' and the 'lgpPduAuxSensorIndex'which is a unique identifier for the auxiliary sensor attached to the given PDU. Taken together these two indexes uniquely identify an Auxiliary Sensor within this agent.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.1,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorIndex,Unsigned32,not-accessible,,deprecated,,This is the index indicating the nth element of the table.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.5,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorMeasType,INTEGER,read-only,,deprecated,not-specified(0):temperature(1):humidity(2):temperature-and-humidity(3),not-specified The type of sensor is unknown. temperature The sensor in this row of the table measures temperature. humidity The sensor in this row of the table measures relative humidity. temperature-and-humidity The sensor in this row of the table measures both temperature and relative humidity.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.10,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorId,Unsigned32,read-only,,deprecated,,System assigned auxiliary sensor identification number. The value assigned is product specific.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.15,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorSysAssignLabel,OCTET,read-only,,deprecated,,Label assigned to the auxiliary sensor at runtime by the system. The value is independent of any user assigned label or asset tag.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.20,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorPositionRelative,Unsigned32,read-only,,deprecated,,Auxiliary sensor relative position. This is a one-based value that indicates the sensor's position relative to the sensor string connector.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.25,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorUsrLabel,OCTET,read-write,,deprecated,,User assigned auxiliary sensor label.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.30,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorUsrTag1,OCTET,read-write,,deprecated,,User assigned Tag to assist in identifying or grouping this auxiliary sensor within the end-users domain.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.35,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorUsrTag2,OCTET,read-write,,deprecated,,User assigned Tag to assist in identifying or grouping this auxiliary sensor within the end-users domain.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.40,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTempSerialNum,OCTET,read-only,,deprecated,,The temperature sensor's globally unique serial number assigned at the time of manufacture.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.45,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorHumSerialNum,OCTET,read-only,,deprecated,,The humidity sensor's globally unique serial number assigned at the time of manufacture.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.50,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTempMeasurementDegF,Integer32,read-only,,deprecated,,Temperature measured at the temperature sensor reported in degrees Fahrenheit.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.55,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTempThrshldUndrAlmDegF,Integer32,read-write,,deprecated,,Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.60,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTempThrshldOvrAlmDegF,Integer32,read-write,,deprecated,,Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.65,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTempThrshldUndrWarnDegF,Integer32,read-write,,deprecated,,Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.70,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTempThrshldOvrWarnDegF,Integer32,read-write,,deprecated,,Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.75,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTempMeasurementDegC,Integer32,read-only,,deprecated,,Temperature measured at the temperature sensor reported in degrees Celsius.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.80,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTempThrshldUndrAlmDegC,Integer32,read-write,,deprecated,,Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.85,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTempThrshldOvrAlmDegC,Integer32,read-write,,deprecated,,Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.90,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTempThrshldUndrWarnDegC,Integer32,read-write,,deprecated,,Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.95,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTempThrshldOvrWarnDegC,Integer32,read-write,,deprecated,,Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.100,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorHumMeasurement,Unsigned32,read-only,,deprecated,,Relative Humidity measured at the humidity sensor.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.105,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorHumThrshldUndrAlm,Unsigned32,read-write,,deprecated,,Under relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.110,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorHumThrshldOvrAlm,Unsigned32,read-write,,deprecated,,Over relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.115,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorHumThrshldUndrWarn,Unsigned32,read-write,,deprecated,,Under relative humidity warning threshold. A warning is activated if the relative humidity is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.120,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorHumThrshldOvrWarn,Unsigned32,read-write,,deprecated,,Over relative humidity warning threshold. A warning is activated if the relative humidity is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasTable,,not-accessible,,current,,This table contains a list of the PDU's Auxiliary Sensor Measurements. The table contains zero, one, or more rows, depending upon the number of PDUs being monitored, the number of auxiliary sensors installed for each PDU, and the number of measurements within each sensor. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDUs being monitored. Each row in the table represents an auxiliary sensor measurement in a PDU.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasEntry,,not-accessible,lgpPduEntryIndex:lgpPduAuxMeasSensorIndex:lgpPduAuxMeasSensorMeasurementIndex,current,,This entry defines the attributes to be populated in the various columns of the 'lgpPduAuxMeasTable'. This table is indexed by 'lgpPduEntryIndex' which is the sole index into the 'lgpPduTable', 'lgpPduAuxSensorIndex' which is a unique identifier for the auxiliary sensor attached to the given PDU, and 'lgpPduAuxMeasSensorMeasurementIndex' which is the measurement's index identified on the sensor. Taken together these three indexes uniquely identify an Auxiliary Sensor Measurement within this agent.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.1,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasSensorIndex,Unsigned32,not-accessible,,current,,This is the index indicating the sensor the measurement is accessed from.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.5,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasSensorMeasurementIndex,Unsigned32,not-accessible,,current,,This is the measurement's index identified on the sensor.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.10,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasType,INTEGER,read-only,,current,not-specified(0):temperature(1):humidity(2):door-closure(3):contact-closure(4):differential-pressure(5):leak-detection(6),not-specified The type of measurement is unknown. temperature The measurement in this row of the table measures temperature. humidity The measurement in this row of the table measures relative humidity. door-closure The measurement in this row of the table measures the state of a door. contact-closure The measurement in this row of the table measures the state of a contact closure. differential-pressure The measurement in this row of the table measures differential pressure. leak-detection The measurement in this row of the table measures the state of a leak detection sensor.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.15,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasSensorSysAssignLabel,OCTET,read-only,,current,,Label assigned to the auxiliary sensor at runtime by the system. The value is independent of any user assigned label or asset tag.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.20,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasUsrLabel,OCTET,read-write,,current,,User assigned auxiliary sensor measurement label.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.25,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasUsrTag1,OCTET,read-write,,current,,User assigned Tag to assist in identifying or grouping this auxiliary sensor measurement within the end-users domain.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.30,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasUsrTag2,OCTET,read-write,,current,,User assigned Tag to assist in identifying or grouping this auxiliary sensor measurement within the end-users domain.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.35,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasSensorSerialNum,OCTET,read-only,,current,,The sensor's globally unique serial number assigned at the time of manufacture.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.40,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasTempDegF,Integer32,read-only,,current,,Temperature measured at the temperature sensor reported in degrees Fahrenheit.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.50,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasTempThrshldUndrAlmDegF,Integer32,read-write,,current,,Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.55,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasTempThrshldOvrAlmDegF,Integer32,read-write,,current,,Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.60,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasTempThrshldUndrWarnDegF,Integer32,read-write,,current,,Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.65,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasTempThrshldOvrWarnDegF,Integer32,read-write,,current,,Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.70,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasTempDegC,Integer32,read-only,,current,,Temperature measured at the temperature sensor reported in degrees Celsius.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.75,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasTempThrshldUndrAlmDegC,Integer32,read-write,,current,,Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.80,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasTempThrshldOvrAlmDegC,Integer32,read-write,,current,,Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.85,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasTempThrshldUndrWarnDegC,Integer32,read-write,,current,,Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.90,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasTempThrshldOvrWarnDegC,Integer32,read-write,,current,,Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.95,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasHum,Unsigned32,read-only,,current,,Relative Humidity measured at the humidity sensor.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.100,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasHumThrshldUndrAlm,Unsigned32,read-write,,current,,Under relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.105,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasHumThrshldOvrAlm,Unsigned32,read-write,,current,,Over relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.110,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasHumThrshldUndrWarn,Unsigned32,read-write,,current,,Under relative humidity warning threshold. A warning is activated if the relative humidity is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.115,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasHumThrshldOvrWarn,Unsigned32,read-write,,current,,Over relative humidity warning threshold. A warning is activated if the relative humidity is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.120,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasDrClosureState,INTEGER,read-only,,current,not-specified(0):open(1):closed(2),The state of a door sensor measurement. not-specified The door state is unknown. open The door is in the open state. closed The door is in the closed state.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.125,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasDrClosureConfig,INTEGER,read-write,,current,disabled(0):alarm-when-open(1),Configure door state alarms. This object provides the ability to select when a door closure measurement should cause an alarm. disabled The door state will never result in alarm. alarm-when-open Activate an alarm when the door state becomes open.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.130,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasCntctClosureState,INTEGER,read-only,,current,not-specified(0):open(1):closed(2),The state of a contact closure sensor measurement. not-specified The contact closure state is unknown. open The contact closure is in the open state. closed The contact closure is in the closed state.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.135,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasCntctClosureConfig,INTEGER,read-write,,current,disabled(0):alarm-when-open(1):alarm-when-closed(2),Configure contact closure state alarms. This object provides the ability to select when a contact closure measurement should activate an alarm. disabled The contact closure state will never result in alarm. alarm-when-open Activate an alarm when the contact closure state becomes open. alarm-when-closed Activate an alarm when the contact closure state becomes closed.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.140,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasDiffPressure,Integer32,read-only,,current,,Pressure difference measured at the differential pressure sensor.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.145,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasDiffPressureThrshldUndrAlm,Integer32,read-write,,current,,Under differential pressure alarm threshold. An alarm is activated if the differential pressure is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.150,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasDiffPressureThrshldOvrAlm,Integer32,read-write,,current,,Over differential pressure alarm threshold. An alarm is activated if the differential pressure is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.155,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasDiffPressureThrshldUndrWarn,Integer32,read-write,,current,,Under differential pressure warning threshold. A warning is activated if the differential pressure is equal to or below this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.160,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasDiffPressureThrshldOvrWarn,Integer32,read-write,,current,,Over differential pressure warning threshold. A warning is activated if the differential pressure is equal to or above this value.
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.165,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasLeakDetectState,INTEGER,read-only,,current,not-specified(0):no-leak-detected(1):leak-detected(2):leak-detection-pending(3):cable-fault(4),not-specified The leak detection state is unknown. no-leak-detected No leak has been detected. leak-detected A leak has been detected. leak-detection-pending Characterization of possible leak is pending further analysis based on new data received from the sensor. This state may not occur at all, but if it does, it should occur only for a small amount of time before transitioning to  no-leak-detected or leak-detected. cable-fault A fault in the cable has been detected (for example, a disconnected cable). The sensor will not be able to detect a leak. 
.1.3.6.1.4.1.476.1.42.3.8.60.20,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasOrderTable,,not-accessible,,current,,This table contains a list of the PDU's Auxiliary Sensors and their respective 'location' in the lgpPduAuxMeasTable table. This table contains 1 row, for potential sensor for each PDU. The rows in this table are created by the agent based on the maximum number of sensor's supported for each PDU. Each row in the table represents an auxiliary sensor, identified by its factory assigned serial number and its placement in the lgpPduAuxMeasTable. If all serial numbers in this table are empty strings then the location of the sensors in the lgpPduAuxMeasTable will default to the agent's default placement algorithm. If sensors in the lgpPduAuxMeasTable and are not represented by an entry in this table then the location of the unrepresented sensor(s) in the lgpPduAuxMeasTable, and other display mediums, will be determined by the agent, but in no case will an unrepresented sensor occupy a position reserved for a sensor present in this table. Those unrepresented sensor's display location is not guaranteed to be consistent across reboots or rediscovery actions on the sensor bus. Only sensors represented in this table are guarantted consistent placement as specified by their index entries (position) in this table. Note that it is possible to have entries in this table representing sensors that may not exist on the given PDU at runtime. These allocated by not present sensors will reduce the total number of sensors that can be displayed for the given PDU.
.1.3.6.1.4.1.476.1.42.3.8.60.20.1,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasOrderEntry,,not-accessible,lgpPduEntryIndex:lgpPduAuxSensorOrderIndex,current,,This entry defines the attributes to be populated in the various columns of the 'lgpPduAuxMeasOrderTable'. This table is indexed by 'lgpPduEntryIndex' which is the sole index into the 'lgpPduTable' and 'lgpPduAuxMeasSensorIndex' which is a unique identifier for the auxiliary sensor attached to the given PDU. Taken together these two indexes uniquely identify a Auxiliary Sensor within this agent.
.1.3.6.1.4.1.476.1.42.3.8.60.20.1.5,LIEBERT-GP-PDU-MIB::lgpPduAuxSensorOrderIndex,Unsigned32,not-accessible,,current,,Index representing the position within the sensor string on the given PDU
.1.3.6.1.4.1.476.1.42.3.8.60.20.1.15,LIEBERT-GP-PDU-MIB::lgpPduAuxMeasOrderSensorSerialNum,OCTET,read-write,,current,,The sensor's globally unique serial number assigned at the time of manufacture. The sensor represented by this serial number will be, if discovered, by the agent placed in the lgpPduAuxMeasTable at the location specified by the index entries herein. A empty string in this object indicates an open display position that can be occupied by any sensor not given a specific display position in this table.
.1.3.6.1.4.1.476.1.42.3.9,LIEBERT-GP-REGISTRATION-MIB::lgpFlexible,,,,,,This branch is used to register Liebert system object identifiers.
.1.3.6.1.4.1.476.1.42.3.9.10,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleTableCount,Unsigned32,read-only,,current,,This is the number of entries in the lgpFlexibleBasicTable.
.1.3.6.1.4.1.476.1.42.3.9.20,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleBasicTable,,not-accessible,,current,,This table contains data points supported by the managed device. The  data in this table is formatted in string form. This data is also  available in numerical form in the augmented  lgpFlexibleExtendedTable. In this table, the row indexing is not necessarily sequential and  leads to a sparsely populated table.
.1.3.6.1.4.1.476.1.42.3.9.20.1,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleBasicEntry,,not-accessible,IMPLIEDlgpFlexibleEntryIndex,current,,This entry defines the columns to be populated in the 'lgpFlexibleBasicTable'.
.1.3.6.1.4.1.476.1.42.3.9.20.1.1,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleEntryIndex,OBJECT,not-accessible,,current,,This is the index which defines a specific row in the  lgpFlexibleBasicTable. Each row index is associated with a unique data point ID which fixes the data point to its permanent location in the table.
.1.3.6.1.4.1.476.1.42.3.9.20.1.10,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleEntryDataLabel,OCTET,read-only,,current,,A short description of the data reported in this row.
.1.3.6.1.4.1.476.1.42.3.9.20.1.20,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleEntryValue,OCTET,read-write,,current,,A string representation of any data available. This is the preferred method of data access, since this will give fully scaled data for both integer and floating point data, in addition to textual data. If this string column cannot be used, then  columns in the lgpFlexibleExtendedTable must be used in order  to get a fully scaled version of integer data.
.1.3.6.1.4.1.476.1.42.3.9.20.1.30,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleEntryUnitsOfMeasure,OCTET,read-only,,current,,The unit of measure that the value will be presented in. This is not populated when the data does not have a unit of measure associated with it.
.1.3.6.1.4.1.476.1.42.3.9.30,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleExtendedTable,,not-accessible,,current,,This table contains data points supported by the managed device. This table augments the lgpFlexibleBasicTable, providing additional information that may be relevant to advanced users. Values presented  in string format in the lgpFlexibleBasicTable table are also available in  numeric form in this table. Since the lgpFlexibleBasicTable and this table are both indexed by  lgpFlexibleEntryIndex, data applicable to a specific data point can be  found in both tables at the same index.
.1.3.6.1.4.1.476.1.42.3.9.30.1,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleExtendedEntry,,not-accessible,,current,,This entry defines the columns to be populated in the 'lgpFlexibleExtendedTable'.
.1.3.6.1.4.1.476.1.42.3.9.30.1.10,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleEntryIntegerValue,Integer32,read-write,,current,,This is the data point value formatted as a signed integer. This  column is populated only for numerical data points whose type  requires a signed value. To convert this value to the units indicated in the units of  measure columns (lgpFlexibleEntryUnitsOfMeasure or  lgpFlexibleEntryUnitsOfMeasureEnum), divide this value  by 10^n, where n is the value from the  lgpFlexibleEntryDecimalPosition column. For data points that are writable (as designated by the lgpFlexibleEntryAccessibility column), the inverse calculation must done. The desired value must be multiplied by 10^n before it is written to this column, where n is the value  from the lgpFlexibleEntryDecimalPosition column.
.1.3.6.1.4.1.476.1.42.3.9.30.1.20,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleEntryUnsignedIntegerValue,Unsigned32,read-write,,current,,This is the data point value formatted as an unsigned integer. This  column is populated only for numerical data points whose type  does not require a signed value. To convert this value to the units indicated in the units of  measure columns (lgpFlexibleEntryUnitsOfMeasure or  lgpFlexibleEntryUnitsOfMeasureEnum), divide this value  by 10^n, where n is the value from the  lgpFlexibleEntryDecimalPosition column. For data points that are writable (as designated by the lgpFlexibleEntryAccessibility column), the inverse calculation must done. The desired value must be multiplied by 10^n before it is written to this column, where n is the value  from the lgpFlexibleEntryDecimalPosition column.
.1.3.6.1.4.1.476.1.42.3.9.30.1.30,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleEntryDecimalPosition,Unsigned32,read-only,,current,,This is a power of ten divider needed to convert values from the  signed and unsigned integer columns  (lgpFlexibleEntryIntegerValue or  lgpFlexibleEntryUnsignedIntegerValue) to floating  point values. This essentially tells how many positions to move  the decimal point to the left. To convert the integer values to the units indicated in the units  of measure columns (lgpFlexibleEntryUnitsOfMeasure or  lgpFlexibleEntryUnitsOfMeasureEnum), divide the  integer value by 10^n, where n is the value from this column. For data points that are writable (as designated by the lgpFlexibleEntryAccessibility column), the inverse calculation must done. The desired value must be multiplied by 10^n before it is written to the signed or unsigned integer  columns.
.1.3.6.1.4.1.476.1.42.3.9.30.1.40,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleEntryDataType,INTEGER,read-only,,current,not-specified(0):int16(1):uint16(2):int32(3):uint32(4):text(5):enum(6):event16(7):event32(8):ipv4(9):time32(10),The format that the data will appear as. This can be used to determine which field the numerical data will appear in. Data of  type int16 and int32 will appear in the column lgpFlexibleEntryIntegerValue. Data of type uint16,  uint32, and enum, will appear in the column lgpFlexibleEntryUnsignedIntegerValue.
.1.3.6.1.4.1.476.1.42.3.9.30.1.50,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleEntryAccessibility,INTEGER,read-only,,current,not-specified(0):readonly(1):writeonly(2):readwrite(3),This describes the read/write access that is available for the  data in the row.
.1.3.6.1.4.1.476.1.42.3.9.30.1.60,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleEntryUnitsOfMeasureEnum,INTEGER,read-only,,current,not-specified(0):milliSeconds(4096):seconds(4097):minutes(4098):hours(4099):voltsAcRms(4100):milliVoltsAcRms(4101):voltsDc(4102):milliVoltsDc(4103):voltsPeak(4104):voltsPeakToPeak(4105):ampsAcRms(4106):milliAmpsAcRms(4107):ampsDc(4108):milliAmpsDc(4109):voltAmps(4110):kiloVoltAmps(4111):voltAmpsReactive(4112):kVAReactive(4113):watts(4114):kiloWatts(4115):wattHours(4116):kiloWattHour(4117):ampDcHours(4118):hertz(4119):milliHertz(4120):kiloHertz(4121):megaHertz(4122):gigaHertz(4123):percent(4124):degC(4125):degCDelta(4126):degF(4127):degFDelta(4128):psi(4129):pascal(4130):psia(4131):relativeHumidity(4132):thd(4133):days(4134):phase(4135):microOhms(4136):milliOhms(4137):ohms(4138):kiloOhms(4139):megaOhms(4140):bars(4141):rpm(4142):bytes(4143):kilobytes(4144):megabytes(4145):gigabytes(4146):terabytes(4147):voltAmpHours(4148):kiloVoltAmpHours(4149):vaReactiveHours(4150):kVAReactiveHours(4151):meter(4152):feet(4153):cms(4154):cmh(4155):cfs(4156):cfm(4157):lpm(4158):gpmUk(4159):gpmUs(4160):absoluteHumidity(4161):kilograms(4162):cubicMeters(4163):btu(4164):torrs(4165):millitorrs(4166):pounds(4167):mps(4168):fpm(4169):liter(4170):gallonUs(4171):gallonUk(4172):lps(4173):mho(4174):siemensCm(4175):weeks(4176):inWC(4177):btuHours(4178),The unit of measurement that the value will be in.
.1.3.6.1.4.1.476.1.42.3.9.30.1.70,LIEBERT-GP-FLEXIBLE-MIB::lgpFlexibleEntryDataDescription,OCTET,read-only,,current,,A description of the data reported in this row. This is generally  longer and more thorough than the simple label described by  lgpFlexibleEntryDataLabel.
.1.3.6.1.4.1.476.1.42.3.10,LIEBERT-GP-REGISTRATION-MIB::lgpSrc,,,,,,This branch is used to register Liebert system object identifiers.
.1.3.6.1.4.1.476.1.42.3.10.1,LIEBERT-GP-SRC-MIB::lgpSrcTable,,not-accessible,,current,,A table containing information about SRC device.
.1.3.6.1.4.1.476.1.42.3.10.1.1,LIEBERT-GP-SRC-MIB::lgpSrcEntry,,not-accessible,lgpSrcDevId,current,,This entry defines the contents of the rows for the table 'lgpSrcTable'. A row in this table cannot be created or deleted by SNMP operations on columns of the table.
.1.3.6.1.4.1.476.1.42.3.10.1.1.1,LIEBERT-GP-SRC-MIB::lgpSrcDevId,Unsigned32,read-only,,current,,This value must remain constant between agent initializations. This Device ID is used as an index of the table 'lgpSrcTable'.
.1.3.6.1.4.1.476.1.42.3.10.1.1.2,LIEBERT-GP-SRC-MIB::lgpSrcDevAddress,Unsigned32,read-only,,current,,This value must remain constant between agent initializations. This Device Address is used as an index of the table 'lgpSrcTable'.
.1.3.6.1.4.1.476.1.42.3.10.1.1.3,LIEBERT-GP-SRC-MIB::lgpSrcDevState,INTEGER,read-only,,current,enabled(1):standbyOffline(2):unavailableOffline(3):absent(4),Indicates the current state of SRC device. The value of this object is set to enabled(1) if the SRC device has been enabled. The value of this object is set to standbyOffline(2) if the SRC device is waiting for an external action to activate it. The value of this object is set to unavailableOffline(3) if the SRC device is present but cannot be used. The value of this object is set to absent(4) if the SRC device is not present or not detected. The value of this object will be one of the valid device state: enabled(1), standbyOffline(2), unavailableOffline(3), or absent(4).
.1.3.6.1.4.1.476.1.42.3.10.1.1.4,LIEBERT-GP-SRC-MIB::lgpSrcDevTemperatureDegF,INTEGER,read-only,,current,unknown(2147483647),The measured temperature value in Fahrenheit. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).
.1.3.6.1.4.1.476.1.42.3.10.1.1.5,LIEBERT-GP-SRC-MIB::lgpSrcDevTemperatureSetpointDegF,INTEGER,read-write,,current,unknown(2147483647),The temperature setting in Fahrenheit for SRC. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).
.1.3.6.1.4.1.476.1.42.3.10.1.1.6,LIEBERT-GP-SRC-MIB::lgpSrcDevTemperatureDegC,INTEGER,read-only,,current,unknown(2147483647),The measured temperature value in Celsius. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).
.1.3.6.1.4.1.476.1.42.3.10.1.1.7,LIEBERT-GP-SRC-MIB::lgpSrcDevTemperatureSetpointDegC,INTEGER,read-write,,current,unknown(2147483647),The temperature setting in Celsius for SRC. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).
.1.3.6.1.4.1.476.1.42.3.10.1.1.8,LIEBERT-GP-SRC-MIB::lgpSrcDevFanSpeed,INTEGER,read-write,,current,low(1):middle(2):high(3):auto(4):unknown(2147483647),The present fan speed of the SRC device. This object will be one of the valid fan speed: low(1), middle(2), high(3) or auto(4) if the value of lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).
.1.3.6.1.4.1.476.1.42.3.10.1.1.9,LIEBERT-GP-SRC-MIB::lgpSrcDevPowerStatus,INTEGER,read-write,,current,off(0):on(1):unknown(2147483647),The value of this object specifies the power status of SRC device. Power status cannot be configured by an operator. The value of this object is set to off(0) if the SRC device is powered off. The value of this object is set to on(1) if the SRC device is powered on. The value of this object will be one of the valid power status: off(0) or on(1) if lgpSrcDevState is enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).
.1.3.6.1.4.1.476.1.42.3.10.1.1.10,LIEBERT-GP-SRC-MIB::lgpSrcDevOperatingMode,INTEGER,read-write,,current,cooling(0):dehumidify(1):fan(2):ai(3):heating(4):unknown(2147483647),The present operating mode of the SRC device. This object will be one of the valid operating mode: cooling(0), dehumidify(1), fan(2), ai(3) or heating(4) if the value of lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).
.1.3.6.1.4.1.476.1.42.3.10.1.1.11,LIEBERT-GP-SRC-MIB::lgpSrcDevTemperatureHighThresholdDegF,INTEGER,read-write,,current,unknown(2147483647),The high temperature notification threshold. This is the maximum value of 'lgpSrcDevTemperatureDegF' before the agent sends a notification. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).
.1.3.6.1.4.1.476.1.42.3.10.1.1.12,LIEBERT-GP-SRC-MIB::lgpSrcDevTemperatureLowThresholdDegF,INTEGER,read-write,,current,unknown(2147483647),The low temperature notification threshold. This is the minimum value of 'lgpSrcDevTemperatureDegF' before the agent sends a notification. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).
.1.3.6.1.4.1.476.1.42.3.10.1.1.13,LIEBERT-GP-SRC-MIB::lgpSrcDevTemperatureHighThresholdDegC,INTEGER,read-write,,current,unknown(2147483647),The high temperature notification threshold. This is the maximum value of 'lgpSrcDevTemperatureDegC' before the agent sends a notification. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).
.1.3.6.1.4.1.476.1.42.3.10.1.1.14,LIEBERT-GP-SRC-MIB::lgpSrcDevTemperatureLowThresholdDegC,INTEGER,read-write,,current,unknown(2147483647),The low temperature notification threshold. This is the minimum value of 'lgpSrcDevTemperatureDegC' before the agent sends a notification. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).
.1.3.6.1.4.1.476.1.42.4,LIEBERT-GP-REGISTRATION-MIB::lgpProductSpecific,,,,,,This branch is used to register Liebert product specific object identifiers.
.1.3.6.1.4.1.476.1.42.4.2,LIEBERT-GP-REGISTRATION-MIB::lgpUpsProducts,,,,,,This branch is used to register Liebert UPS object identifiers.
.1.3.6.1.4.1.476.1.42.4.2.1,LIEBERT-GP-REGISTRATION-MIB::lgpSeries7200,,,,,,This branch is used to register Liebert Series 7200 UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.2,LIEBERT-GP-REGISTRATION-MIB::lgpUPStationGXT,,,,,,This branch is used to register Liebert UPStationGXT UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.3,LIEBERT-GP-REGISTRATION-MIB::lgpPowerSureInteractive,,,,,,This branch is used to register Liebert PowerSure Interactive UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.4,LIEBERT-GP-REGISTRATION-MIB::lgpNfinity,,,,,,This branch is used to register Liebert Nfinity UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.5,LIEBERT-GP-REGISTRATION-MIB::lgpNpower,,,,,,This branch is used to register Liebert Npower UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.6,LIEBERT-GP-REGISTRATION-MIB::lgpGXT2Dual,,,,,,This branch is used to register Liebert GXT2 Dual Inverter product information.
.1.3.6.1.4.1.476.1.42.4.2.7,LIEBERT-GP-REGISTRATION-MIB::lgpPowerSureInteractive2,,,,,,This branch is used to register Liebert PowerSure Interactive 2 UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.8,LIEBERT-GP-REGISTRATION-MIB::lgpNX,,,,,,This branch is used to register ENPC Nx UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.9,LIEBERT-GP-REGISTRATION-MIB::lgpHiNet,,,,,,This branch is used to register Hiross HiNet UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.10,LIEBERT-GP-REGISTRATION-MIB::lgpNXL,,,,,,This branch is used to register NXL UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.10.1,LIEBERT-GP-REGISTRATION-MIB::lgpNXLJD,,,,,,This branch is used to register information for Liebert NXL-JD UPS products.
.1.3.6.1.4.1.476.1.42.4.2.11,LIEBERT-GP-REGISTRATION-MIB::lgpSuper400,,,,,,This branch is used to register Super 400 UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.12,LIEBERT-GP-REGISTRATION-MIB::lgpSeries600or610,,,,,,This branch is used to register the Liebert Series 600/610 UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.13,LIEBERT-GP-REGISTRATION-MIB::lgpSeries300,,,,,,This branch is used to register the Liebert Series 300 UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.14,LIEBERT-GP-REGISTRATION-MIB::lgpSeries610SMS,,,,,,This branch is used to register the Liebert Series 610 Single Module System (SMS) UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.15,LIEBERT-GP-REGISTRATION-MIB::lgpSeries610MMU,,,,,,This branch is used to register the Liebert Series 610 Multi Module Unit (MMU) UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.16,LIEBERT-GP-REGISTRATION-MIB::lgpSeries610SCC,,,,,,This branch is used to register the Liebert Series 610 System Control Cabinet (SCC) UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.17,LIEBERT-GP-REGISTRATION-MIB::lgpGXT3,,,,,,This branch is used to register Liebert GXT3  product information.
.1.3.6.1.4.1.476.1.42.4.2.18,LIEBERT-GP-REGISTRATION-MIB::lgpGXT3Dual,,,,,,This branch is used to register Liebert GXT3 Dual Inverter product information.
.1.3.6.1.4.1.476.1.42.4.2.19,LIEBERT-GP-REGISTRATION-MIB::lgpNXr,,,,,,This branch is used to register Liebert APM UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.19.1,LIEBERT-GP-REGISTRATION-MIB::lgpITA,,,,,,This branch is used to register information for ITA UPS product.
.1.3.6.1.4.1.476.1.42.4.2.19.2,LIEBERT-GP-REGISTRATION-MIB::lgpNXRb,,,,,,This branch is used to register information for NXRb UPS product.
.1.3.6.1.4.1.476.1.42.4.2.19.3,LIEBERT-GP-REGISTRATION-MIB::lgpNXC,,,,,,This branch is used to register information for NXC(ITAb) UPS product.
.1.3.6.1.4.1.476.1.42.4.2.19.4,LIEBERT-GP-REGISTRATION-MIB::lgpNXC30to40k,,,,,,This branch is used to register information for NXC 30/40k UPS product.
.1.3.6.1.4.1.476.1.42.4.2.19.5,LIEBERT-GP-REGISTRATION-MIB::lgpITA30to40k,,,,,,This branch is used to register information for ITA 30/40k UPS product.
.1.3.6.1.4.1.476.1.42.4.2.20,LIEBERT-GP-REGISTRATION-MIB::lgpAPS,,,,,,This branch is used to register Liebert APS Modular UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.22,LIEBERT-GP-REGISTRATION-MIB::lgpMUNiMx,,,,,,This branch is used to register Liebert UPS with MUNiMx product information.
.1.3.6.1.4.1.476.1.42.4.2.22.1,LIEBERT-GP-REGISTRATION-MIB::lgpNX225to600k,,,,,,This branch is used to register information for Liebert NX UPS products.
.1.3.6.1.4.1.476.1.42.4.2.23,LIEBERT-GP-REGISTRATION-MIB::lgpGXT4,,,,,,This branch is used to register Liebert GXT4  product information.
.1.3.6.1.4.1.476.1.42.4.2.24,LIEBERT-GP-REGISTRATION-MIB::lgpGXT4Dual,,,,,,This branch is used to register Liebert GXT4 Dual Inverter product information.
.1.3.6.1.4.1.476.1.42.4.2.25,LIEBERT-GP-REGISTRATION-MIB::lgpEXL,,,,,,This branch is used to register Liebert eXL UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.26,LIEBERT-GP-REGISTRATION-MIB::lgpEXM,,,,,,This branch is used to register eXM UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.26.1,LIEBERT-GP-REGISTRATION-MIB::lgpEXM208v,,,,,,This branch is used to register information for eXM 208v UPS product.
.1.3.6.1.4.1.476.1.42.4.2.26.2,LIEBERT-GP-REGISTRATION-MIB::lgpEXM400v,,,,,,This branch is used to register information for eXM 400v UPS product.
.1.3.6.1.4.1.476.1.42.4.2.26.3,LIEBERT-GP-REGISTRATION-MIB::lgpEXM480v,,,,,,This branch is used to register information for eXM 480v UPS product.
.1.3.6.1.4.1.476.1.42.4.2.27,LIEBERT-GP-REGISTRATION-MIB::lgpEPM,,,,,,This branch is used to register ePM UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.27.1,LIEBERT-GP-REGISTRATION-MIB::lgpEPM300k,,,,,,This branch is used to register information for ePM 300k UPS product.
.1.3.6.1.4.1.476.1.42.4.2.27.2,LIEBERT-GP-REGISTRATION-MIB::lgpEPM400k,,,,,,This branch is used to register information for ePM 400k UPS product.
.1.3.6.1.4.1.476.1.42.4.2.27.3,LIEBERT-GP-REGISTRATION-MIB::lgpEPM500k,,,,,,This branch is used to register information for ePM 500k UPS product.
.1.3.6.1.4.1.476.1.42.4.2.27.4,LIEBERT-GP-REGISTRATION-MIB::lgpEPM600k,,,,,,This branch is used to register information for ePM 600k UPS product.
.1.3.6.1.4.1.476.1.42.4.2.27.5,LIEBERT-GP-REGISTRATION-MIB::lgpEPM800k,,,,,,This branch is used to register information for ePM 800k UPS product.
.1.3.6.1.4.1.476.1.42.4.2.27.9,LIEBERT-GP-REGISTRATION-MIB::lgpAPM600,,,,,,This branch is used to register information for APM 600 UPS product.
.1.3.6.1.4.1.476.1.42.4.2.28,LIEBERT-GP-REGISTRATION-MIB::lgpEXLS1,,,,,,This branch is used to register Liebert eXL S1 UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.28.1,LIEBERT-GP-REGISTRATION-MIB::lgpEXLS1UPS,,,,,,This branch is used to register information for EXL S1 UPS product.
.1.3.6.1.4.1.476.1.42.4.2.29,LIEBERT-GP-REGISTRATION-MIB::lgpEXMMSR,,,,,,This branch is used to register eXM M/S/R UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.29.2,LIEBERT-GP-REGISTRATION-MIB::lgpAPM600GHMI,,,,,,This branch is used to register information for the APM 600 GHMI product.
.1.3.6.1.4.1.476.1.42.4.2.29.3,LIEBERT-GP-REGISTRATION-MIB::lgpEPMGHMI,,,,,,This branch is used to register information for the EPM 600 GHMI product.
.1.3.6.1.4.1.476.1.42.4.2.31,LIEBERT-GP-REGISTRATION-MIB::lgpITA2,,,,,,This branch is used to register ITA2 UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.31.1,LIEBERT-GP-REGISTRATION-MIB::lgpITA2cap20k,,,,,,This branch is used to register ITA2 20k UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.31.2,LIEBERT-GP-REGISTRATION-MIB::lgpITA2cap40k,,,,,,This branch is used to register ITA2 40k UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.31.3,LIEBERT-GP-REGISTRATION-MIB::lgpEXSRackMountAndFrame1,,,,,,This branch is used to register EXS Rack Mount and Frame 1 product information.
.1.3.6.1.4.1.476.1.42.4.2.31.4,LIEBERT-GP-REGISTRATION-MIB::lgpGXE,,,,,,This branch is used to register GXE product information.
.1.3.6.1.4.1.476.1.42.4.2.31.5,LIEBERT-GP-REGISTRATION-MIB::lgpITA2cap5k30k,,,,,,This branch is used to register ITA2 5k-30k UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.32,LIEBERT-GP-REGISTRATION-MIB::lgpEXS,,,,,,This branch is used to register EXS UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.32.2,LIEBERT-GP-REGISTRATION-MIB::lgpEXSFr45,,,,,,This branch is used to register EXS Frame 4/5 product information.
.1.3.6.1.4.1.476.1.42.4.2.33,LIEBERT-GP-REGISTRATION-MIB::lgpPowerSureInteractive5,,,,,,This branch is used to register Liebert PowerSure Interactive 5 UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.34,LIEBERT-GP-REGISTRATION-MIB::lgpGXT5,,,,,,This branch is used to register Liebert GXT5 UPS product information.
.1.3.6.1.4.1.476.1.42.4.2.38,LIEBERT-GP-REGISTRATION-MIB::lgpEXM2,,,,,,This branch is used to register EXM 2.0 product information.
.1.3.6.1.4.1.476.1.42.4.2.39,LIEBERT-GP-REGISTRATION-MIB::lgpTrinergyCube,,,,,,This branch is used to register Liebert TrinergyCube product information.
.1.3.6.1.4.1.476.1.42.4.2.40,LIEBERT-GP-REGISTRATION-MIB::lgpEdgeUPS,,,,,,This branch is used to register Vertiv Edge (PSI6) UPS product information.
.1.3.6.1.4.1.476.1.42.4.3,LIEBERT-GP-REGISTRATION-MIB::lgpAcProducts,,,,,,This branch is used to register Liebert Environmental object identifiers.
.1.3.6.1.4.1.476.1.42.4.3.1,LIEBERT-GP-REGISTRATION-MIB::lgpAdvancedMicroprocessor,,,,,,This branch is used to register Liebert Environmental Advanced Microprocessor control information.
.1.3.6.1.4.1.476.1.42.4.3.2,LIEBERT-GP-REGISTRATION-MIB::lgpStandardMicroprocessor,,,,,,This branch is used to register Liebert Environmental Standard Microprocessor control information.
.1.3.6.1.4.1.476.1.42.4.3.3,LIEBERT-GP-REGISTRATION-MIB::lgpMiniMate2,,,,,,This branch is used to register Liebert Environmental Mini-Mate 2 product information.
.1.3.6.1.4.1.476.1.42.4.3.4,LIEBERT-GP-REGISTRATION-MIB::lgpHimod,,,,,,This branch is used to register Liebert Environmental Himod product information.
.1.3.6.1.4.1.476.1.42.4.3.5,LIEBERT-GP-REGISTRATION-MIB::lgpCEMS100orLECS15,,,,,,This branch is used to register Australia Environmental CEMS100 and LECS15 control information.
.1.3.6.1.4.1.476.1.42.4.3.6,LIEBERT-GP-REGISTRATION-MIB::lgpIcom,,,,,,This branch is used to register the Environmental iCOM control information.
.1.3.6.1.4.1.476.1.42.4.3.7,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPA,,,,,,This branch is used to register information for the  Liebert PA (Floor mount) Environmental product family.
.1.3.6.1.4.1.476.1.42.4.3.7.1,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeDS,,,,,,This branch is used to register information for  DS Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.2,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeHPM,,,,,,This branch is used to register information for  HPM Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.3,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeChallenger,,,,,,This branch is used to register information for  Liebert Challenger Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.4,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypePeX,,,,,,This branch is used to register information for  Liebert PeX Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.5,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeDeluxeSys3,,,,,,This branch is used to register information for  Liebert Deluxe Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.5.1,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeDeluxeSystem3,,,,,,This branch is used to register information for  Liebert Deluxe System 3 and lower Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.5.2,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeCW,,,,,,This branch is used to register information for  Liebert CW146 and lower Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.6,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeJumboCW,,,,,,This branch is used to register information for  Liebert CW181 and larger Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.7,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeDSE,,,,,,This branch is used to register information for  Liebert DSE Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.7.1,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeDSE400,,,,,,This branch is used to register information for  Liebert DSE 400 products.
.1.3.6.1.4.1.476.1.42.4.3.7.7.2,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeDP060,,,,,,This branch is used to register information for  Liebert DP 060 products.
.1.3.6.1.4.1.476.1.42.4.3.7.8,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypePEXS,,,,,,This branch is used to register information for  Liebert PDX - PCW Small Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.8.1,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypePDXsmall,,,,,,This branch is used to register information for  Liebert PDX Small Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.8.2,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypePCWsmall,,,,,,This branch is used to register information for  Liebert PCW Small Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.9,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypePDX,,,,,,This branch is used to register information for  Liebert PDX - PCW Large Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.9.1,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypePDXlarge,,,,,,This branch is used to register information for  Liebert PDX Large Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.9.2,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypePCWlarge,,,,,,This branch is used to register information for  Liebert PCW Large Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.10,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeHPS,,,,,,This branch is used to register information for  Liebert HPS Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.7.11,LIEBERT-GP-REGISTRATION-MIB::lgpMiniMate3,,,,,,This branch is used to register Liebert Environmental Mini-Mate 3 product information.
.1.3.6.1.4.1.476.1.42.4.3.7.12,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeXDU,,,,,,This branch is used to register Liebert Environmental XDU product information.
.1.3.6.1.4.1.476.1.42.4.3.7.13,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeXDM,,,,,,This branch is used to register Liebert Environmental XDM product information.
.1.3.6.1.4.1.476.1.42.4.3.7.14,LIEBERT-GP-REGISTRATION-MIB::lgpIcomPAtypeCWA,,,,,,This branch is used to register Liebert Environmental CWA product information.
.1.3.6.1.4.1.476.1.42.4.3.8,LIEBERT-GP-REGISTRATION-MIB::lgpIcomXD,,,,,,This branch is used to register information for the  Liebert XD (Rack cooling with compressor) Environmental product family.
.1.3.6.1.4.1.476.1.42.4.3.8.1,LIEBERT-GP-REGISTRATION-MIB::lgpIcomXDtypeXDF,,,,,,This branch is used to register information for  Liebert XDF Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.8.2,LIEBERT-GP-REGISTRATION-MIB::lgpIcomXDtypeXDFN,,,,,,This branch is used to register information for  Liebert XDFN Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.9,LIEBERT-GP-REGISTRATION-MIB::lgpIcomXP,,,,,,This branch is used to register information for the  Liebert XP (Pumped refrigerant) Environmental product family.
.1.3.6.1.4.1.476.1.42.4.3.9.1,LIEBERT-GP-REGISTRATION-MIB::lgpIcomXPtypeXDP,,,,,,This branch is used to register information for  Liebert XDP Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.9.1.1,LIEBERT-GP-REGISTRATION-MIB::lgpIcomXPtypeXDPCray,,,,,,This branch is used to register information for  Liebert XDP Environmental products for Cray.
.1.3.6.1.4.1.476.1.42.4.3.9.2,LIEBERT-GP-REGISTRATION-MIB::lgpIcomXPtypeXDC,,,,,,This branch is used to register information for  Liebert XDC Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.9.3,LIEBERT-GP-REGISTRATION-MIB::lgpIcomXPtypeXDPW,,,,,,This branch is used to register information for  Liebert XDP-W Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.10,LIEBERT-GP-REGISTRATION-MIB::lgpIcomSC,,,,,,This branch is used to register information for the  Liebert SC (Chiller) Environmental product family.
.1.3.6.1.4.1.476.1.42.4.3.10.1,LIEBERT-GP-REGISTRATION-MIB::lgpIcomSCtypeHPC,,,,,,This branch is used to register information for  Liebert HPC Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.10.1.1,LIEBERT-GP-REGISTRATION-MIB::lgpIcomSCtypeHPCSSmall,,,,,,This branch is used to register information for  Liebert HPC-S Small.
.1.3.6.1.4.1.476.1.42.4.3.10.1.2,LIEBERT-GP-REGISTRATION-MIB::lgpIcomSCtypeHPCSLarge,,,,,,This branch is used to register information for  Liebert HPC-S Large.
.1.3.6.1.4.1.476.1.42.4.3.10.1.3,LIEBERT-GP-REGISTRATION-MIB::lgpIcomSCtypeHPCR,,,,,,This branch is used to register information for Liebert HPC-R.
.1.3.6.1.4.1.476.1.42.4.3.10.1.4,LIEBERT-GP-REGISTRATION-MIB::lgpIcomSCtypeHPCM,,,,,,This branch is used to register information for Liebert HPC-M.
.1.3.6.1.4.1.476.1.42.4.3.10.1.5,LIEBERT-GP-REGISTRATION-MIB::lgpIcomSCtypeHPCL,,,,,,This branch is used to register information for Liebert HPC-L.
.1.3.6.1.4.1.476.1.42.4.3.10.1.6,LIEBERT-GP-REGISTRATION-MIB::lgpIcomSCtypeHPCW,,,,,,This branch is used to register information for Liebert HPC-W.
.1.3.6.1.4.1.476.1.42.4.3.11,LIEBERT-GP-REGISTRATION-MIB::lgpIcomCR,,,,,,This branch is used to register information for the  Liebert CR (Computer Row) Environmental product family.
.1.3.6.1.4.1.476.1.42.4.3.11.1,LIEBERT-GP-REGISTRATION-MIB::lgpIcomCRtypeCRV,,,,,,This branch is used to register information for  Liebert CRV Environmental products.
.1.3.6.1.4.1.476.1.42.4.3.12,LIEBERT-GP-REGISTRATION-MIB::lgpIcomAH,,,,,,This branch is used to register information for the  Liebert AH (Air Handler) Environmental product family.
.1.3.6.1.4.1.476.1.42.4.3.12.1,LIEBERT-GP-REGISTRATION-MIB::lgpIcomAHStandard,,,,,,This branch is used to register information for  Liebert AH Standard (Air Handler).
.1.3.6.1.4.1.476.1.42.4.3.13,LIEBERT-GP-REGISTRATION-MIB::lgpIcomDCL,,,,,,This branch is used to register information for the  Liebert DCL Environmental product family.
.1.3.6.1.4.1.476.1.42.4.3.14,LIEBERT-GP-REGISTRATION-MIB::lgpIcomEEV,,,,,,This branch is used to register information for the  Liebert EEV Environmental product family.
.1.3.6.1.4.1.476.1.42.4.3.30,LIEBERT-GP-REGISTRATION-MIB::lgpIproAFC,,,,,,This branch is used to register information for the  Liebert AFC Environmental product family.
.1.3.6.1.4.1.476.1.42.4.3.31,LIEBERT-GP-REGISTRATION-MIB::lgpIproEFC,,,,,,This branch is used to register information for the  Liebert EFC Environmental product family.
.1.3.6.1.4.1.476.1.42.4.3.32,LIEBERT-GP-REGISTRATION-MIB::lgpCpcoPDX,,,,,,This branch is used to register information for the  Liebert PDX Environmental product family.
.1.3.6.1.4.1.476.1.42.4.4,LIEBERT-GP-REGISTRATION-MIB::lgpPowerConditioningProducts,,,,,,This branch is used to register Liebert Power Conditioning object identifiers.
.1.3.6.1.4.1.476.1.42.4.4.1,LIEBERT-GP-REGISTRATION-MIB::lgpPMP,,,,,,This branch is used to register Liebert Power Distribution product information for the PMP (Power Monitoring Panel) product.
.1.3.6.1.4.1.476.1.42.4.4.2,LIEBERT-GP-REGISTRATION-MIB::lgpEPMP,,,,,,This branch is used to register Liebert Power Distribution product information for the EPMP (Extended Power Monitoring Panel) product.
.1.3.6.1.4.1.476.1.42.4.5,LIEBERT-GP-REGISTRATION-MIB::lgpTransferSwitchProducts,,,,,,This branch is used to register Liebert Transfer Switch object identifiers.
.1.3.6.1.4.1.476.1.42.4.5.1,LIEBERT-GP-REGISTRATION-MIB::lgpStaticTransferSwitchEDS,,,,,,This branch is used to register Liebert Transfer Switch product information for the EDS Static Transfer Switch product.
.1.3.6.1.4.1.476.1.42.4.5.2,LIEBERT-GP-REGISTRATION-MIB::lgpStaticTransferSwitch1,,,,,,This branch is used to register Liebert Transfer Switch product information for the Static Transfer Switch 1 product.
.1.3.6.1.4.1.476.1.42.4.5.3,LIEBERT-GP-REGISTRATION-MIB::lgpStaticTransferSwitch2,,,,,,This branch is used to register Liebert Transfer Switch product information for the Static Transfer Switch 2 product.
.1.3.6.1.4.1.476.1.42.4.5.4,LIEBERT-GP-REGISTRATION-MIB::lgpStaticTransferSwitch2FourPole,,,,,,This branch is used to register Liebert Transfer Switch product information for the Static Transfer Switch 2 - 4Pole product.
.1.3.6.1.4.1.476.1.42.4.7,LIEBERT-GP-REGISTRATION-MIB::lgpMultiLinkProducts,,,,,,This branch is used to register Liebert MultiLink object identifiers.
.1.3.6.1.4.1.476.1.42.4.7.1,LIEBERT-GP-REGISTRATION-MIB::lgpMultiLinkBasicNotification,,,,,,This branch is used to register Liebert MultiLink MLBN device proxy information.
.1.3.6.1.4.1.476.1.42.4.8,LIEBERT-GP-REGISTRATION-MIB::lgpPowerDistributionProducts,,,,,,This branch is used to register stand-alone Liebert Power Distribution object identifiers.
.1.3.6.1.4.1.476.1.42.4.8.2,LIEBERT-GP-REGISTRATION-MIB::lgpRackPDU,,,,,,This branch is used to register Liebert Power Distribution product information for Rack Power Distribution Products (RPDU).
.1.3.6.1.4.1.476.1.42.4.8.2.1,LIEBERT-GP-REGISTRATION-MIB::lgpMPX,,,,,,This branch is used to register Liebert Power Distribution product information for the MPX product distribution (PDU) product family.
.1.3.6.1.4.1.476.1.42.4.8.2.2,LIEBERT-GP-REGISTRATION-MIB::lgpMPH,,,,,,This branch is used to register Liebert Power Distribution product information for the MPH product distribution (PDU) product family.
.1.3.6.1.4.1.476.1.42.4.8.4,LIEBERT-GP-REGISTRATION-MIB::lgpRackPDU2,,,,,,This branch is used to register Liebert Power Distribution product information for Rack Power Distribution Products (RPDU).
.1.3.6.1.4.1.476.1.42.4.8.4.1,LIEBERT-GP-REGISTRATION-MIB::lgpRPC2kMPX,,,,,,This branch is used to register Liebert Power Distribution product information for the MPX product distribution (PDU) product family.
.1.3.6.1.4.1.476.1.42.4.8.4.2,LIEBERT-GP-REGISTRATION-MIB::lgpRPC2kMPH,,,,,,This branch is used to register Liebert Power Distribution product information for the MPH product distribution (PDU) product family.
.1.3.6.1.4.1.476.1.42.4.10,LIEBERT-GP-REGISTRATION-MIB::lgpCombinedSystemProducts,,,,,,This branch is used to register object identifiers for Combined System devices.
.1.3.6.1.4.1.476.1.42.4.10.1,LIEBERT-GP-REGISTRATION-MIB::lgpPMPandLDMF,,,,,,This branch is used to register Liebert Combined PMP version 4/LDMF Product information.
.1.3.6.1.4.1.476.1.42.4.10.1.1,LIEBERT-GP-REGISTRATION-MIB::lgpPMPgeneric,,,,,,This branch is used to register information for  Liebert PMP version 4.
.1.3.6.1.4.1.476.1.42.4.10.1.2,LIEBERT-GP-REGISTRATION-MIB::lgpPMPonFPC,,,,,,This branch is used to register information for  Liebert PMP version 4 for FPC.
.1.3.6.1.4.1.476.1.42.4.10.1.3,LIEBERT-GP-REGISTRATION-MIB::lgpPMPonPPC,,,,,,This branch is used to register information for  Liebert PMP version 4 for PPC.
.1.3.6.1.4.1.476.1.42.4.10.1.4,LIEBERT-GP-REGISTRATION-MIB::lgpPMPonFDC,,,,,,This branch is used to register information for  Liebert PMP version 4 for FDC.
.1.3.6.1.4.1.476.1.42.4.10.1.5,LIEBERT-GP-REGISTRATION-MIB::lgpPMPonRDC,,,,,,This branch is used to register information for  Liebert PMP version 4 for RDC.
.1.3.6.1.4.1.476.1.42.4.10.1.6,LIEBERT-GP-REGISTRATION-MIB::lgpPMPonEXC,,,,,,This branch is used to register information for  Liebert PMP version 4 for EXC.
.1.3.6.1.4.1.476.1.42.4.10.1.7,LIEBERT-GP-REGISTRATION-MIB::lgpPMPonSTS2,,,,,,This branch is used to register information for  Liebert PMP version 4 for STS2.
.1.3.6.1.4.1.476.1.42.4.10.1.8,LIEBERT-GP-REGISTRATION-MIB::lgpPMPonSTS2PDU,,,,,,This branch is used to register information for  Liebert PMP version 4 for STS2/PDU.
.1.3.6.1.4.1.476.1.42.4.10.3,LIEBERT-GP-REGISTRATION-MIB::lgpPM5,,,,,,This branch is used to register Liebert PM version 5.
.1.3.6.1.4.1.476.1.42.4.12,LIEBERT-GP-REGISTRATION-MIB::lgpAcPACCProducts,,,,,,This branch is used to register Environmental PACC Control  Product object identifiers.
.1.3.6.1.4.1.476.1.42.4.12.1,LIEBERT-GP-REGISTRATION-MIB::lgpCRD,,,,,,This branch is used to register CRD information.
.1.3.6.1.4.1.476.1.42.4.12.1.1,LIEBERT-GP-REGISTRATION-MIB::lgpCRD010,,,,,,This branch is used to register information for CRD010.
.1.3.6.1.4.1.476.1.42.4.12.2,LIEBERT-GP-REGISTRATION-MIB::lgpCR,,,,,,This branch is used to register CR information.
.1.3.6.1.4.1.476.1.42.4.12.2.1,LIEBERT-GP-REGISTRATION-MIB::lgpCR012,,,,,,This branch is used to register information for CR012.
.1.3.6.1.4.1.476.1.42.4.12.2.2,LIEBERT-GP-REGISTRATION-MIB::lgpCR025,,,,,,This branch is used to register information for CR025.
.1.3.6.1.4.1.476.1.42.4.12.2.3,LIEBERT-GP-REGISTRATION-MIB::lgpCR030,,,,,,This branch is used to register information for CR030.
.1.3.6.1.5,SNMPv2-SMI::security,,,,,,
.1.3.6.1.6,SNMPv2-SMI::snmpV2,,,,,,
.1.3.6.1.6.1,SNMPv2-SMI::snmpDomains,,,,,,
.1.3.6.1.6.2,SNMPv2-SMI::snmpProxys,,,,,,
.1.3.6.1.6.3,SNMPv2-SMI::snmpModules,,,,,,